Manual

Electromagnetic Flowmeter LF610 Series
Operation Guide
Setting Parameters Flow
Setting Menu
Items Screen Display Setting or selecting value
A
A DETECTOR
1 Exicitation Current EXC CUR 0.0000A
0.2500A (0.0001A each) *1
2 Meter size SIZE 0.1
36 inch , 2.5mm
900mm *1
3 Exicitation Frequency EXC FREQ 6, 12, 24 Hz
4 Flow Direction FLOW DIR NORMAL , SWITCH
5 Measurement Mode EXIT
B
B DISPLAY
1 Display 1 DSPL1
First Unit : Volume, Others
%, m
3
, L, mL, bbl, gal, m/s, ft/s, COUNT, RANGE, pt, qt,
CUSTOM, GRAPH (*3)
Second Unit : Time unit
/s, /min, /h, /d
Third unit : Flow direction code
B (Automatic selection bi-directionflow)
F (Fixed forward flow), R (Fixed reverse flow)
D (Difference)
*2
*3
2 Display 2 DSPL2
3 Custom Coefficient CS VAL 0
99999999
4 Custom Unit CS UNIT 7 Characters
5 Measurement Mode EXIT
C
C RANGE
1 Range Type R TYPE SINGLE, 4F-0R, 2F-2R, EXT 2F-0R, EXT 2F-2R *4
2 Range 1 R1
Volume unit
m
3
, L, mL, bbl, gal, pt, qt
Time unit
/s, /min, /h, /d
Velocity unit
m/s, ft/s
3 Range 2 R2
4 Range 3 R3
5 Range 4 R4
6 Range Hysteresis R HYS 0.0
25.0 % (0.1% each)
7 Measurement Mode EXIT
D
D FILTER
1 Damping Constant DAMPING 00.0, 00.5, 01.0
60.0 s
2 Rate-of-change Limit LIM RATE 0.0
30.0 % (0.1% each)
3 Control Limit Time LIM TIME 00
20 s (1s each)
4 Measurement Mode EXIT
E
E LOW CUT
1 Low Cutoff CUT VAL 0.0
10.0 % (0.1% each)
2 Display Low Cutoff DSPL SET LINEAR, LOW CUT
3 Measurement Mode EXIT
F
F ZERO
1 Zero Adjustment ZERO ADJ Hold down the
key
2 Manual Zero MANUAL ±10% of 10m/s-maximum range (0.1% each) *5
3 Measurement Mode EXIT
G
G 4-20mA
1 4-20mA Alam Output ALM 4-20 UNDER 3mA, 4mA, HOLD , OVER 24mA
2 Output Low Limit LOW LIM 4.0mA, 3.2mA, 2.4mA *6
3 Measurement Mode EXIT
H
H DO
1 Digital Output 1 DO1 FUNC
NO USE, HIGH ALM, HH ALM, LOW ALM, LL ALM
RNG SIG1, RNG SIG2, PRESET C, CONV ALM
EMPTY ALM, PLS OUT, PLS FRD, PLS REV
*7
2 Digital Output 2 (*13) DO2 FUNC
3 Digital Output 1 Active Status DO1 STAT
NormOPEN, NormCLOSE *8
4 Digital Output 2 Active Status (*13) DO2 STAT
5 Measurement Mode EXIT
I
I DI
1 Digital Input (*13) DI FUNC
NO USE, C ST/SP, C RS/ST
RNG SW, ZERO ADJ, FIX OUT
2 Digital Input Detective Level (*13) DET LVL H LEVEL, L LEVEL *9
3 Measurement Mode EXIT
J
J CNT/PLS
1 Counting Rate CNT RATE
Units : m
3
, L, mL, bbl, gal, pt, qt
Value : within the range 3.6
36000000 pulse/h
(0.001
10,000 pps)
2 Plulse Mode PLS MODE AUTO, MANUAL
3 Pulse Width PLS WID
0.3
500.0ms (0.1ms each)
or Less than 40% of the pulse rate for 100% flow rate output
4 Measurement Mode EXIT
K
K PRESET C
1 Preset Count PRST VAL 0
99999999 count (1 count each)
2 Preset Function OUT MODE HOLD, 50ms PLS, 500ms PLS *10
3 Measurement Mode EXIT
L
L H/L ALM1
1 High Alarm Set H SET ON, OFF
2 High Alarm Value H VAL -10
110 % (0.1% each)
3 Low Alarm Set L SET ON, OFF
4 Low Alarm Value L VAL -10
110 % (0.1% each)
5 Measurement Mode EXIT
M
M H/L ALM2
1 High High Alarm Set HH SET ON, OFF
2 High High Alarm Value HH VAL -10
110 % (0.1% each)
3 Low Low Alarm Set LL SET ON, OFF
4 Low Low Alarm Value LL VAL -10
110 % (0.1% each)
5 Measurement Mode EXIT
N
N SELF CHK
1 Empty Pipe Alarm EMPTY OFF, NORMAL, SENS, SENS-H *11
2 Self-diagnosis function SELF CHK ON, OFF
3 Alarm Output Preset CONV ALM CONV ONLY, WITH EMP
4 Measurement Mode EXIT
O
O FIX OUT
1 Fixed-value Output FIX SET ON, OFF *12
2 Fixed-current Output CUR VAL 2.4
24.0 mA (0.1mA each)
3 Fixed-pulse Output PLS VAL 0
10000 pps (1pps each)
4 Measurement Mode EXIT
P
P OTHERS
1 Password PASSWORD 000
999 (1 each)
2 LCD Density Adjustment LCD ADJ 1(Light)
5 (Dark)
3 Swich Position SW POSN TOP, BOTTOM, LEFT, RIGHT
4 Measurement Mode EXIT
Q
Q COMM
1 PROFIBUS Communication PROFIBUS *13
2 MODBUS Communication MODBUS *13
3 Measurement Mode EXIT
R
R CAL
1 0% Flow Rate Calibration CAL 0%
2 50% Flow Rate Calibration CAL 50%
3 100% Flow Rate Calibration CAL 100%
4 Checking the Excitation Current Value EXC DSPL
5 Measurement Mode EXIT
*1 This value is factory adjusted when shipped.
*2
In case of choosing COUNT or RANGE
COUNT : displays totalized flow counts (8 digits) without a unit.
RANGE : displays the range number (1 to 4)
*3 Only display2
*4
Range type Description
1 : SINGLE Single range
2 : 4F-0R Unidirectional flw , automatic selection of multiple ranges
3 : 2F-2R Bidirectional flows , automatic selestion of multiple ranges
4 : EXT 2F-0R Unidirectional flows , multiple ranges selected by exterminal single
5 : EXT 2F-2R Bidirectional flows , multiple ranges selected by exterminal single
*5
(1) In case of the zero adjustment (Menu No.F1),Zero offset is automatically cleared to Zero.
(2) Calculate the zero offset value with the follwing equation:
Zero offset value (%) = {(Actual flow rate) - (LF610 measured value)}
(Sample)
Measured condition Flow rate % in measured span
Actual flow rate obtained
from other instrument
10.0 m
3
/min 50%
LF610 measured value 10.5 m
3
/min 52.5%
Zero offset
-
-2.5%
If zero offset is set to -2.5% , LF610 will output 50.0% flow rate instead of 52.5%
*6
4-20mA Alarm Output Output Status
0 : UNDER 3mA Under 3mA output
1 : 4mA 4mA output
2 : HOLD Measured data hold
3 : OVER 24mA Over 24mA output
*7
DO1,DO2 items Digital output function
0 : NO USE Not used
1 : HIGH ALM High limit alarm output
2 : HH ALM High high limit alarm output
3 : LOW ALM Low limit alarm output
4 : LL ALM Low low limit alarm output
5 : RNG SIG1 Multi - range output No.1
6 : RNG SIG2 Multi - range output No.2
7 : PRESET C Preset point output
8 : CONV ALM Converter failure alarm output
9 : EMPTY ALM Empty pipe alarm output
10 : PLS OUT Pulse output (bidrectional flow)
11 : PLS FRD Pulse output (fixed forward flow)
12 : PLS REV Pulse output (fixed reverse flow)
*8
DO1/DO2 Active Status Alarm - output Status
0 : NormCLOSE Normal close
1 : NormOPEN Normal open
*9
DI Detective Level Detective Level
0 : L LEVEL L level
1 : H LEVEL H level
*10
Preset Function Output Status
0 : HOLD Output Status Level Hold
1 : 50ms PLS Pulse out (pulse width 50ms)
2 : 500ms PLS Pulse out (pulse width 500ms)
*11
Empty Pipe Alarm Digital output function
0 : OFF Not used
1 : NORMAL Used and Low-sensitive
2 : SENS Used and Middle-sensitive
2 : SENS-H Used and High-sensitive
*12
When this function is set to ON , the conditions are follwing.
Items Conditions
Current output User - set current output
Pulse output Pulse output with a user - set counting rate
Digital outputs Previous status is retained (excluding pulse output).
Data indicating Instaneous flow rates and flow velocity (no totalization).
*13 These functions are option.