Installation space
Secure the specified space in the figure for installation and servicing.
unit : in (mm)
Selection of installation place
In case of continued operation of the indoor unit under high-humidity conditions as described below, dew may
condense and water may drop.
Especially, high-humidity atmosphere (dew point temperature : 73.4°F (23°C) or more) may generate dew inside
the ceiling.
1. Unit is installed inside the ceiling with slated roof.
2. Unit is installed at a location using inside of the ceiling as fresh air take-in path.
3. Kitchen
Advice
Set a service check opening panel at right side of the unit (size: 17.7" × 17.7" (450 × 450mm) or more) for piping,
maintenance, and servicing.
If installing a unit at such place, put insulating material (glass wool, etc.) additionally on all the positions of the
indoor unit which come to contact with high-humidity atmosphere.
REQUIREMENT
When the humidity inside the ceiling seems to be higher than 80%, attach a heat insulator to the side (top)
surface of the indoor unit. (Use a heat insulator that is 0.4" (10 mm) or more thick.)
Model RAV- A in (mm)
SP180, SP240 Type 10.7” (271) or more
SP300, SP360, SP420 Type 13.1” (334) or more
1000 (39.4) or more
Obstacle
15 (0.6) or more
A
1000 (39.4)
or more
Obstacle
39.4” (1000) or more
39.4” (1000) or more
0.6” (15)
or more
200 (7.9)
Check port
450×450
(17.7×17.7)
Check port
450×450
(17.7×17.7)
Check port must be located on
the Fresh air inlet box side,
if it is installed
200 (7.9)
7.9” (200)
7.9” (200)
Check port
17.7” x 17.7”
(450 x 450)
Check port
17.7” x 17.7”
(450 x 450)
Check port must be located on the
Fresh air inlet box side, if it is installed.