Warning (cont.)
Description and Resolution
This warning can be caused by
the same conditions listed for
Ambient Overheat. Another pos-
sible cause would be a problem
with the battery module, which
could prevent the unit from provid-
ing backup power.
This warning will occur if the input
voltage drops below the minimum
allowable voltage. If the unit was
online when the warning occurred it
will transfer to battery backup. If the
unit was in bypass the output will be
turned off. The unit will reinitialize the
startup sequence if input power returns
to within specied limits.
This warning will occur if the input volt-
age exceeds the maximum allowable
voltage. If the unit was online when
the warning occurred it will transfer
to battery backup. If the unit was in
bypass the output will be turned off.
The unit will return to normal operation
if input power returns to within speci-
ed limits.
Alarm State
Alarm will
sound for
1-second at
15- second
intervals.
Alarm will
sound for
1/2-second
at 10-second
intervals.
Alarm will
sound for
two 1/2-sec-
ond beeps
at 10-second
intervals.
LED State
Warning/Fault Flash
Battery Flash
Warning/Fault Flash
20% Flash
Warning/Fault Flash
40% Flash
Display State
Warning
Battery Over
Heat
Input Under
Voltage
(see Note 1,
page 31)
Input Over
Voltage
(see Note 1,