Power Supply User Manual

B-11
1600XP Series Installation and Operation Manual
1600XP Command Parameters Table
Cmd
ID
Description
on LCD
Brief Description Location Map Example
Rqd Security
Level to change
By
Tab Block
639 En Startup
Delay*
Enable Startup Time Delay
- Non-volatile conguration. Default from fac-
tory is Disable.
Settings C&C Disable Nonchangeable
Changeable
Changeable
User
Administrator
Service
640 Startup Mode* Startup UPS Mode
- Non-volatile conguration. Default from fac-
tory is Bypass. It can be changed to On-Line.
Settings C&C Bypass Nonchangeable
Changeable
Changeable
User
Administrator
Service
641 Startup Delay* Startup Time Delay in Second
- Non-volatile conguration. Default from
factory is zero. You can congure up to 800
Seconds.
Settings C&C 0 Sec Nonchangeable
Changeable
Changeable
User
Administrator
Service
645 Mode of Rmt
SDown
Mode of Remote Shutdown
- Non-volatile conguration. When remote con-
tact is close, it could go to bypass or shutdown.
Settings C&C Shutdown Nonchangeable
Changeable
Changeable
User
Administrator
Service
646 En DCntct
LANSD
Enable Dry Contact LAN Shutdown
- Non-volatile conguration. Default from fac-
tory is Enable.
Settings C&C Enable Nonchangeable
Changeable
Changeable
User
Administrator
Service
647 DCntct LANSD
Wndw
Time Window of LAN Shutdown
- Non-volatile conguration. Default from fac-
tory is 600 Seconds
Settings C&C 600 Sec Nonchangeable
Changeable
Changeable
User
Administrator
Service
648 BK DContact
Delay
Time Delay Remote Contact On Backup
- Non-volatile conguration. Time delay for
Backup dry contact will be on after UPS goes
to Backup Mode. Default from factory is 10 Sec
Settings C&C 10 Sec Nonchangeable
Changeable
Changeable
User
Administrator
Service
649 LB DContact
Delay
Time Delay Remote Contact On Low Battery
- Non-volatile conguration. Time delay for Low
Battery dry contact will be on after UPS detects
Low Battery warning. Default from factory is 0
Sec
Settings C&C 0 Sec Nonchangeable
Changeable
Changeable
User
Administrator
Service
652 En Batt Test
Sup*
Enable Battery Test at UPS Startup
- Non-volatile conguration. Default from fac-
tory is Disable
Settings C&C Disable Nonchangeable
Changeable
Changeable
User
Administrator
Service
653 En Batt Test* Enable or Disable Battery Test
- Non-volatile conguration. Default from fac-
tory is Enable.
Settings C&C Enable Nonchangeable
Changeable
Changeable
User
Administrator
Service