Datasheet

Light Commercial
55
Physical data outdoor unit
Single phase
Outdoor unit RAV-SM563AT-E RAV-SM803AT-E RAV-SM1103AT-E RAV-SM1403AT-E RAV-SM1603AT-E
2 HP 3 HP 4 HP 5 HP 6 HP
Air Flow m/h – l/s 2400 - 667 2700 - 750 4500 - 1250 4500 - 1250 6180 - 1717
Sound pressure level dB(A) CO 46 48 53 54 51
Sound power level dB(A) CO 63 65 70 71 68
Operating range °C CO -15 / +43 -15 / +43 -15 / +43 -15 / +43 -15 / +43
Sound pressure level dB(A) HP 48 50 54 54 53
Sound power level dB(A) HP 65 67 71 71 70
Operating range °C HP -15 / +15 -15 / +15 -15 / +15 -15 / +15 -15 / +15
Dimensions (HxWxD) mm 550 x 780 x 290 550 x 780 x 290 795 x 900 x 320 795 x 900 x 320 1340 x 900 x 320
Weight kg 38 44 77 77 99
Compressor type DC Twin Rotary DC Twin Rotary DC Twin Rotary DC Twin Rotary DC Twin Rotary
Flare connections
Gas in 1/2 5/8 5/8 5/8 5/8
Liquid in 1/4 3/8 3/8 3/8 3/8
Minimum pipe length m 5 5 5 5 5
Maximum pipe length m 30 30 50 50 50
Maximum height dierence m 30 30 30 30 30
Chargeless pipe length m 20 20 30 30 30
Power supply V-ph-Hz 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50
CO = cooling mode
HP = heating mode