Power Supply User Manual

B-3
1600XP Series Installation and Operation Manual
1600XP Command Parameters Table
Cmd
ID
Description
on LCD
Brief Description Location Map Example
Rqd Security
Level to change
By
Tab Block
119 VIOV DeLevel Input Overvoltage Detection Level
- Of rated input voltage which was congured
with Command ID 111.
Setting IN 274 V Nonchangeable
Nonchangeable
Changeable
User
Administrator
Service
120 VIOV ReLevel Input Overvoltage Recovery Level - Of rated
input voltage which was congured with Com-
mand ID 111.
Setting IN 264 V Nonchangeable
Nonchangeable
User
Administrator
121 Vin Gain Used to convert AD value to actual value Setting IN 6720 Changeable Service
122 Vin Offset Feedback Offset adjustment due to hardware
and software AD converter’s offset
Setting IN 0 Changeable Service
124 Iin Gain Used to convert AD value to actual value Setting IN 5241 Changeable Service
125 Iin Offset Feedback Offset adjustment due to hardware
and software AD converter’s offset.
Settings IN 0 Changeable Service
127 Iin 100% 100% Input Current Amount Settings IN 250 Changeable Service
128 Iref Phase Adj Time delay adjustment to sync the phase of
input voltage and current due to hardware and
software delay.
Settings IN 17500 Changeable Service
141 Freq on
FIERR*
Freq setup on input frequency error
- Toshiba UPS try to detect input frequency but
very tiny percentage when UPS can not detect
the input frequency because of uctuation,
1600XP UPS will start by using this setup.
Setting IN 60.0 Hz Nonchangeable
Changeable
Changeable
User
Administrator
Service
202 No of Output
Line
No of Output Lines
- Always 1 input line for 1600XP series
Setting OUT 1 Line Nonchangeable
Nonchangeable
Changeable
User
Administrator
Service
215 Rated Vout* Rated Output Voltage
- Must be setup properly at initial startup.
Rated output voltage is used to calculate per-
centages for ID 220, 222
Setting OUT 240 V Nonchangeable
Changeable
Changeable
User
Administrator
Service
216 Rated Iout Rated Output Current
- UPS calculated rated output current from
typeform command id 002.
Monitor OUT 25.0 A Nonchangeable
Nonchangeable
Changeable
User
Administrator
Service
220 VOUV De-
Level*
Output Undervoltage Detection Level in Per-
centage
- Of rated output voltage which was congured
with Command ID 215.
Setting OUT 90 % Nonchangeable
Nonchangeable
Changeable
User
Administrator
Service