Power Supply User Manual

1800 Series User Manual
29
Warning
Description and Resolution
The batteries have less than 30%
power remaining. The warning will
continue until either the batteries
become completely exhausted or
AC input power is restored.
An output current limit warning is
typically a sign of misapplication.
The load may not be appropri-
ate for UPS support. For further
explanation contact your Toshiba
UPS service representative at 1-
877-867-8773 (outside the U.S. call
713-466-0277).
The temperature of the UPS operating
environment is too high. Causes of
this condition include allowing the room
temperature to exceed 104°F (40°C), a
blocked vent, or direct sunlight on the
unit. The unit will transfer to bypass
mode until the temperature is reduced.
If temperature is not reduced after an
allowable time, the unit will shut down.
Alarm State
Alarm will
sound for
1-second at
5- second
intervals.
Alarm will
sound for
1/2- sec-
ond at
1-second
intervals.
Alarm will
sound for
1-second at
15- second
intervals.
LED State
Warning/Fault Flash
Backup Flash
Warning/Fault Flash
80% Flash
Warning/Fault Flash
100% Flash
Display StateWarning
Low Battery
Current Limit
(Over
Current)
Ambient
Over Heat