User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 5-17
5.3.6 Excessive ascent prevention unit (alarm unit) setting
★ Setting for the excessive ascent prevention unit
Setting to use the OUT 1 (output 1) as the excessive ascent prevention unit in constant value run mode
Hold MODE key pressed for 2 seconds.
Constant value run mode screen
PV value (present value)
SV value (target value)
Press the ▲ key four times. Press it, however, three times for TTM-204.
Input 1 setting screen
Each set screen
Each setting mode
OUT 1(output 1) setting screen
Hold MODE key pressed for 2 seconds.
Each set screen
Each setting mode
Press MODE key once.
S05-1 Target connection selection screen
* Target connection is set in this screen.
* Use the ▲/▼ key for the setting.
* The value is set at “0” at factory shipment.
Changing the setting from “0” to “2” results in the event output.
S05-2 Event function 1 setting screen
Press MODE key once.
Press MODE key once.
* Event function is set in this screen.
* Use the ▲/▼ key for the setting.
* The value is set at “000” at factory shipment.
Set the screen “006” or “016” for the use of the excessive ascent prevention unit
(alarm unit). In case of the setting of “016,” the displayed value may exceed the
target value, and it stays as is even when it decreases below the target value.
The setting is reset by turning on the power again.
S05-3 Event upper limit setting mode
* Event upper limit is set in this screen.
* Use the ▲/▼ key for the setting.
* The value is set at “0” at factory shipment.
Set a specific target value.
* Holding the MODE key pressed for 2 seconds moves each setting screen to the run mode screen.
* In about 2 minutes, each setting screen (or any setting screen) automatically moves back to the run mode
screen.