Datasheet

TOSHIBA | 65
Outdoor unit
Indoor unit (600X600 Cassette)
RAV-SP404ATP-E
RAV-SM404MUT-E
RAV-SP454ATP-E
RAV-SM454MUT-E
RAV-SP564ATP-E
RAV-SM564MUT-E
Cooling capacity kW 3,6 4,0 5,0
Cooling range (min. - max.) kW 1,5 - 4,0 1,5 - 4,5 1,2 - 5,6
Power input (min. - rated - max.) kW C 0,36 - 1,00 - 1,49 0,36 - 1,19 - 1,49 0,21 - 1,56 - 2.29
EER W/W 3,60 3,36 3,21
SEER 5,38 5,30 5,61
Energy efficiency class C A A A+
Seasonal electricity consumption kWh/a C 234 264 312
Heating capacity kW 4,0 4,5 5,6
Heating range (min. - max.) kW 1,5 - 5,0 1,5 - 5,6 0,9 - 7,4
Power input (min. - rated - max.) kW H 0,36 - 0,97 - 2,20 0,36 - 1,16 - 2,30 0,17 - 1,54 - 2,37
COP W/W 4,12 3,88 3,64
SCOP (Average) 4,17 4,17 4,20
Energy efficiency class (Average) H A+ A+ A+
Seasonal electricity consumption kWh/a H 1477 1477 1801
SM_MUT + SP_AT
Performance data with Super Digital Inverter / Series 4
Outdoor unit
Indoor unit (600X600 Cassette)
RAV-SM564ATP-E
RAV- SM564MUT-E
Cooling capacity kW 5,0
Cooling range (min. - max.) kW 1,5 - 5,6
Power input (min. - rated - max.) kW C 0,30 - 1,65 - 1,86
EER W/W 3,03
SEER 5,48
Energy efficiency class C A
Seasonal electricity consumption kWh/a C 319
Heating capacity kW 5,3
Heating range (min. - max.) kW 1,5 - 6,3
Power input (min. - rated - max.) kW H 0,30 - 1,52 -2,40
COP W/W 3,49
SCOP (Average) 4,16
Energy efficiency class (Average) H A+
Seasonal electricity consumption kWh/a H 1480
SM_MUT + SM_AT
Performance data with Digital Inverter / Series 4
Indoor unit RAV-SM404MUT-E RAV-SM454MUT-E RAV- SM564MUT-E
Air Flow (h/l) m
3
/h - l/s 660/468 - 183/130 660/468 - 183/130 798/546 - 222/152
Sound pressure level (h-m-l) dB(A) 40-36-31 40-36-31 43-39-34
Sound power level (h-m-l) dB(A) 55-51-46 55-51-46 58-54-49
Dimensions (HxWxD) mm 268x575x575 268x575x575 268x575x575
Weight kg 16 16 16
Panel dimensions (HxWxD) mm 27x700x700 27x700x700 27x700x700
Panel weight kg 3 3 3
SM_MUT
Physical data Indoor unit
C = cooling mode
H = heating mode
h-m-l = high - medium - low speed