Installation Instructions

I
nstallation Guidelines
Note the flow direction arrow in the side of the valve body
and install accordingly.
The valve can be installed at any angle without affecting
operation.
Use direct-burial irrigation control wire for connection from
the controller to valves.
Leave a 12" wire expansion loop at each valve location on
long-run wire lengths.
Waterproof wire splice connectors are absolutely essential
for proper electric control system operation. Follow the
installation instructions provided by the connector
manufacturer for optimum performance.
Valve Adjustment Procedures
Close the valve by turning the Flow Control Handle fully clockwise, just until
resistance is felt - do not overtighten!
Remove the EZReg dial protective cover (if installed). Turn the control dial
until the pointer indicates the desired downstream pressure (5 to 100 psi).
Note: One revolution of the control dial adjusts the pressure setting
approximately 10 psi. A minimum of 10 psi pressure differential between
the valve inlet and outlet is required for proper EZReg operation.
Pressurize the main supply line to the valve. Confirm that all pipe connections
are properly sealed.
Actuate the valve either electrically at the controller, or manually by turning
the Manual Bleed knob counterclockwise sloely until the valve opens.
Turn the Flow Control Handle slowly counterclockwise to adjust sprinkler
operation.
To confirm outlet pressure, remove the poppet valve cap, located directly
below the EZReg. Attach a water-pressure test gauge to the poppet valve
for a direct reading. Adjust pressure as preferred.
Important: The EZReg assembly can be removed for service while
the valve is pressurized. However, the valve must not be operated with
the EZReg assembly removed.
Close Manual Bleed knob (if necessary) to close valve.
© 2009 The Toro Company, Irrigation Division www.toro.com Form Number 373-0544 Rev. A
Manual Bleed
Knob
Flow Control
Handle
EZReg Dial
Poppet
Valve
Common Wire
G
auge Size
Control Wire Gauge Size
Note: Values indicate maximum one-way distance ( in feet) between controller
and valve solenoid under the followig conditions: minimum voltage - 20 VAC
amperage - 0.12A and operating pressure - 150 psi.
Typical Installation Detail