Datasheet

Light Commercial
65
Physical data indoor unit
Performance data with Super Digital Inverter Serie 4
Performance data with Digital Inverter Serie 3
Indoor unit RAV-SM404SDT-E RAV-SM454SDT-E RAV-SM564SDT-E
Air Flow (H/L) m/h – l/s 690/522 - 192/145 690/522 - 192/145 780/582 - 217/162
Sound pressure level (H-M-L)* dB(A) 39-36-33 39-36-33 45-40-36
Sound power level (H-M-L)* dB(A) 54-51-48 54-51-48 60-55-51
Dimensions (HxWxD) mm 210 x 845 x 645 210 x 845 x 645 210 x 845 x 645
Weight kg 22 22 22
External static pressure (stand/upper limit) Pa 5/24 5/24 4/24
CO = cooling mode
HP = heating mode
*bottom air inlet
Outdoor unit RAV-SP404AT-E RAV-SP454AT-E RAV-SP564AT-E
Indoor unit (Slim duct) RAV-SM404SDT-E RAV-SM454SDT-E RAV-SM564SDT-E
Cooling capacity kW 3,6 4,0 5,0
Cooling range (min. - max.) kW 1,5 - 4,0 1,5 - 4,5 1,2 - 5,6
Power input (min. - rated - max.) kW CO 0,37 - 1,03 - 1,25 0,37 - 1,2 - 1,49 0,21 - 1,56 - 2,29
EER W/W 3,50 3,33 3,21
Energy eciency class CO A A A
Annual energy consumption kWh 515 600 780
Heating capacity kW 4,0 4,5 5,6
Heating range (min. - max.) kW 1,5 - 5,0 1,5 - 5,6 0,9 - 7,4
Power input (min. - rated - max.) kW HP 0,37 - 1,00 - 2,20 0,37 - 1,15 - 2,30 0,17 - 1,44 - 2,37
COP W/W 4,00 3,91 3,89
Energy eciency class HP A A A
Outdoor unit RAV-SM563AT-E
Indoor unit (Slim duct) RAV-SM564SDT-E
Cooling capacity kW 5,0
Cooling range (min. - max.) kW 1,5 - 5,6
Power input (min. - rated - max.) kW CO 0,21 - 1,66 - 2,78
EER W/W 3,01
Energy eciency class CO B
Annual energy consumption kWh 830
Heating capacity kW 5,6
Heating range (min. - max.) kW 1,5 - 6,3
Power input (min. - rated - max.) kW HP 0,38 - 1,59 - 2,40
COP W/W 3,52
Energy eciency class HP B