This compressor has 4-pole motor. The value when compressor frequency (Hz) is measured by a clamp
meter becomes 2 times of No. of compressor revolutions (rps).
Outdoor unit
Strainer
Packed valve
Outer dia. Ø12.7
Packed valve
Outer dia. Ø6.4
TS sensor
TD sensor
TO sensor
TE
sensor
Distributor
4-way valve
(STF-0108Z)
Muffler
Ø19 × L160
2-step muffler
Ø19 .05 × 200L
Rotary compressor
(DA150A1F-20F)
Heat exchanger Ø8 ripple,
2 rows, 14 steps
FP1.3 flat fin
PMV
(Pulse Motor Valve)
(CAM-B30YGTF-1)
R410A 1.0 kg
Cooling
Heating
Standard
Cooling Overload
Low load
Standard
Heating Overload
Low load
Pressure
(MPa) (kg/cm²G)
Pd Ps Pd Ps
3.50 0.97 35.7 9.9
3.90 1.08 39.8 11.0
1.90 0.70 19.4 7.1
2.31 0.61 13.6 6.2
2.86 0.89 29.2 9.1
1.86 0.25 19.0 2.6
Pipe surface temperature (°C)
Discharge Suction
Indoor heat Outdoor heat
exchanger exchanger
(TD) (TS) (TC) (TE)
85 14 12 48
93 26 17 54
48 7 5 30
87 5 40 1
86 17 47 11
69 14 31 15
Compressor
revolutions per
second (rps)
70
70
50
97
95
98
Indoor
fan
HIGH
HIGH
LOW
HIGH
LOW
HIGH
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Indoor Outdoor
27/19 35/
32/24 43/
18/15.5 5/
20/ 7/6
28/ 24/18
15/
10/(70%)