Power Supply User Manual

B-5
1600XP Series Installation and Operation Manual
1600XP Command Parameters Table
Cmd
ID
Description
on LCD
Brief Description Location Map Example
Rqd Security
Level to change
By
Tab Block
256 DC-AC Ef-
ciency
DC to AC Efciency Setting OUT 81 Changeable Service
261 Rated PFactor Calculated from Typeform and Rated Voltage Monitor OUT 85 Nonchangeable
Nonchangeable
Changeable
User
Administrator
Service
262 AC-AC Ef-
ciency
AC-AC Efciency Setting OUT 85 Changeable Service
267 Vref PhAdj
50Hz
Output Voltage Reference Phase Adjustment
for 50 Hz
Setting OUT -7 Changeable Service
268 Cnv/Xfmer Lmt Power calculation is limited by converter or
transformer
Setting OUT 0 Changeable Service
271 Comp. Ainv Inverter Mode A Compensation Setting OUT 2 Changeable Service
272 Comp. Binv Inverter Mode B Compensation Setting OUT 10 Changeable Service
273 Comp. Cinv Inverter Mode C Compensation Setting OUT 0 Changeable Service
274 Comp. Abyp Bypass Mode A Compensation Setting OUT 3 Changeable Service
275 Comp. Bbyp Bypass Mode B Compensation Setting OUT 7 Changeable Service
276 Comp. Cbyp Bypass Mode C Compensation Setting OUT 1 Changeable Service
277 OL Time Wndw Overload Time Window Setting OUT 10 Changeable Service
278 Rated OutXfmr
(P)
Rated Output Primary Transformer Setting OUT 230 Changeable Service
279 50Hz Derating 50Hz Derating Setting OUT 100 Changeable Service
280 60Hz Derating 60Hz Derating Setting OUT 100 Changeable Service
302 No Of Bypass
Line
No of Bypass Lines
- Always 1 input line for 1600XP series
Setting BYP 1 Line Nonchangeable
Nonchangeable
Changeable
User
Administrator
Service
315 VBypUV De-
Level*
Bypass Undervoltage Detection Level - Per-
centage of rated input voltage command ID
111.
Setting BYP 62 % Nonchangeable
Nonchangeable
Changeable
User
Administrator
Service
316 VBypUV
ReLevel*
Bypass Undervoltage Recovery Level in per-
centage
- Of rated input voltage command ID 111.
Setting BYP 66 % Nonchangeable
Nonchangeable
Changeable
User
Administrator
Service
317 VBypOV De-
Level
Bypass Over Voltage Detection Level in Volt Setting BYP 284 V Nonchangeable
Nonchangeable
Changeable
User
Administrator
Service