UninterrUptible power SyStem Instruction Manual

46
1600EP Series Instruction Manual
Optional MB (Maintenance Bypass) Units
The following illustration shows the circuit power ow when the UPS is operating in the optional Mainte-
nance Bypass Mode. The input on the UPS must be set for 240 VAC.
CAUTION
Ensure the UPS is in Static Bypass before switching the unit from UPS to Maintenance
Bypass mode or from Maintenance Bypass to UPS mode. Failure to do so could result
in damage to the maintenance bypass switch or the UPS.
This Maintenance Bypass unit can only be used for 240 V applications. Ensure the
UPS voltage selector jumper is set to 240 V. See page 11 for the correct 240 V setting.
Follow the instructions below when switching to and from the Maintenance Bypass mode.
From Inverter Mode to Maintenance Bypass Mode
Turn the RUN/STOP switch to the STOP position on the UPS.
Turn the Maintenance Bypass Switch to the Bypass position. The Bypass LED should be ON and the
UPS LED should be OFF. The LEDs are next to the Maintenance Bypass switch, on the back of the
UPS.
Turn the MCCB input breaker on the UPS to the OFF position. The UPS is now operating in Mainte-
nance Bypass Mode.
From Maintenance Bypass Mode to Inverter Mode
Turn the MCCB input breaker on the UPS to the ON position.
Turn the Maintenance Bypass switch to the UPS position. The UPS LED should be ON and the By-
pass LED OFF>
Turn the RUN/STOOP switch to the RUN position on the UPS. The UPS is now operating in the UPS
Mode.
1.
2.
3.
1.
2.
3.
POWER FLOW IN MAINTENANCE BYPASS MODE FOR ALL MODELS