User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 7-15
7.5.3 Input 2 setting mode (SET 02)
Setting data
Character
Setting (monitor) value
Initial value
Unit
Setting
value
Blind
Input type
INP2
16: 0 - 1 VDC
17: 0 - 5 VDC
18: 1 - 5 VDC
19: 0 - 10 VDC
20: 4 - 20 mADC
18
None
Scaling upper limit
FSH2
FSL 2 to SV setting range upper
limit
1200
Scaling lower limit
FSL2
SV setting range lower limit to
FSH 2
0
PV compensation
gain
PVG2
0.500 to 2.000
1.000
Times
PV compensation
zero
PVS2
-999 to 999
0
Digit
PV filter
PdF2
0.0 to 99.9
0.0
Second
Local/remote
switchover
LR
0: Local
1: Remote 1
(Scaled with SLL , SLH )
2: Remote 2
(Scaled with FSL 2, FSH 2)
0
None
7.5.4 Key function setting mode (SET 03)
Setting data
Character
Setting (monitor) value
Initial value
Unit
Setting
value
Blind
Function key 1
function
Function key 2
function
Function key 3
function
Function key 4
function
Function key 5
function
FU1
to
FU5
*0: No function
*1: Digit shift
*2: Control mode (MD)/control
stop (RDY)
*3: AT start/AT stop
*4: Timer start/stop
*5: Screen reverse feed
*6: ENT
*7: Bank switchover
*8: AUTO/MANUAL
*9: SV/MV screen switchover
*A: Constant value run mode/
Program mode switchover *1
*B: Step feed *1
*C: Pause *1
*d: SET 22 call-up function *1
0.0
None
0*: None
1*: Pressing time of 1 second
2*: Pressing time of 2 seconds
3*: Pressing time of 3 seconds
4*: Pressing time of 4 seconds
5*: Pressing time of 5 seconds
Second
Key lock
LoC
0: Lock OFF
1: Lock all
2: Lock of run mode
3: Lock of other than run mode
4: Lock all (only during a run) *1
5: Lock of run mode (only during
a run) *1
6: Lock of other than run mode
(only during a run) *1
7: Lock of parameter mode (only
during a run) *1
0
None
*1: Selectable only on Ver3.xx or later