Service Manual

Table Of Contents
Reelmaster 7000−D Page 6 − 65 Electrical System
Battery Testing
1. Conduct a hydrometer test of the battery electrolyte.
IMPORTANT: Make sure the area around the cells is
clean before opening the battery caps.
A. Measure the specific gravity of each cell with a
hydrometer. Draw electrolyte in and out of the
hydrometer barrel prior to taking a reading to warm−
up the hydrometer. At the same time take the tem-
perature of the cell.
B. Temperature correct each cell reading. For each
10
o
F (6C) above 80F (27C) add 0.004 to the specific
gravity reading. For each 10F (6C) below 80F (27C)
subtract 0.004 from the specific gravity reading.
Example: Cell Temperature 100F
Cell Gravity 1.245
100F minus 80F equals 20F
(38C minus 27C equals 11C)
20F multiply by 0.004/10F equals 0.008
(11C multiply by 0.004/6C equals 0.008)
ADD (conversion above) 0.008
Correction to 80F (27C) 1.253
C. If the difference between the highest and lowest
cell specific gravity is 0.050 or greater or the lowest
cell specific gravity is less than 1.225, charge the bat-
tery. Charge at the recommended rate and time giv-
en in Battery Charging or until all cells specific
gravity is 1.225 or greater with the difference in spe-
cific gravity between the highest and lowest cell less
than 0.050. If these charging conditions can not be
met, replace the battery.
2. Perform a high−discharge test with an adjustable
load tester.
This is one of the most reliable means of testing a battery
as it simulates the cold−cranking test. A commercial bat-
tery load tester is required to perform this test.
CAUTION
Follow the battery load tester manufacturers
instructions when using a load tester.
A. Check the voltage across the battery terminals
prior to testing the battery. If the voltage is less than
12.4 VDC, recharge the battery.
B. If the battery has been charged, apply a 150 amp
load for fifteen (15) seconds to remove the surface
charge. Use a battery load tester following the
manufacturer’s instructions.
C. Make sure battery terminals are free of corrosion.
D. Measure the temperature of the center battery
cell.
E. Connect a battery load tester to the battery termi-
nals following the load tester manufacturer’s in-
structions. Connect a digital multimeter to the
battery terminals.
F. Apply a test load of 330 amps (one half the Crank-
ing Performance rating of the battery) for fifteen (15)
seconds.
G. Take a battery voltage reading after the load has
been applied to the battery for fifteen (15) seconds,
then remove the load. Record the voltage reading.
H. Using the table below, determine the minimum
voltage for the cell temperature reading:
Minimum
Voltage
Battery Electrolyte
Temperature
9.6 70F (and up) 21C (and up)
9.5 60F 16C
9.4 50F 10C
9.3 40F 4C
9.1 30F −1C
8.9 20F −7C
8.7 10F −12C
8.5 0F −18C
I. If the test voltage is below the minimum, replace
the battery. If the test voltage is at or above the mini-
mum, return the battery to service.
Electrical
System