5. Installation Precautions
NOTICE
1. Observe the following environmental restrictions:
• Install the unit in a well-ventilated location; allow at least 4 inches (10 cm) on all sides for air
ventilation and for maintenance.
• Install the unit where the ambient temperature is within the range specied on pages 53 - 58.
• DO NOT install the UPS in areas that are subject to high humidity.
• DO NOT install the UPS in areas that allow exposure to direct sunlight.
• DO NOT install the UPS in areas that allow exposure to high levels of airborne dust, metal
particles, or ammable gases.
• DO NOT install the UPS in areas near sources of electrical noise. Ensuring a proper earth ground
will reduce the effects of electrical noise and will reduce the potential for electrical shock.
• DO NOT install the UPS in areas that would allow uids or any foreign object to get inside the
UPS.
2. UPS is intended for permanent installation only. Install the unit in a stable, level and upright position
that is free of excessive vibration.
3. Follow the instructions on the unpacking label afxed to the exterior of the UPS.
4. Retain the shipping rails for use as permanent mounting of the UPS.
WARNING
This unit contai ns se ale d lead a cid batterie s.
La ck of p re venta tive m ainte nan ce cou ld result
in b atte ries e xplod in g a nd emittin g ga sses an d/o r
flam e. An nu al preven tative main tena nce must be
pe rfo rm ed by a n autho rized , traine d te chnician .
WARNING
CR IT ICAL F USE SIZ ING
Incor rect fu se replacem ent size
may result in fire or inadeq uate
equ ipm ent protection.
Re place only with same t ype
and rating of fuse.
49455 SHEET
CAUTIO N/
A TT EN TI O N
Do not di sco nne ct
whi le uni t is
o pe rating
on battery power.
Nes pas debrancher
sou s cha rge.
48524 SHEET
Risk of electric sho ck. Do not re move cover.
. Refer servicing to qualified service personnel.
N O USER SERVI C E AB LE PARTS
INSIDE
To reduce the risk of fire or electric shock, install in a temperature and
hum idity controlled indoor area free of conduc tive conta mina nts.
En c as utilisation en atm osphe re controlee. Consulter la notice technique.
Note: Service pe rsonnel only.
Hazardous live p arts inside the UPS are energized from the battery supp ly
even when the input AC power is disconnected.
Capac itors store hazardous energy. Do not rem ove cover until 5 minutes
after disconnecting all sources of supp ly.
Battery b ackup time, which wa s factory-set at a predetermined level,
decreases gradually b etween service periods. The batteries should be
replaced every three years after the last servicing, the da te of which is
written on the ID plate located on the rear side of the UPS unit, or in the
boxes b elow.
Date of last battery cha rge:
WARNING
CAUTION
Do not i nsert ba tte ry trays w ith the p ow er off !
Th is uni t is desi gned for ho t chan geable bat teries!
When installing batteries, the UPS must b e in the
onlin e or bypass mode. Contact Tosh iba
Intern ati onal Corporation fo r further details.
6041 2
PN 51727
EXTERNAL BATTERY CABINET
The battery cabinet must have
a nominal battery voltage of
288VDC.
WARNING
DANGER/ATTENTION
Risk of electrical shock. Do n ot touch u nin sulat ed
batt ery ter minals. Batteries should be serviced b y
qua lified service r epre se ntative only. Miswiring of
batt ery could result in ele ctrcal sh ock a nd/or fire.
Risque de choc electrique . Le circuit des ba tteries
nest pa s esolede secteur. Le s cosses des ba tteries
peu ven t prese nter une te nsion dange reuse part
rapport a la terre. Ve rifier avan t de to uch er.
DANGER
Batte ry fuse is always
l iv e . R isk o f ele ctr ica l
shock. Check fuse
voltage an d discon nect
exter nal batte ries
befo re cha nging fuse.
48518 SHEET
fig 1
fig 2
1
2
3
Unpacking Instructions
P/N 48537
TYPEFORM
OUTPUT
MFD. IN U.S.A. FROM FOREIGN AND DOMESTIC COMPONENTS
HOUSTON, TEXAS
UNINTERRUPTIBLE POWER SUPPLY
INPUT
SERIAL NO.
PN 60381
LISTED
POWER
SUPPLY
27E5
C US
EPO
14
15
16
17
EPO 1
EPO 2
RE M O TE
REMOTE
1
L1
L2 G
X1 X2
208V
120V
120V
20 8/2 40 V
O UTPUT
I N PUT
N
X3
G
208V
USE COPPER 90 C ONDUCTORS ON LY. REFER TO IN STRUCTION MANUAL REGARDING TIG HTENING TORQUE OF TERMINAL BLOCKS. FACTO RY WIRED FOR 2 08V IN PUT.
C OM
2
3
4
5
6 7
8
11
12
13
240V
240V
RE M O TE
JU MPER SELECTION
50802