Installation instructions

For 1 tube luminaire: For 2 tubes luminaire:
Direct line voltage connection
If ECG/CCG (ex, for 2 fluorescent tubes) luminaire is retrofitted or the losses of CCGs should
be eliminated, rewiring of the luminaire is mandatory. The installation must only be done by a
qualified electrician. All the security instructions that follow have to be respected and kept as
guidance for future maintenance use. Responsibility of technical and safety consequences of
the re-wired luminaire is shifted to the party carrying out the wiring changes. Conformity with
all applicable legal requirements must be assured for the rewired luminaire. It must be suitably
re-tested. Re-inspection of the luminaire is recommended after conversion according to
known standards. The new luminaire has to be specified for TOSHIBA LED tube use only.
After re-wiring the new luminaire must not be operated with fluorescent lamps. It is recom-
mended to rewire a luminaire on both sides as shown below. Thus TOSHIBA LED tube can be
inserted in any direction with standardized IEC compliant G13 lamp holders. All wires need to
be approved for the existing voltages and appliance class. Usually solid wires with single
isolation can be used for class I, double insulation wires could be used for class II. The
maximum wire cross-section for lamp holders and starters is typically 0.5mm
2
. Built-in control
gears must not remain connected after rewiring.
Installation instructions:
• Only rework done by qualified electricians
• Make sure if supply voltage and frequency fall within product rating on lamp/package
• Make sure the supply voltage is disconnected
• Remove the conventional lamp
• Remove power factor correction capacitor (if installed) to improve power factor
• Rewire the luminaire according to the circuit diagrams shown below
Use a fuse (250V, T2A)
• Insert the TOSHIBA LED tubes into lamp holders and check the light distribution angle
Assure that the rewired luminaire conforms with all applicable legal requirements and establish
that it complies with all relevant safety requirements and other technical standards
• Mark rewired luminaire visually with "WARNING Sticker"
WARNING:
Do not insert any fluorescent lamp after conversion changes have been made. F
use (250V, T2A)
is necessary for installation protection.
2.
TOSHIBA LED TUBE INSTALLATION OPTIONS_ver1.0
LED tube
LED tube
U
N
Fuse
Direct wiring circuit diagram of retrofitted luminaire:
LED tube
U
N
Fuse