Power Supply User Manual

1800 Series User Manual
36
Recharging requirements during storage:
Recharging the batteries requires that the UPS has AC input power
available. The UPS can be in either the online or bypass mode. (See
“Starting the UPS System”, page 20, and “Battery Recharge Time”,
page 24).
1) If stored in an ambient temperature less than 68°F (20°C), recharge
the batteries every 9 months.
2) If stored in an ambient temperature of 68° to 86°F (20° to 30°C),
recharge the batteries every 6 months.
3) If stored in an ambient temperature of 86° to 104°F (30° to 40°C),
recharge the batteries every 3 months.
DISPOSAL
Please contact your local environmental agency for details on disposal of
electrical components and packaging in your particular area. It is illegal to
dump lead-acid batteries in landlls or dispose of improperly. Please
help our Earth by contacting the environmental protection agencies in your
area, the battery manufacturer, or call Toshiba toll-free at 877-867-8773 for
more information about recycling.