Air Conditioner User Manual

Toshiba
–24–
4-way Air Discharge Cassette Type
Installation Manual
EN
Filter sign setting
According to the installation condition, the lighting time
of the filter sign (Notification of filter cleaning) can be
changed.
Follow to the basic operation procedure
(
1 2 3 4 5 6 ).
For the CODE No. in Procedure
3, specify [01].
For the [Set data] in Procedure
4, select the setup
data of filter sign lighting time from the following
table.
To secure better effect of
heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator, etc. to circulate heat air
near the ceiling.
Follow to the basic operation procedure
(
1 2 3 4 5 6 ).
For the CODE No. in Procedure
3, specify [06].
For the set data in Procedure
4, select the setup
data of shift value of detection temperature to be set
up from the table below.
Horizontal louver direction
1. Push and TEMP. buttons for at least four
seconds when the air conditioner is not working.
flashes.
Indicates CODE No. “01.”
2. Select an indoor unit to be set by pushing
button (left side of the button).
Indoor unit number changes each time you push the
button.
The fan of the selected unit runs and the louvers
start swinging.
3. Change the CODE No. to “45” with TEMP.
buttons.
4. Select louver direction setting with TIME
buttons.
5. Push button to check the setting.
The display state changes from flashing to lighting,
and the setting is fixed.
6. Push button to end the setting.
* When the cold draft position is selected, ceiling
contamination is less reduced.
Setup data Filter sign lighting time
0000 None
0001 150 H
0002 2500 H (Factory default)
0003 5000 H
0004 10000 H
Setup
data
Detection temp shift value
0000 No shift
0001 +1.8 °F (+1 °C)
0002
+3.6 °F (+2 °C)
(Factory default)
0003 +5.4 °F (+3 °C)
0004 +7.2 °F (+4 °C)
0005 +9.0 °F (+5 °C)
0006 +10.8 °F (+6 °C)
Louver
direction
setting code
Louver direction setting
0000
Smudge reducing position
(Air direction to reduce ceiling
contamination) [Factory default]
0002
Cold draft position
(Air direction to control cold air fall)
Not
display
UNIT No.
1-1
UNIT No.
1-2
UNIT No.
1-3
UNIT No.
1-4
24-EN