Installation Instructions

30
Line 1
Header Follower
Indoor
Outdoor
Line address 1
Indoor address 1
Group address 1
Line 2
Remote
controller
1
2
2
1
3
2
2
1
2
2
2
2
Manual address setup from remote controller
In case to decide an address of the indoor unit prior to finish of indoor electric wiring work and unpracticed outdoor
electric wiring work (Manual setup from wired remote controller)
Arrange indoor unit in which address is
set up and the wired remote controller to 1 : 1.
(Wiring example in 2 lines)
Turn on the power.
1
Push simultaneously
SET
+
CL
+
TES
T
buttons for
4 seconds or more.
LCD changes to flashing.
2
Using the setup temp. / buttons, set
12 to the item code.
3
Using the timer time / buttons, set up
the line address.
(Match it with the line address on the interface P.C.
board of the outdoor unit in the identical refrigerant
system.)
4
Push
SET
button.
(OK when display goes on.)
5
Using the setup temp. / buttons, set
13 to the item code.
6
Using the timer time / buttons, set up
the indoor address.
7
Push
SET
button.
(OK when display goes on.)
8
Using the setup temp. / buttons, set
14 to the item code.
9
Using the timer time / buttons, set
Individual =
0000 , Header unit = 0001 ,
Follower unit =
0002 .
10
Push
SET
button.
(OK when display goes on.)
11
Push
TES
T
button.
Setup operation finished.
(Status returns to normal stop status.)
(Line
address)
(Indoor
address)
(Group address)
In the above example, under condition of
no inter-unit wire of the wired remote
controller, set the address after individual
connecting of the wired remote controller.
Group address
Individual : 0000
Header unit : 0001
Follower unit : 0002
}
In case of group control
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
Operation procedure
1 2 3 4 5 6
7 8 9 10 11
End
11
4, 7, 10
2, 5, 8
3, 6, 9
1
Data Item code