5. Indications on display
Messages appearing on the display are classified into three, namely, title indications, malfunction
indications and alarm indications.
Title indications (function indications): Indicated by LED lamps
LED indication Description
init In initialization
chc In checking of initial communication with inverter
copy Copying function
comp Comparing function
prot Memory protecting function
clr Memory initializing function
abcin
syssup
Name of objective
memory
a (memory A), b(memory B), c(memory C)
in(inverter's memory), sys(all memories), sup(Special data)
_ _-_ _ Copying from _ to_
_ _=
==
=_ _ Comparing data of _ with that of _
end End of copying or comparing
0ff0n On/Off status of memory protection function or memory initializing function
(ON: to execute, OFF: not to execute)
f___ Communication number of parameter
00 - ff Result of check sum (hexadecimal number)
Malfunction indications: Indicated by blinking LED
LED indication Description
raMe RAM built in the parameter writer is abnormal.
If the same indication appears after resetting the parameter writer, it needs to repair.
roMe ROM built in the parameter writer is abnormal.
If the same indication appears after resetting the parameter writer, it needs to repair.
eePe E
2
PROM built in the parameter writer is abnormal.
If the same indication appears after writing (copying) data again, it needs to repair.
cpUe CPU of the parameter writer is abnormal.
If the same indication appears after resetting the parameter writer, it needs to repair.
coMe Abnormal communication
When communication is normally operated after the indication, the alarm mode (indication)
is automatically cancelled. If the same indication appears after checking connection of the
inverter's serial communication cable and resetting the parameter writer, the unit needs to repair.
Alarm indications (warning indications): Indicated by blinking LED
LED indication Description
prot The target memory to copy data or to initialize is write protected. You cannot copy data to the
memory or initialize that memory.
deVe The type of device is different (different in type or capacity of inverter).
If you press the ENT key when you are copying between two inverters of different capacities, the
system executes a copying operation forcefully but the system ends the operation if you press the
ESC key. If you set “sup” (system area parameters) to “off” (protection disabled) with
prot (memory protection)” function, you cannot write data even if you press the ENT key.
If you have written data forcefully between two inverters with different capacities, we suggest you
execute a parameter initialization for each level of inverter capacity. See the inverter instruction
manual on how to initialize parameters.
erRa
erRb
erRc
When memory A (or B or C) is selected as the source of copying operation or when it is selected
with comparison and protection functions with no data in either case in the memory (including the
case when power was turned off during the previous copying operation), or when a check sum
error occurred, this indication appears.
Write data other than zero to the memory.
f___ Indicates the communication number of the parameter whose setting value is different.
clr If you press the “STOP key” while an alarm message is displayed, “clr” flickers for one
second. If you press the “STOP key” again when “clr” flickers, the parameter writer will be
reset.