Heat Pump User Manual

Quick Reference Guide - Page 25
Function Code List (cont.)
Function Code Number
Function Hydro Unit
C
Range Default
Remote
ontroller
Outside temperature T1 °C
29 - -15 ~ 0 -10
Outside temperature T2 °C
- - 0 0
Outside air temperature T3 °C
2B 0 ~ 15
- 10
Setting temperature A at -20 °C
2C - 20 ~ 55 40
Setting temperature B at T1°C
2D - 20 ~ 55 35
Setting temperature C at T2°C
2E - 20 ~ 55 30
Setting temperature D at T3°C
2F - 20 ~ 55 25
Setting temperature E at +20°C
30 - 20 ~ 55 20
Ratio of Zone 2 in Zone 1 Auto mode (%)
31 - 0 ~ 100 80
Heating
Auto Curve
Settings
Temperature shift of entire Auto curve (°C)
27 - -5 ~ 5 0
Function 0 = Valid; 1 = Invalid
3A - 0 ~ 1 1
Frost Protection
Setting temperature °C
3B - 8 ~ 20 15
Back up heater downtime. 0=5min; 1=10min;
33 - 0 ~ 3 1
2=15min; 3=20min
Back Up Heater
e. 0=10min; 1=20min;
34 - 0 ~ 3 0
Control
Back up heater uptim
2=30min; 3=40min
Zone Selection: 0=Zones 1 and Zone 2;
58 - 0 ~ 1 0
1=Zone 1 Only
Change Setback temperature °C
3 ~ 20
26 - 5
Start time (hour)
- 0E 0 ~ 23 22
Night Setback
End time (hour) - 0F 0 ~ 23 06
Room temperature control adjustment. 0=Valid;
1=Invalid
- 02 0 ~ 1 0
Compensation for temperature °C 35 - 1 ~ 5 1
Downtime Zone B (x 5min) 36 -
1 ~ 24
(5 ~ s) 120min
6
Room Temperature
Uptime Zone C (x5min) 37 -
(5 ~ s)
6
Setting
1 ~ 24
120min
2 Way Valve
O l
2 way valve activation for cooling.
3C - 0 ~ 1 0
peration Contro
0=activated during cooling;
g
1=not activated during coolin
3 Way valve
Op ol
3 way valve activation.
ater operation;
n
54 - 0 ~ 1 0
eration Contr
0=activated during hot w
1=not activated during hot water operatio
2 Zone Mixing
V
0C - 3 ~ 24 6
alve Drive Time
Specified Drive Time for Mixing Valve to 90°
open (x 10 sec)
Boiler & Heat
Pump
hronisa
Sync tion
heat pump.
3E - 0 ~ 1 0
Boiler synchronisation with
0=synchronised; 1=not synchronised
Maximum
Ope of
Maximum heat pump operation time in hot
07 - 1 ~ 120 30
ration Time
Hot Water Heat
Pump
water operation priority mode (minutes)
Cooling Operation
Activate cooling mode.
e; 02 - 0 ~ 1 1 0=cooling & heating mod
1=heating mode only