Installation Instructions

29
When address setup has finished in all the systems, turn
off SW30-2 on the interface P.C. boards of the lines
connected to the identical central control except a line
with least line address number.
(Terminator resistors of the wires in the central control
line of indoor/outdoor are unified.)
Connect the relay connector between [U1U2] and [U3U4]
terminals of the outdoor unit for each refrigerant line.
Then set up the central control address.
(For the central control address setup, refer to the Instal-
lation manual of the central control devices.)
Interface P.C. board
SW11
1
ON
2 3 4
SW12
1
ON
2 3 4
SW06
1
ON
2 3 4
SW07
1
ON ONON ON
2 3 4
SW09SW08
11 2 3 4
SW10
1 2 3 4
SW13
1
ON
2 3 4
SW14
1
ON
2 3 4
SW30
SW30
1
ON
2
SW04
SW01
1
SW05 SW15
D600 D601 D602 D603 D604
1 1
SW02 SW03
SW15
7-segment
display
Switch setup
(Example in case of central control over refrigerant system)
Outdoor side (Manual setup)
* Manual setup is necessary for column of which letter color is reversed.
CAUTION
For relay connector
Never connect a relay connector until address setup for all the refrigerant systems finishes;
otherwise address cannot be correctly set up.
U3 U4
U1 U2
U1 U2
A B
Outdoor unit
Individual
Central
remote controller
Group
Remote
controller
U1 U2
A B
Remote
controller
U1 U2
A B
Outdoor unit
Remote
controller
U1 U2
A B
U1 U2
A B
Outdoor unit
Remote
controller
Relay
connector
U3 U4 U3 U4
U1 U2
Relay
connector
U3 U4
U1 U2
Relay
connector
Line address
Indoor unit address
Group address
Indoor side
(Automatic setup)
Outdoor interface
P.C. board
Setup at shipment
from factory
SW13, 14
(Line address)
Relay connector
Outdoor unit Outdoor unit
Open
OFF after
address setup
Short after
address setup
Short after
address setup
ON
1
ON
12
Outdoor unit
OFF after
address setup
Short after
address setup
3
SW30-2
Terminator resistor of
indoor/outdoor communi
cation line/central control
communication line
1
1
0
1
2
0
2
1
1
2
2
2
3
1
0
6
ADDRESS SETUP