Power Supply User Manual

B-10
1600XP Series Installation and Operation Manual
1600XP Command Parameters Table
Cmd
ID
Description
on LCD
Brief Description Location Map Example
Rqd Security
Level to change
By
Tab Block
612 Faults UPS Faults
- UPS Faults decoded at footer fault/s eld or
Setting Tab in hex format
Footer:
Setting
Fault/s
Field :
C&C
DVCOH
0X00000008
Changeable
Changeable
Changeable
User
Administrator
Service
613 Warnings UPS Warnings
- UPS Warnings decoded at footer warning/s
eld or Setting Tab in hex format
Footer:
Setting
Warning/s
Field :
C&C
VIOV
0X00000001
Nonchangeable
Nonchangeable
Changeable
User
Administrator
Service
619 Security Level Security Level
- Change the password with this command ID
to have different level of security
Settings C&C USER, ADMIN Changeable
Changeable
Changeable
User
Administrator
Service
620 Manage Admin
PW
Manage Admin Password
- Default is ADMIN
Settings C&C ADMIN Changeable
Changeable
Administrator
Service
621 Reset Admin
PW
Reset Admin Password
- Restore administrator’s password to default
ADMIN
Settings C&C Idle Changeable
Changeable
Changeable
User
Administrator
Service
623 En Bypass* Decides the system’s bypass availability Settings C&C Enabled Changeable Service
624 En Asyn Byp When disabled, the UPS will not prevent trans-
fers to bypass mode during periods when the
frequencies are out of sync.
Settings C&C Enabled Changeable Service
625 En CVCF* Constant Voltage, Constant Frequency Mode Settings C&C Enabled Changeable Service
626 CVCF
Frequency*
500 or 600 all other values will default to 500
systems.
Settings C&C 600 Changeable Service
634 UPS Date UPS Real Time Date (Battery Backup)
- Follow the same format as display shows (
Mon 10/05/2009)
Settings C&C Mon 10/05/2009 Changeable
Changeable
Changeable
User
Administrator
Service
635 UPS Time UPS Real Time (Battery Backup)
- Use the same format as display shows (12
hour format)
Settings C&C 11:46 AM Changeable
Changeable
Changeable
User
Administrator
Service
636 Timestamp UPS Real Time Date and Time Stamp
- Used for recording feature
Monitor C&C 0X268AB487
637 En REye UPS
Ctl
Enable REye UPS Control
- Enable or disable RemoteEye Network Card
to control UPS modes
Settings C&C Enable Nonchangeable
Changeable
Changeable
User
Administrator
Service