PROGRAMMABLE CONTROLLER PROSEC T1-16S Advanced Features ♦ Compact Modular Style ♦ High-Speed Processing ♦ 8K Steps Program Memory ♦ RS485 Communication Port ♦ Clock/calendar Function ♦ High-speed Counter Function ♦ Online Program Changes ♦ Interrupt Input Function ♦ Built-in EEPROM ♦ Pulse Output Function ♦ Special Data Transfer Function with Toshiba Inverters (VF-A7/G7/S9)
PROSEC T1-16S Expandable Micro Programmable Controller T1-16S is a micro programmable controller with optional add-on expansion I/O modules. Its communications capability, advanced instruction set, and large memory (program & data register) make it ideally suited for applications previously requiring larger more expensive programmable controllers. The T1-16S’s high-speed performance makes it especially adapt at sophisticated machine control applications.
Memory & Expansion Capacity The T1-16S is a micro PLC. But it has a large program and data memory.
Configuration T1-16S Main Unit There are four types of T1-16S controllers depending on the built-in functions and the power supply voltage. Type Description TDR116S6C Standard version, 100-240Vac power TDR116S6S Enhanced version, 100-240Vac power (with Real-time clock and RS485 port) TDR116S3C Standard version, 24Vdc power TDR116S3S Enhanced version, 24Vdc power (with Real-time clock and RS485 port) I/O Modules The following types of I/O modules are available.
Advanced Applications Motion Control The T1-16S has two high-speed counter inputs. These 5k pps (pulse per second) counters can be used independently (of each other and of the CPU scan) for discrete parts count in applications requiring high-speed compare, reset, and strobe. The counters can also be used together as a quadrature counter to count a 2-phase pulse encoder signal. In the quadrature counter mode, the counting speed is max 20k cps (counts per second).
Communication Features SCADA System / Remote Programming The T1-16S enhanced version has a built-in RS485 communication port. By using this communication port, up to 32 T1-16Ss can communicate with a computer or other higher-level controller. Most major SCADA software supports T-series PLC communication protocol. A DDE server software (T-PSV) is also available. When using the T-series programming tool (T-PDS) in this configuration, each station can be programmed remotely.
Flexible Communication Interface The RS485 port on the T1-16S enhanced version supports a flexible communication function called the Free ASCII mode. This Free ASCII mode lets the T1-16S act as a master to communicate with other field devices that have a serial ASCII communication function. The field devices must support ASCII text communication with fixed trailing code. Serial ASCII devices RS485 T1-16S Max 1km Bar Code Reader, ID System, Printer, Power Meter, Weigh Scale, etc.
Programming Tools T-series Program Development System (T-PDS) The T-series Program Development System (T-PDS) is a software program that runs on any Toshiba Notebook computer or other IBM-PC compatible personal computer. The T-PDS software supports on-line/off-line programming, debugging, and program documentation for all T-series programmable controllers; T1/T1S, T2/T2E/T2N, T3/T3H and S2T.
Handy Programmer (HP911A) The HP911A is a hand-held graphic programmer. Its portability makes it ideal for maintenance use at remote locations. The HP911A has all the features of a full size programming terminal. (2 m cable for T1-16S is included) Note: Some T1-16S functions are limited with using the HP911A. ♦ Ladder logic programming of T-series programmable controllers T1/T1S, T2/T2E/T2N and T3. (other than T3H and S2T) ♦ Built-in EEPROM allows program copy between Tseries controllers.
Instruction Set Basic Instructions Symbol -| |-| / |-| ↑ |-| ↓ |-( )-| ∗( )-| -| I |-( I )-| -| P |-| N |-( P )-| -( N )-| MCS MCR JCS JCR TON TOF SS CNT END 10 Function Instructions Name NO contact NC contact Transitional contact (rising edge) Transitional contact (falling edge) Coil Forced coil (debugging purpose only) Inverter Invert coil Positive pulse contact Negative pulse contact Positive pulse coil Negative pulse coil Master control set Master control reset Jump control set Jump control reset ON
Function Instructions FUN No.
Specifications Functional specifications Model Control method Scan system I/O update Program memory RAM memory buck-up Program capacity Programming language Instructions Execution speed Program types I/O capacity User data I/O register Auxiliary relay Special relay Timer Counter Data register Index register Real-time-clock/calendar Special I/O functions Communications interface Debug support function 12 T1-16S Standard version T1-16S Enhanced version Stored program, cyclic scan system Floating scan or
General specifications Model Power supply voltage T1-16S AC power type T1-16S DC power type 100 to 240Vac (+10%, -15%), 24Vdc (+20%, -15%) 50/60 Hz Power consumption 45 VA or less 18 W or less Retentive power interruption 10 ms or less Internal 5Vdc power output Max. 1.5A for I/O modules (when 24Vdc service power is not used) 24Vdc service power output Max. 0.
Input/Output specifications T1-16S main unit Relay output DC output Output Input Model Input points Rated input voltage Rated input current Min. ON voltage Max. OFF voltage ON/OFF delay time Output points Rated load voltage Max. load current Leak current at OFF Minimum load ON/OFF delay time Output points Rated load voltage Max.
Ordering Information Item T1-16S main unit I/O module Data link module Peripheral Cable and others Description AC power supply, Standard version AC power supply, Enhanced version DC power supply, Standard version DC power supply, Enhanced version 16 points DC input 8 points input & 8 points output combo 16 points DC output 8 points relay output 1 channel analog input, 0-5V/0-20mA 1 channel analog input, ±10V 1 channel analog output, 0-20mA 1 channel analog output, ±10V 1 channel thermocouple input, type
Safety Precaution This product is intended to be used for the control of industrial machines and processes. Misuse of this product can result in property damage or human injury. Read related manuals carefully before using this product. PROSEC and TOSLINE are trademarks of TOSHIBA Corporation. IBM is a registered trademark of International Business Machines Corporation. MS-DOS and Windows are registered trademarks of Microsoft Corporation.