Programmable Controllers Installation Guide

SPECIFICATIONS
ANALOG INPUTS
ITEM SPECIFICATION
Part Number: See Order Numbers Below
I/O Registers Assigned: None (Uses Data Registers, 1 Register per Channel Designated by Sfwr)
Input Range: Thermocouple
Resolution
J, K, R, S, T, E, N, & B . 0-100 mV, Cold Junction Compensation Error
1° maximum, 0.5°C typical.
Input Range: RTD
Resolution
PT100 (0.00395 and 0.00385), 3 Wire Compensation, Current Sense
0.5ma. Range: -200° to 800° C
Input Range: Voltage
Current
Resolution
0-100 mV, 0-10 V (via PLC scaling/external shunt resistor)
0-20 mA
12 bit
ANALOG OUTPUTS
ITEM SPECIFICATION
Part Number: See Order Numbers Below
I/O Registers Assigned: None (Uses Data Registers, 1 Register per Channel Designated by Sfwr)
Output Range: Voltage
Current
0-10 V, Minimum Load = 400
4-20 mA Maximum Load = 500
GENERAL
ITEM SPECIFICATION
Communication Ports: PLC
IBM
Connects to T1 Programming Port
Connects to Computer for Setup Connects to OIS for PLC Access
Temperature:
Operating: 0° to 50° C Storage: -25° to 80° C
Humidity: 10% to 90% Non condensing
Immunity to ESD: Level 3 per IEC 61000-4-2
Immunity to Transients: Level 3 per IEC 61000-4-4
Radiated Susceptibility: Level 3 per IEC 61000-4-3
Emissions: EN55011 CISPR A
Certifications: CE, CSA
Isolation: Analog isolated from Digital, no isolation between channels.
Size Eagle 0800 & 0404 155mm x 102mm x 48mm
Eagle 0201 94mm x 42mm x 47 mm
Mounting: DIN rail or through hole
Weight Eagle 0800 & 0404: 0.5 kg Eagle 020:1 02 kg
ORDER NUMBERS
ITEM DESCRIPTION
Eagle0201U 2 Universal Analog Inputs, 1 Analog Output.
Eagle0404U 4 Universal Analog Inputs, 4 Analog Outputs.
Eagle-0800U 8 Universal Analog Inputs.
TKEAGLE05T1 Cable, 50 cm, Connects T1 to Eagle Exp.Unit
TKEAGLE20T1 Cable, 2 m, Connects T1 to Eagle Exp.Unit1
TKEAGLE20T2 Cable, 2 m, Connects T2 to Eagle Exp.Unit
NOTES: 1. Each Eagle unit contains setup software.
2. Connection cables must be ordered separately