<Twin type>
Indoor unit 1 RAV- SM562MUT-E SM562MUT-E
Model Indoor unit 2 RAV- SM562MUT-E SM562MUT-E
Outdoor unit RAV- SM1102AT-E SM1103AT-E
Cooling capacity (kW) 10.0 10.0
Heating capacity (kW) 11.2 11.2
Indoor unit
Power supply 1 phase 230V (220 240V) 50Hz
Running current (A) 14.96 16.32 14.96 16.32
Power consumption (kW) 3.52 3.52
Cooling
Power factor (%) 98 98
EER 2.84 2.84
Energy efficiency class CC
Electrical
Energy rating ∗∗ ——
characteristics
Running current (A) 13.35 14.56 13.35 14.56
Power consumption (kW) 3.14 3.14
Heating
Power factor (%) 98 98
COP 3.57 3.57
Energy efficiency class BB
Energy rating ∗∗ ——
Fan Turbo fan
Fan unit Standard air flow H/M/L (m³/min.) 13.3 / 11.2 / 9.1
Motor (W) 60
Sound pressure level H/M/L (dBA) 43 / 39 / 34
Sound power level H/M/L (dBA) 58 / 54 / 49
Outdoor unit
Power supply 1 phase 230V (220 240V) 50Hz
Standard length (m) 7.5
Outer
Min. length (m) 5.0
Max. total length (m) 50
dimension
Height
Outdoor lower (m) 30
difference
Outdoor higher (m) 30
Fan Propeller fan
Fan unit Standard air flow volume (m³/min.) 75
Motor (W) 100 63
Gas side
Main (mm) 15.9
Connecting
Sub (mm) 12.7
pipe
Liquid side
Main (mm) 9.5
Sub (mm) 6.4
Sound pressure level Cooling/Heating (dBA) 53 / 54
Sound power level Cooling/Heating (dBA) 70 / 71
: IEC standard, ∗∗ : AS standard