User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 7-16
7.5.5 Control setting mode (SET 04) (1/4)
Setting data
Character
Setting (monitor) value
Initial value
Unit
Setting
value
Blind
Bank switchover
bANK
0: Bank 0
0
None
1: Bank 1
2: Bank 2
3: Bank 3
4: Bank 4
5: Bank 5
6: Bank 6
7: Bank 7
Bank upper limit
setting
bANKH
0 to 7
7
None
Control setting
SV
SLL to SLH
0
C
SV limiter upper limit
SLH
Temperature:
(SLL + 5.0) to SV setting range
upper limit
(SLL + 5) to SV setting range
upper limit
Analog:
(SLL + 50) to SV setting range
upper limit
1200
C
Digit
SV limiter lower limit
SLL
Temperature:
SV setting range lower limit to
(SLH - 5.0)
SV setting range lower limit to
(SLH - 5)
Analog:
SV setting range lower limit to
(SLH - 50)
0
C
Digit
Control mode
Md
RDY: Control stop
RUN: Control start
MAN: Manual
TIME 1: Timer 1 operation
TIME 2: Timer 2 operation
TIME 3: Timer 3 operation
RUN
None
Control type
CNt
0: Primary nonexistent
Secondary nonexistent
1: Primary PID control
Secondary nonexistent
2: Primary ON/OFF control
Secondary nonexistent
3: Primary PID control
Secondary PID control
4: Primary PID control
Secondary ON/OFF control
5: Primary ON/OFF control
Secondary ON/OFF control
6: Primary position proportional
Secondary position
proportional
1
None