Power Supply User Manual

B-6
1600XP Series Installation and Operation Manual
1600XP Command Parameters Table
Cmd
ID
Description
on LCD
Brief Description Location Map Example
Rqd Security
Level to change
By
Tab Block
318 VBypOV
ReLevel
Bypass Over Voltage Recovery Level in Volt Setting BYP 274 V Nonchangeable
Nonchangeable
Changeable
User
Administrator
Service
320 BypOL DeDe-
lay
Bypass Overload Fault Detection Delay at
125% @ 25°C
Setting BYP 600 Changeable Service
404 Rated DC Bus* Rated DC Bus Voltage
- Used to calculated percentage.
Setting DC 770 Vdc Nonchangeable
Nonchangeable
Changeable
User
Administrator
Service
405 DCOV Delevel DC Bus Overvoltage Fault Detection Level
Percentage
Setting DC 110 Changeable Service
406 DCUV DeLevel DC Bus Undervoltage Fault Detection Level Setting DC 83 Changeable Service
409 DCIB DeLevel DC Bus Imbalance Fault Detection Level Per-
centage.
Setting DC 11 Changeable Service
415 VdcP Gain Use this value to convert AD value to Actual
value
Setting DC 7947 Changeable Service
416 VdcP Offset Feedback Offset adjustment due to hardware
and software components.
Setting DC 0 Changeable Service
418 VdcN Gain Use this value to convert AD value to Actual
value.
Setting DC 7947 Changeable Service
419 VdcN Offset Feedback Offset adjustment due to hardware
and software components.
Setting DC 0 Changeable Service
431 SoftCharge
Time
DC Bus Soft charging time Setting DC 5 Changeable Service
432 hardCharge
Time
DC Bus Hard charging time. Setting DC 360 Changeable Service
436 Calibrated
DCRef
Calibrated DC Bus Reference Setting DC 100 Changeable Service
438 AC/DC Ref ACDC reference Setting DC 288 Changeable Service
439 Ii Ref Offset Input Current Reference Offset Adjustment Setting DC 0 Changeable Service
440 DCUV SW
DeDelay
DC Undervoltage detection delay Setting DC 2 Changeable Service
441 DCOV SW
DeDElay
DC Overvoltage detection delay Setting DC 2 Changeable Service