user manual

6
: EC standard, ∗∗ : AS standard
Indoor unit 1 RAV- SM562MUT-E SM562MUT-E
Model Indoor unit 2 RAV- SM562MUT-E SM562MUT-E
Outdoor unit RAV- SP1102AT(Z, ZG)-E SP1104AT(Z, ZG)-E
Cooling capacity (kW) 10.0 10.0
Heating capacity (kW) 11.2 11.2
Indoor unit
Power supply 1 phase 230V (220 240V) 50Hz
Running current (A) 10.31 11.24 12.51 11.47
Power consumption (kW) 2.4 2.67
Cooling
Power factor (%) 97 97
EER 4.17 3.75
Energy efficiency class AA
Electrical
Energy rating ∗∗ ——
characteristics
Running current (A) 10.95 11.95 12.51 11.47
Power consumption (kW) 2.55 2.67
Heating
Power factor (%) 97 97
COP 4.39 4.19
Energy efficiency class AA
Energy rating ∗∗ ——
Fan Turbo fan
Fan unit Standard air flow H/M/L (m³/min.) 13.3 / 11.2 / 9.1
Motor (W) 60
Sound pressure level H/M/L (dBA) 43 / 39 / 34
Sound power level H/M/L (dBA) 58 / 54 / 49
Outdoor unit
Power supply 1 phase 230V (220 240V) 50Hz
Standard length (m) 7.5
Outer
Min. length (m) 5 3
Max. total length (m) 50
dimension
Height
Outdoor lower (m) 30
difference
Outdoor higher (m) 30
Fan Propeller fan
Fan unit Standard air flow volume (m³/min.) 125 101
Motor (W) 63 + 63 100 + 100
Gas side
Main (mm) 15.9
Connecting
Sub (mm) 12.7
pipe
Liquid side
Main (mm) 9.5
Sub (mm) 6.4
Sound pressure level Cooling/Heating (dBA) 49 / 51 49 / 50
Sound power level Cooling/Heating (dBA) 66 / 68 66 / 67
<Twin type>