User Manual
Table Of Contents
- TTM-200シリーズユーザーズマニュアル 英語 48-7009-D.pdfから挿入したしおり
- TOP
- Contents
- 2. Installation
- 3. Wiring
- 4. Basic operation
- 5. Operating the equipment
- 5.1 Precautions on operating the equipment
- 5.2 Operating monitor display
- 5.3 How to set run settings
- 5.4 How to set each function and description of function
- 5.5 Explanation of the program run function
- 5.5.1 Operation flow of the program run
- 5.5.2 SET 21 program function setting
- 5.5.3 SET 21 program function setting screen
- 5.5.4 SET 22 program setting
- 5.5.5 SET 22 program setting screen
- 5.5.6 Explanation of the screen display and operation of a program run
- 5.5.7 Complementary explanation of the program run
- 5.6 Explanation of the bank automatic switching function
- 6. Explanation on parameters
- 6.1 Input 1 type setting
- 6.2 Remote SV input type setting
- 6.3 Function key function setting
- 6.4 Control function setting
- 6.5 Output (from OUT 1 to OUT 7) type setting
- 6.6 Current transformer (CT) setting
- 6.7 DI setting
- 6.8 Timer function setting
- 6.9 Communication function setting
- 6.10 Initial setting
- 6.11 Priority screen setting
- 6.12 Bank function setting
- 6.13 PROGRAM FUNCTION SETTING
- 6.14 PROGRAM SETTING
- 6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING
- 7. Appendix
- 7.1 Product specifications
- 7.2 Accessories
- 7.3 Error (abnormality) display
- 7.4 Troubleshooting
- 7.5 Setting list
- 7.5.1 Run mode
- 7.5.2 Input 1 setting mode (SET 01)
- 7.5.3 Input 2 setting mode (SET 02)
- 7.5.4 Key function setting mode (SET 03)
- 7.5.5 Control setting mode (SET 04) (1/4)
- 7.5.6 OUT 1 and 2 setting modes (SET 05 and 06) (1/3)
- 7.5.7 OUT 3 to 7 setting modes (SET 07, 08, 09, 10 and 11) (1/2)
- 7.5.8 CT setting mode (SET 12)
- 7.5.9 DI setting mode (SET 13)
- 7.5.10 Timer 1 to 3 setting modes (SET 14, 15 and 16)
- 7.5.11 Communication setting mode (SET 17)
- 7.5.12 Initial setting mode (SET 18)
- 7.5.13 Priority screen setting mode (SET 19)
- 7.5.14 Bank setting mode (SET 20)
- 7.5.15 Program function setting mode (SET 21)
- 7.5.16 Program setting mode (SET 22)
- 7.5.17 Bank automatic switching function setting mode (SET 23)

48-7009-E 5-18
5.3.7 Event setting
★ Setting the event setting value (alarm value)
When setting OUT 2 for the event setting value (alarm value)
Setting condition: Deviation lower limit, with standby function, 30 °C and sensitivity of 1 °C (no
other functions)
This setting is not possible in case that no selection is made for outputs as an option.
Hold MODE key pressed for 2 seconds.
For constant value run mode screen:
PV value (present value)
SV value (target value)
Press the ▲ key five times. Press it, however, four times for TTM-204
Input 1 setting screen
Each set screen
Each setting mode
OUT 2 (output 2) setting screen
Hold MODE key pressed for 2 seconds.
Each set screen
Each setting mode
Press MODE key twice.
S06-2 Event function 1 setting screen
* Event functions are set in this screen.
* Use the ▲/▼ key for the setting.
* The value is set at “000” at factory shipment.
Setting “000” to “023” results in the type of alarm for the deviation lower limit and standby
function.
Deviation lower limit: Range from the setting value (SV) being set
Standby function: Function that no alarm is generated until a value exceeds the alarm range.
Press MODE key once.
S06-4 Event lower setting screen
* Event lower target value is set in this screen.
* Use the ▲/▼ key for the setting.
* The value is set at “0” at factory shipment.
Setting “0” to “30” results in setting the deviation lower limit alarm value to 30 °C.
An alarm is generated in case that a value reaches 30 °C below the setting value (SV).
Example: SV = 200 °C and lower limit alarm = 170 °C or lower
Press MODE key six times.
Continued to the next page
For program run mode screen:
PV value (present value)
SV value (PRoG)
Hold MODE key pressed for 2 seconds.
Setting mode is the same as that for Hereinafter,
to the input 1 setting screen similarly to that for
the constant value run mode