User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 7-28
7.5.11 Communication setting mode (SET 17)
Setting data
Character
Setting (monitor) value
Initial value
Unit
Setting
value
Blind
Communication
protocol
PRt
0: TOHO
1: MODBUS (RTU)
2: MODBUD (ASCII)
0
None
Communication
parameter
CoM
***1: 1 bit
***2: 2 bits
**N*: Nonexistent
**o*: Odd No.
**E*: Even No.
*7**: 7 bits*2
*8**: 8 bits
N***: Without BCC *3
b***: With BCC *3
Caution:
For MODBUS (RTU), only 8N1,
8N2, 8o1, 8o2, 8E1 and 8E2 are
settable.
For MODBUS (ASCII), only 7N1,
7N2, 7o1, 7o2, 7E1, 7E2, 8N1,
8N2, 8o1, 8o2, 8E1 and 8E2 are
settable.
b8N2
None
Communication
speed
bPS
2.4: 2400
4.8: 4800
9.6: 9600
19.2: 19200
38.4: 38400
9.6
bps
Communication
address
AdR
TOHO: 1 to 99
MODBUS: 1 to 247
1
Station
Response delay
time in
communication
AWt
0 to 250
0
ms
Communication
switchover
Mod
0: Write inhibit
1: Writable
2: Concurrent temperature ascent
master
3: Concurrent temperature ascent
slave
1
*2: “Modbus (RTU)” should not be set.
*3: Only TOHO protocol can be set.