FILE NO.
CONTENTS 1. SPECIFICATIONS ................................................................................................ 3 2. AIR DUCTING WORK ........................................................................................ 12 3. CONSTRUCTION VIEWS (EXTERNAL VIEWS) ............................................... 13 4. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM ....................................... 20 5. WIRING DIAGRAM .................................................................................
1. SPECIFICATIONS 1-1. Indoor Unit 1-1-1. 4-Way Air Discharge Cassette Type Model name RAV-SM560UT-E Standard capacity (Note 1) (kW) Cooling Heating 5.3 (1.5 – 5.6) 5.6 (1.5 – 6.3) Heating low temp. capacity (Note 1) (kW) 3.01 [B] Running current (A) (kW) (Low temp.) (kW) Power factor (%) 8.42–7.72 6.78–6.29 1.76 1.435 Ceiling panel (Sold separately) 7.1 (2.2 – 8.0) 8.0 (2.2–9.0) 3.46 3.03 [B] Average 3.45 [B] 3.24 11.32–10.37 11.22–10.28 2.34 1.89 95 2.32 2.
• Operation characteristic curve 14 16 12 14 RAV-SM800UT-E RAV-SM800UT-E 12 10 Current (A) Current (A) 10 8 6 6 RAV-SM560UT-E 4 15 20 40 60 70 80 RAV-SM560UT-E 4 • Conditions Indoor : DB27 C/WB19 C Outdoor : DB35 C Air flow : High Pipe length : 7.
1-1-2. Concealed Duct Type Model name RAV-SM560BT-E Standard capacity (Note 1) (kW) Cooling Heating 5 (1.5 – 5.6) 5.6 (1.5 – 6.3) Heating low temp. capacity (Note 1) (kW) 2.60 [D] (A) Power consumption (kW) (Low temp.) (kW) Power factor (%) 9.19–8.42 8.18–7.50 1.92 1.71 Main unit Outer dimension Ceiling panel (Sold separately) 7.1 (2.2 – 8.0) 8 (2.2–9.0) 2.94 2.73 [D] Average 3.21 [C] 2.97 12.57–11.52 12.04–11.04 2.6 2.49 1.78 95 2.
• Operation characteristic curve 14 12 16 14 RAV-SM800BT-E RAV-SM800BT-E 12 10 Current (A) Current (A) 10 8 6 6 RAV-SM560BT-E 4 15 20 40 60 70 80 RAV-SM560BT-E 4 • Conditions Indoor : DB27 C/WB19 C Outdoor : DB35 C Air flow : High Pipe length : 7.
1-1-3. High-Wall Type Model name RAV-SM560KRT-E Standard capacity (Note 1) (kW) Cooling Heating 5.1 (1.5 – 5.6) 5.6 (1.5 – 6.3) Heating low temp. capacity (Note 1) (kW) 2.93 [D] (A) Power consumption (kW) (Low temp.) (kW) Power factor (%) 8.33–7.63 8.138–7.46 1.74 1.7 Main unit Outer dimension Ceiling panel (Sold separately) 6.7 (2.2 – 8.0) 8 (2.2–9.0) 3.11 2.46 [E] Average 3.00 [D] 3.24 13.15–12.05 12.91–11.84 2.72 1.95 95 2.67 2.
• Operation characteristic curve 14 12 16 14 RAV-SM800KRT-E RAV-SM800KRT-E 12 10 Current (A) Current (A) 10 8 6 6 RAV-SM560KRT-E 4 15 20 40 60 70 80 RAV-SM560KRT-E 4 • Conditions Indoor : DB27 C/WB19 C Outdoor : DB35 C Air flow : High Pipe length : 7.
1-1-4. Flexible Type Model name RAV-SM560XT-E Standard capacity (Note 1) (kW) Cooling Heating 5.1 (1.5 – 5.6) 5.6 (1.5 – 6.3) Heating low temp. capacity (Note 1) (kW) 2.93 [D] (A) Power consumption (kW) (Low temp.) (kW) Power factor (%) 8.33–7.63 8.138–7.46 1.74 1.7 Main unit Outer dimension Ceiling panel (Sold separately) 6.7 (2.2 – 8.0) 8 (2.2–9.0) 3.11 2.46 [E] Average 3.00 [D] 3.24 13.15–12.05 12.91–11.84 2.72 1.95 95 2.67 2.
• Operation characteristic curve 14 12 14 RAV-SM800XT-E RAV-SM800XT-E 12 10 Current (A) Current (A) 10 8 6 6 RAV-SM560XT-E 4 15 20 40 60 70 80 RAV-SM560XT-E 4 • Conditions Indoor : DB27 C/WB19 C Outdoor : DB35 C Air flow : High Pipe length : 7.
1-2. Outdoor Unit RAV-SM560AT-E Model name RAV-SM800AT-E Appearance Silky shade (Muncel 1Y8.5/0.5) Power supply 1 phase 230V (220 – 240V) 50Hz (Power exclusive to outdoor is required.) Type Compressor Hermetic compressor Motor (kW) 1.1 1.6 Pole 4 poles Refrigerant charged (kg) R410A 0.9 Refrigerant control Pulse motor valve Standard length 20 (without additional charge) Max. total length Pipe Outer dimension (m) Over 20m Height difference 30 50 Add 20g/m (Max.
2. AIR DUCTING WORK 2-1. Static Pressure Characteristics of Each Model Fig. 1 RAV-SM560BT-E 12 70% (570m³/h) Standard air volume : 840m³/h 110% (925m³/h) 11 Extra High tap External static pressure (mmAq) 10 9 8 High tap 7 6 Middoletap tap Middle 5 4 3 Low tap 2 1 0 500 570 600 700 800 Air volume (m³/hr.) 900 925 1000 Fig.
3. CONSTRUCTION VIEWS (EXTERNAL VIEWS) 3-1. Indoor Unit 4-Way Air Discharge Cassette Type RAV-SM560UT-E/RAV-SM800UT-E 200 860 to 910 Recommended external size 860 to 910 Recommended external size 200 Check port ( 450) Check port ( 450) Standing 850 or less 105 Refrigerant pipe connecting port A Refrigerant pipe connecting port B 70 270 250 Standing 640 or less Surface under ceiling Indoor unit 950 Panel external dimension 790 Hanging bolt pitch 346.
Concealed Duct Type RAV-SM560BT-E 750 ± 7.5 Hanging bolt pitch 700 Dimension of main unit 20 2-Ø200 Discharge port flange 4-M10 Hanging bolt (Procured locally) 120 252 Drain up kit (Sold separately) 70 457 to 637 160~640 150 280 170 60 80 5 For hanging bolt M10 (4-12 x 25 long hole) 730 780 Ceiling opening size 75 720 314.5 240 509 211 300 6-Ø4 tapping screw lower hole Ø160 80 170 Drain pipe connecting port at main unit side (For polyvinyl chloride pipe (Inner dia. 32, Nominal dia.
RAV-SM800BT-E 1050 ± 7.5 Hanging bolt pitch 1000 Dimension of main unit 2-Ø200 Discharge port flange 170 20 4-M10 Hanging bolt (Procured locally) 290 Drain up kit (Sold separately) 252 70 457 to 637 460~640 150 290 120 60 80 5 For hanging bolt M10 (4-12 x 25 long hole) 1030 1050 Ceiling opening size 75 720 314.5 240 509 211 300 6-Ø4 tapping screw lower hole Ø160 80 170 Drain pipe connecting port at main unit side (For polyvinyl chloride pipe (Inner dia. 32, Nominal dia.
High-Wall Type RAV-SM560KRT-E/RAV-SM800KRT-E 998 75 Discharge port Pipe port from left (Knockout hole) 50 Suction port Pipe port from right (Knockout hole) 75 Pipe port from lower side (Knockout hole) Z views 110 56 Drain hose Refrigerant pipe connecting port B 390 490 540 55 55 55 40 40 115 298 20 29 48 10 48 20 998 763.5 450 41 Refrigerant pipe connecting port A 100 100 115 55 or more Position of installation plate B A Liquid Side Gas Side SM560 Ø6.4 Ø12.7 SM800 Ø9.
Under Ceiling/Console Type RAV-SM560XT-E/RAV-SM800XT-E Front panel 208 633 1093 Knock out system Grille air inlet Back body 200 Min 1093 1015 742 450 For stud bolt (Ø6) 20 Installation plate Mount plate 20 74 70 Min Ø 165 460 633 330 M10 Suspention bolt 160 For stud bolt (Ø8 – Ø10) UNDER CEILING & CONSOLE INSTALLATION – 17 – 57 18 Wireless remote control Knock out system
3-2. Outdoor Unit RAV-SM560AT-E A legs Drain hole (2-Ø20 x 88 long hole) 600 125 31 780 Discharge guide mounting hole (4-Ø4 embossing) 115.3 (49.3) 147 Discharge guard 216 500 (Fan center dividing) Valve cover 31 23 Earth terminal 90.6 132 593 598 521 21 21 49.5 270 76 21 B legs 330 30 153 150 11 302 Ø6 hole pitch 308 (Long hole pitch For anchor bolt) 30 115.
Suction port 17.5 Installation bolt hole (Ø12 x 17 U-shape holes) 40 40 Details of B part Knockout (For draining) Discharge port 60 150 300 43 Part A 39 47 26 40 Details of A part 17.5 21 365 95 900 Installation bolt hole (Ø12 x 17 U-shape holes) 101 314 Handles (Both sides) Refrigerant pipe connecting port (Ø9.5 flare at liquid side) 565 Refrigerant pipe connecting port (Ø15.
4. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM Indoor Unit/Outdoor Unit RAV-SM560UT-E, RAV-SM560BT-E, RAV-SM560KRT-E/RAV-SM560AT-E Indoor unit TCJ sensor Air heat exchanger TC sensor Outer diameter of refrigerant pipe Gas side ØA Liquid side ØB 12.7mm 6.4mm Refrigerant pipe at liquid side Outer dia. ØB Refrigerant pipe at gas side Outer dia. ØA Max 30m Packed valve Outer dia. ØB Packed valve Outer dia.
Indoor Unit/Outdoor Unit RAV-SM800UT-E, RAV-SM800BT-E, RAV-SM800KRT-E/RAV-SM800AT-E Indoor unit TCJ sensor TC sensor Air heat exchanger Outer diameter of refrigerant pipe Gas side ØA Liquid side ØB 15.9mm 9.5mm Refrigerant pipe at liquid side Outer dia. ØB Refrigerant pipe at gas side Outer dia. ØA Max 50m Packed valve Outer dia. ØB Pd Outdoor unit Ps Modulating (PMV) (SKV-18D26) Strainer TS sensor Packed valve Outer dia.
5. WIRING DIAGRAM 5-1. Indoor Unit 4-Way Air Discharge Cassette Type RAV-SM560UT-E/RAV-SM800UT-E TA FS CN34 (RED) 3 3 2 2 1 1 LM1 LM2 5 4 3 2 1 5 4 3 2 1 5 4 3 2 1 5 4 3 2 1 5 4 3 2 1 1 2 1 2 1 2 1 2 CN104 (YEL) CN102 (RED) 1 1 2 2 (EXCT) CN101 (BLK) 1 2 3 1 2 CN80 (GRN) CN73 (RED) 1 2 CN70 (WHI) 2 CN32 1 (WHI) DC20V DC15V DC12V DC7V (FAN DRIVE) 6 5 4 CN61 3 (YEL) 2 1 Power supply circuit Fuse F302 T3.
Concealed Duct Type RAV-SM560BT-E/RAV-SM800BT-E TA TCJ 1 2 1 2 FS CN030 (RED) 3 3 2 2 1 1 1 2 1 2 TC PNL 1 2 1 2 EXCT 1 2 1 2 3 CN104 CN102 CN101 (YEL) (RED) (BLK) 1 2 CN080 (GRN) 1 2 CN073 CN070 (RED) (WHI) CN060 (WHI) CN032 (WHI) LM CN033 (GRN) 3 2 1 RY001 CN068 (BLU) 3 3 2 2 1 1 DP CN061 (YEL) FM RC FM RED YEL BLU OPN BLK BRW RED YEL BLU OPN BLK BRW 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 YEL 1 1 2 2 2 3 BLU 3 3 4 4 4 5 5 5 6 ORN 6 6 7
High-Wall Type RAV-SM560KRT-E/RAV-SM800KRT-E SUB-CONTROL P.C. BOARD CN12 2 1 WHI 2 1 CN01 BLK TR 1 1 2 2 CN 240 1 2 CN63 6 5 4 3 2 1 CN62 1 2 WHI 6 5 4 3 2 1 WHI Indoor unit CN16 1 2 3 BLU 1 2 3 GRN&YEL BLK Remote Controller (Option) ORG A A B B YEL BLU C C P03 P02 Central Centroller Connection (Option) X Y 1 1 2 2 CN01 RED 1 2 CN64 6 5 4 3 2 1 CN61 1 2 6 5 4 3 2 1 WHI F201 T3,15A 250V~ 1 1 2 2 3 3 CN02 WHI AI-NET P.C.
RAV-SM560XT-E/RAV-SM800XT-E HEAT EXCHANGER SENSOR (TCJ) SWITCH PCB MCC-1428B CN101 1 2 3 WHI GRY GRY FOR FLOAT SWITCH (OPTION) When you use float switch you should cut J401 2 INFRARED RAYS RECEIVE AND INDICATION PARTS 1 2 3 CN402 1 2 CN100 1 2 3 10 10 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 WHI BLU BLU BLU BLU BLU BLU BLU BLU BLU 9 8 7 6 5 4 3 2 1 1 2 3 4 5 6 1 2 3 4 5 6 POWER SUPPLY CIRCUIT 4 BRW RED ORN YEL PNK BLU CN07 DC12V DC5V CN03 THERMO SENSOR (TA) 2 2 BLK BLK 1 1 BLK IC03 HEAT
5-2. Outdoor Unit RAV-SM560AT-E Q200 DB01 IGBT MODULE BRW + ~ – ~ A E G P10 P20 P17 P18 P23 P22 P21 2 1 CN500 2 1 P07 1 1 CN600 2 2 P09 P08 P19 ELECTRONIC STARTER BLK WHI RED THERMOSTAT FOR COMPRESSOR 2 1 2 1 ORN BZ BY BX EW BW EV BV EU BU BLU CT POWER RELAY CN602 Q300 C12 + + + CM – – – 3 C13 RELAY C14 TE TD 1 1 CN601 2 2 3 3 P.C. BOARD (MCC-813) 3 2 1 3 2 1 4 REACTOR CONVERTER MODULE TO 1 1 2 2 TS 1 1 CN603 2 2 3 3 1 1 CN701 2 2 COMPRESSOR 3 3 P06 F04 FUSE T3.
RAV-SM800AT-E Compressor THERMOSTAT FOR COMPRESSOR ORN 2 2 CN500 1 1 ORN 4-WAY VALVE COIL 3 3 3 1 1 1 FAN MOTOR FM 5 4 3 2 1 CN700 5 4 3 CN300 2 1 3 3 2 2 CN301 1 1 PMV 6 5 4 3 2 1 CN604 2 2 1 1 TE CN605 2 2 1 1 GRN TS 3 3 CN600 2 1 1 TD CN601 2 2 1 1 BLK CN11 F04 FUSE 3.
6. SPECIFICATIONS OF ELECTRICAL PARTS 6-1. Indoor Unit 4-Way Air Discharge Cassette Type RAV-SM560UT-E/RAV-SM800UT-E No. Parts name 1 Fan motor (for indoor) 2 Thermo.
6-2. Outdoor Unit RAV-SM560AT-E Parts name No. 1 Fan motor 2 Compressor 3 Reactor 4 Type Specifications ICF-140-43-1 Output (Rated) 40 W DA130A1F-23F 3 phase, 4P, 1100 W CH-57 1=10 mH, 16A Outdoor temp. sensor (To-sensor) — 10 kΩ at 25°C 5 Heat exchanger sensor (Te-sensor) — 10 kΩ at 25°C 6 Suction temp. sensor (Ts-sensor) — 10 kΩ at 25°C 7 Discharge temp. sensor (Td-sensor) — 50 kΩ at 25°C 8 Fuse (Switching power (Protect)) T3.
7. REFRIGERANT R410A This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer. The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22).
Table 7-2-1 Thicknesses of annealed copper pipes Thickness (mm) Nominal diameter Outer diameter (mm) R410A R22 1/4 6.35 0.80 0.80 3/8 9.52 0.80 0.80 1/2 12.70 0.80 0.80 5/8 15.88 1.00 1.00 b) Socket Joints Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose diameter is larger than 20 mm. Thicknesses of socket joints are as shown in Table 7-2-2. (2) Joints For copper pipes, flare joints or socket joints are used.
c) Insertion of Flare Nut d) Flare Processing Make certain that a clamp bar and copper pipe have been cleaned. By means of the clamp bar, perform the flare processing correctly. Use either a flare tool for R410A or conventional flare tool. Flare processing dimensions differ according to the type of flare tool. When using a conventional flare tool, be sure to secure “dimension A” by using a gauge for size adjustment. ØD A Fig.
Table 7-2-6 Flare and flare nut dimensions for R22 Nominal diameter Outer diameter (mm) Thickness (mm) 1/4 6.35 3/8 Dimension (mm) A B C D Flare nut width (mm) 0.8 9.0 9.2 6.5 13 17 9.52 0.8 13.0 13.5 9.7 20 22 1/2 12.70 0.8 16.2 16.0 12.9 20 24 5/8 15.88 1.0 19.4 19.0 16.0 23 27 3/4 19.05 1.0 23.3 24.0 19.2 34 36 45 to 4 6 B A C 43 D to 4 5 Fig.
7-3. Tools 7-3-1. Required Tools The service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened. The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc.
7-4. Recharging of Refrigerant When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps. Recover the refrigerant, and check no refrigerant remains in the equipment. When the compound gauge’s pointer has indicated –0.1 Mpa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s power switch. Connect the charge hose to packed valve service port at the outdoor unit’s gas side.
Be sure to make setting so that liquid can be charged. When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down. It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
7-5-3. Brazing (2) Characteristics required for flux • Activated temperature of flux coincides with the brazing temperature. • Due to a wide effective temperature range, flux is hard to carbonize. • It is easy to remove slag after brazing. • The corrosive action to the treated metal and brazing filler is minimum. • It excels in coating performance and is harmless to the human body.
8. CONTROL BLOCK DIAGRAM 8-1. Indoor Control Circuit Weekly timer Main (Sub) master remote controller Display LCD Max. 8 units are connectable.*1 CPU Display LED *1 Max. 7 units when network adapters are attached Central control remote controller (Option) Function setup Function setup CPU Key sw i t c h *2 Network adapters are attached to only one unit. *3 Weekly timer is not connectable to the sub remote controller.
8-2. Control Specifications No. 1 2 Outline of specifications Item When power supply is reset Operation mode selection 1) Distinction of outdoor units When the power supply is reset, the outdoors are distinguished, and control is exchanged according to the distinguished result. 2) Setting of speed of the indoor fan/setting whether to adjust air direction or not. (Only 4-way models) Based on EEPROM data, speed of the indoor fan or setting whether to adjust air direction or not is selected.
No. 3 Item Room temperature control Remarks Outline of specifications 1) Adjustment range Remote controller setup temperature (°C) COOL/ DRY Heating operation Auto operation Wired type 18 to 29 18 to 29 18 to 29 Wireless type* 18 to 30 16 to 30 17 to 27 * : Only for 4-way air discharge cassette type 2) Using the item code 06, the setup temperature in heating operation can be compensated. Setup data Setup temp.
No. 5 Item Air speed selection (Continued) Remarks Outline of specifications Ta ( C) L(L) L(H) H(H) (-0.5) –1.0 (0) Tsh (+0.5) +1.0 (+1.0) +2.0 (+1.5) +3.0 E H (HH) D HH (HH) C B (+2.0) +4.0 A Value in the parentheses indicates one when thermostat of the remote controller works. Value without parentheses indicates one when thermostat of the body works. • If the air speed has been changed once, it is not changed for 1 minute. However when the air speed is exchanged, the air speed changes.
No. 6 Item Cool air discharge preventive control Outline of specifications Remarks 1) In heating operation, the indoor fan is controlled based on the detected temperature of Tc sensor or Tcj sensor. As shown below, the Tc ( C) Tcj upper limit of the HH 32 revolution frequency H 30 L is determined. E zone In D or E zone, the priority is given to setup of air volume exchange. In A and B zones, [PRE-HEAT] is displayed.
No. Item Outline of specifications 9 Drain pump control 1) In cooling operation (including Dry operation), the drain pump is usually operated. 2) If the float switch operates while drain pump operates, the compressor stops, the drain pump continues the operation, and a check code is output. 3) If the float switch operates while drain pump stops, the compressor stops and the drain pump operates. If the float switch keeps operating for approx. 4 minutes, a check code is output.
No. 12 Item Frequency fixed operation (Test run) Outline of specifications Remarks 1. When pushing [CHECK] button for 4 seconds or more, [TEST] is displayed on the display screen and the mode enters in Test run mode. 2. Push [ON/OFF] button. 3. Using [MODE] button, change the mode from [COOL] to [HEAT]. • Do not use other mode than [COOL]/[HEAT] mode. • During test run operation, the temperature cannot be adjusted. • An error is detected as usual.
No. 14 Item Central control mode selection Outline of specifications 1) Setting at the central controller side enables to select the contents which can be operated on the remote controller at indoor unit side. 2) RBC-AMT21 [Last push priority] : The operation contents can be selected from both remote controller and central controller of the indoor unit side, and the operation is performed with the contents selected at the last.
– 46 – Drain pump output DC fan return Float SW Louver Optional output TA sensor DISP CHK EXCT TC sensor Remote controller power LED Outside error input TCJ sensor Remote controller inter-unit cable 8-3.
Concealed Duct Type RAV-SM560BT-E/RAV-SM800BT-E Indoor/Outdoor inter-unit cable Power transformer input (AC11V,14V,20V) Power transformer output Microcomputer operation LED Louver – 47 – Remote controller power LED Drain pump output HA Optional output Network adapter power supply Fan output EXCT Float SW TA sensor Remote controller inter-unit cable TCsensor TCJ sensor Outside error input CHK DISP
9. CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS 9-1. Microcomputer System Block Diagram 9-1-1. Connection of Main Remote Controller Main (Sub) master remote controller EEPROM Display LCD CPU Display LED TMP47C 820F Ke y s w i t c h AC synchronous signal input circuit Serial send/ receive circuit Function setup Power circuit The P.C. boards of the indoor unit are classified into 4 boards according to the function. 1. Main P.C.
9-1-2. Connection of Wireless Remote Controller Indoor unit #1 Main P.C. board (MCC-1370A) Infrared radiation EEPROM LED Sensors TA shift setup Model selection Function setup Sensor display P.C. board Remote controller No. setupTwin/ Triple setup Sub P.C. board(MCC-1370B) CPU TA sensor Optional output Comp.
9-1-3. Control Specifications No. 1 2 Outline of specifications Item When power supply is reset Operation mode selection Remarks 1) Distinction of outdoor units When the power supply is reset, the outdoors are distinguished, and control is exchanged according to the distinguished result. 2) Setting of the indoor fan speed Based on EEPROM data, rspeed of the indoor fan is selected. Air speed 1) Based on the operation mode selecting command from the remote controller, the operation mode is selected.
No. 4 Outline of specifications Item Remarks Automatic 1) Based on the difference between Ta and Ts, the capacity control operation frequency is instructed to the outdoor unit. (GA control) NOTE : In cooling operation : When calculating the following conditions for 29 minutes, the commanded frequency is assumed as the rated cooling frequency.
No. Item 5 Air volume control (Continued) Outline of specifications Air volume setup Tap COOL, DRY, FAN SM560 HEAT Remarks SM800 Revolutions per minute (rpm) F4 UH 1290 1480 F5 H 1230 1480 1180 1340 M+ 1150 1320 M 1120 1310 1060 1200 L+ 1060 1200 L 990 1100 940 1040 900 900 F6 H F7 M+ F8 F9 M FA FB L+ FC L FD UL 3) In heating operation, the mode changes to [Ultra Low (UL)] or [STOP] if thermostat is turned off.
No. Item Outline of specifications Remarks 7 Freeze preventive control (Low temperature release) 1) The cooling operation (including Dry operation) is performed as follows based on the detected temperature of Tc sensor or Tcj sensor. When [J] zone is detected for T1 minutes (Following figure), the commanded frequency is decreased from the real operation frequency. After then the commanded frequency changes every 30 seconds while operation is performed in [J] zone.
No. 9 Item Louver control 1) Louver position Outline of specifications The louver angle is displayed setting 0° as “Full close”. Remarks Full close 1) In the initial operation after 0 power-ON, the position is automatically controlled according to the operating status (COOL/HEAT).
No. Item Outline of specifications 11 Filter sign display 1) The operation time of the indoor fan is calculated, the filter [FILTER] goes lamp (Orange) on the display part of the main unit goes on on. when the specified time (240H) has passed. When a wired remote controller is connected, the filter reset signal is sent to the remote controller, and also it is displayed on LCD of the wired remote controller.
9-2. Indoor Control Circuit 9-2-1. Print Circuit Board
9-2-2. Outline of Main Controls 1. Pulse Modulating Valve (PMV) control 1) For PMV, SM560 is controlled with 45 to 500 pulses and SM800 with 50 to 500 pulses during operation, respectively. 2) In cooling operation, PMV is controlled with the temperature difference between TS sensor and TC sensor. 3) In heating operation, PMV is controlled with the temperature difference between TS sensor and TE sensor.
9-2-3. Indoor P.C. Board Optional Connector Specifications Function Option output Outside error input Filter option error CHK Operation check DISP display mode EXCT demand Connector No. CN60 CN80 CN70 CN71 CN72 CN73 Pin No. Specifications Remarks 1 DC12V (COM) 2 Defrost output ON during defrost operation of outdoor unit 3 Thermo.
12V power supply PMV output TD sensor TS sensor TE sensor TO sensor Case thermo – 59 – Outdoor fan rpm input IGB module Outdoor fan output 4-way valve output (Except cooling only models) Converter module 9-3. Outdoor Controls GND 9-3-1. Print Circuit Board MCU
12V power supply PMV output Case thermo Contactor against night low-noise 5V power supply TD sensor TO sensor TE sensor TS sensor – 60 – Communication between CDB and IPDU Existing pipe corresponding switch (SW 801) 4-way valve output Outdoor fan output GND MCU Status display LED MCC-813 (RAV-SM800AT-E) Pump down switch
9-3-2. Outline of Main Controls 1. Outdoor fan control (Object: SM80) Allocautions of fan tap revolutions [rpm] SM800 W1 W2 W3 W4 W5 W6 W7 W8 W9 WA WB WC WD WE 250 270 290 310 340 370 400 440 480 520 560 610 700 780 1) Cooling fan control Q The outdoor fan is controlled by TE sensor. (Cooling: Temperature conditions after medium term) The cooling fan is controlled by every 1 tap of DC fan control (14 taps).
2. Outdoor fan control (Object: SM560) The outdoor fan is controlled by TO sensor and the revolutions frequency of the compressor (rps). The outdoor fan is controlled by every 1 tap of DC fan control (8 taps). According to each operation mode, the fan is operated by selecting an outdoor fan operation tap in the following table based upon the conditions of TO sensor and the compressor operation (rps).
NOTIFICATION It is not an abnormal phenomenon that electro-noise may be heard while heating the coil. 4. Short intermittent operation preventive control Q The compressor may not stop for preventing the compressor for 3 to 10 minutes after start of the operation even if Thermo-OFF signal has been received from the indoor. This phenomenon is not abnormal. (Continuous operation time of the compressor differs according to the operating status.
8. Defrost control Q In heating operation, defrost operation is performed when TE sensor temperature satisfies any condition in A zone to D zone. R The defrost operation is immediately finished if TE sensor temperature has become 12°C or more, or it also is finished when condition of 7°C ≤ TE < 12°C has continued for 1 minute. The defrost operation is also finished when defrost operation has continued for 10 minutes even if TE sensor temperature has become 7°C or lower.
10. TROUBLESHOOTING 10-1. Summary of Troubleshooting 1. Before troubleshooting 1) Required tools/instruments • + and – screwdrivers, spanners, radio cutting pliers, nippers, push pins for reset switch • Tester, thermometer, pressure gauge, etc. 2) Confirmation points before check Q The following operations are normal. a) Compressor does not operate.
(Only for 4-way air discharge cassette type models) 1. Before troubleshooting 1) Required tools/instruments • + and – screwdrivers, spanners, radio cutting pliers, nippers, etc. • Tester, thermometer, pressure gauge, etc. 2) Confirmation points before check Q The following operations are normal. a) Compressor does not operate.
10-2. Check Code List Error mode detected by indoor unit Wireless sensor lamp display Operation Timer ◎ ● Ready ◎ : Flash, 〇 : Go on, ● : Go off Diagnostic function Wired remote controller Judgment and measures Cause of operation Status of air conditioner E03 No communication from remote controller (including wireless) and communication adapters Stop (Automatic reset) Displayed when 1. Check cables of remote controller and communication adapters.
Error mode detected by outdoor unit ◎ : Flash, 〇 : Go on, ● : Go off Wireless sensor lamp display Operation Timer Ready ● ◎ ● ● ◎ ● ● ◎ ● – 68 – ◎ ○ ◎ ◎ ○ ◎ ◎ ● ◎ ◎ ● ◎ ◎ ● ◎ ◎ ● ◎ ◎ ● ◎ ◎ ◎ ○ ◎ ◎ ○ ◎ ◎ ○ Wired remote controller Diagnostic function Cause of operation Check code Status of air conditioner Condition Judgment and measures H01 Breakdown of compressor • Displayed when error is detected Stop Displayed when 1. Check power voltage.
Error mode detected by remote controller or network adapter ◎ : Flash, 〇 : Go on, ● : Go off Wireless sensor lamp display Operation Timer — — Ready — ◎ ● ● ◎ ● ● ◎ ● ● – 69 – ◎ — ○ — ◎ — Wired remote controller Check code Diagnostic function Cause of operation Status of air conditioner Condition — Judgment and measures No check code is displayed. (Remote controller does not operate.) No communication with master indoor unit • Remote controller cable is not correctly connected.
10-3. Error Mode Detected by LED on Outdoor P.C. Board • When multiple errors are detected, the latest error is displayed. • When LED display is ○ (Go on), there is the main cause of trouble on the objective part of control at CDB side and the unit stops. • When LED display is ◎ (Flash), there is the main cause of trouble on the objective part of control at IPDU side and the unit stops.
10-4. Troubleshooting Procedure for Each Check Code 10-4-1. New Check Code/Present Check Code (Central Control Side) [E01 error]/*[99 error] * : When central controller [99] is displayed, there are other causes of error. Is inter-unit cable of A and B normal? NO Correct inter-unit cable of remote controller. YES Is there no disconnection or contact error of connector on harness from terminal block of indoor unit? YES Correct connection of connector. Check circuit cables.
[E04 error]/[04 error] Does outdoor unit operate? NO YES Is setup of group address correct? NO Check item code [14]. YES Are 1, 2, 3 inter-unit cables normal? NO Correct inter-unit cable. YES Are connections from connectors of inter-terminal blocks (1, 2, 3) of indoor/outdoor units normal? NO Correct connection of connector. YES Does voltage between 2 and 3 of inter-terminal blocks (1, 2, 3) of indoor unit vary?* YES Check indoor P.C. board (MCC-1402).
[E10 error]/[CF error] Check indoor control P.C. board (MCC-1402). Defect Replace [E18 error]/[97 error] *[99 error] * : When central controller [99] is displayed, there are other causes of trouble. NO Correct inter-unit cable of remote controller. Is inter-unit cable of A and B normal? YES Is there no disconnection or contact error of connector on harness from terminal block of indoor unit? YES Correct connection of connector.
[L20 error]/[98 error] Are cable connections to communication line X, Y normal? NO Correct cable connection YES Is central controller [98] displayed? Check indoor P.C. board (MCC-1402 or MCC-1403). Replace Defect NO YES Is indoor remote controller [L20] displayed? YES Are not multiple same central control network addresses connected? YES Correct central control network address. NO Check central controller (including network adapter). Replace.
[P10 error]/[Ob error] NO Is connection of float switch connector (Indoor control P.C. board CH34) normal? Correct connection of connector. YES NO Does float switch operate? YES Is circuit cabling normal? NO Check and correct cabling/wiring. YES Check indoor P.C. board (MCC-1402 or MCC-1403). Defect Replace NO Does drain pump operate? YES Is power of drain pump turned on? NO Check indoor P.C. board (MCC-1402 or MCC-1403). Defect Replace YES Check drain pipe, etc. Replace drain pump.
[P12 error]/[11 error] Turn off the power. Are not there connections errors or disconnection on connectors CN333 and CN334 of indoor unit P.C. board (MCC-1402)? YES Correct connection of connector. NO Remove connectors CN333 and CN334 of indoor unit P.C. board (MCC-1402). Does the fan rotate without trouble when handling the fan with hands? NO Replace indoor fan motor.
[P22 error]/[1A error] (RAV-SM800AT-E) Are connections of CN301 and CN300 of P.C. board correct? YES Does the fan rotate without trouble when handling the fan with hands under condition of removing CN301 and CN300 from P.C. board? CN301 NO YES The status that the resistance values between leads below are 50 to 80 for 40W motor (ICF-140-40) and 25 to 55 for 60W motor (ICF-140-60-1) is normal.
[P19 error]/[08 error] Is operation of 4-way valve normal? NO Is voltage applied to 4-way valve coil terminal in heating operation? YES NO NO YES Is flow of refrigerant by electron expansion valve normal? Check 4-way valve Defect Replace YES Check and replace electron expansion valve. NO Is circuit cable normal? YES NO Check and correct circuit. Are characteristics of TC sensor resistance value normal? * Refer to Characteristics-2. YES NO Check CDB P.C. board. Replace TC sensor.
[F01 error]/[0F error] Is connection of TCJ sensor connector (Indoor P.C. board CN102) normal? NO Correct connection of connector. YES Are characteristics of TCJ sensor resistance value normal? YES NO Replace TCJ sensor. * Refer to Characteristics-2. Check indoor P.C. board (MCC-1403). Replace Defect [P26 error]/[14 error] Is power voltage normal? NO Improve the power supply line. YES Are connections of cabling/connector normal? Check and correct circuit cables.
[P29 error]/[16 error] NO Are connections of cable/connector normal? Check and correct circuit cabling such as cabling to compressor. YES NO Is compressor normal? YES Is not earthed? YES Compressor error Replace Compressor error Replace Compressor error Replace NO Is not winding shorted? (Is resistance between windings 0.6 to 1.2 ?) YES NO Is not winding opened? YES NO Check IPDU P.C. board. Replace Defect * For RAV-SM560AT-E, replace control P.C. board.
[F06 error]/[18 error] Are connections of TE/TS sensor connectors of CDB CN604/CN605 normal? YES Are characteristics of TE/TS sensor resistance values normal? NO Correct connection of connector. * (For RAV-SM560AT-E, CN600 TE sensor and CN603 TS sensor) NO Replace TE and TS sensors. YES Check CDB. Defect Replace * Refer to Characteristics-3.
[L29 error]/[1C error] Are connections of CDB CN800 and CDB IPDU CN06 connectors normal? NO Correct connection of connector. YES Was the error just after power ON determined? YES Are cabling/connector normal? NO Check cabling between IPDU and CDB and connector. YES NO IPDU P.C. board error Defect Replace Is there no abnormal overload? YES Improve and eliminate the cause. NO Is IPDU P.C. board come to closely contact with heat sink? NO Correct mounting. YES IPDU P.C.
[P03 error]/[1E error] Is protective control such as discharge temprelease control normal? NO Are connections of cable/connector normal? YES NO Correct the cabling and connection of connector. YES Check parts. Defect Is charged refrigerant amount normal? NO Replace Check and correct the charged refrigerant amount. YES Is not abnormal overload? YES Improve and delete the cause NO Are characteristics of TD sensor resistance value normal? YES NO Replace TD sensor.
[P04 error]/[21 error] Is high-voltage protective operation by TE sensor normal? NO YES NO Is connection of cabling connector normal? Correct connection of cabling connector. YES Check TE sensor. Defect Replace NO Does cooling outdoor fan normally operate? YES NO Is connection of connector normal? Correct connection of connector. YES NO Is fan motor normal? Replace fan motor. YES NO Does PMV normally operate? YES Do not TD and TO sensors come off the detection part? Correct coming-off.
[97 error] (Central controller) NO Is X, Y communication line normal? Correct communication line. YES Are connections between connectors CN02, CN03 of network adapter P.C. board and connectors CN309, CN41 of indoor P.C. board (MCC-1402 or MCC-1403, normal? NO Correct connection of connector. YES NO Is A, B communication line normal? Check connections of A, B terminal blocks. Correct communication line of remote controller. YES YES Is there no connection error of power line? Correct power cable.
[E03 error] (Master indoor unit) [E03 error] is detected when the indoor unit cannot receive a signal sent from the main remote controller (and central controller). In this case, check the communication cables of the remote controllers A and B, the central control system X and Y. As communication is disabled, [E03] is not displayed on the main remote controller and the central controller. [E01] is displayed on the main remote controller and [97 error] on the central controller, respectively.
10-4-2.
11. REPLACEMENT OF SERVICE INDOOR P.C. BOARD [Requirement when replacing the service indoor P.C. board assembly] In the non-volatile memory (Hereinafter said EEPROM, IC10) installed on the indoor P.C. board before replacement, the type and capacity code exclusive to the corresponding model have been stored at shipment from the factory and the important setup data such as system/indoor/group address set in (AUTO/MANUAL) mode or setting of high ceiling selection have been stored at installation time.
r1 Readout of the setup data from EEPROM (Data in EEPROM contents, which have been changed at the local site, are read out together with data in EEPROM set at shipment from the factory.) 1. Push SET , , and buttons of the remote controller at the same time for 4 seconds or more. (Corresponded with No. in Remote controller) When group operation, the master indoor unit address is displayed at the first time. In this time, the item code (DN) 10 is displayed.
r3 Writing of the setup contents to EEPROM (The contents of EEPROM installed on the service P.C. board have been set up at shipment from the factory.) 1. Push SET , , and buttons of the remote controller at the same time for 4 seconds or more. (Corresponded with No. in Remote controller ) In group operation control, the master indoor unit No. is displayed at the first time. (If the automatic address setup mode is interrupted in item 2. - a) - 2) in the previous page, the unit No. ALL is displayed.
Memorandum for setup contents (Item code table (Example)) DN Item Memo 01 Filter sign lighting time According to type 02 Dirty state of filter 0000: Standard 03 Central control address 0099: Unfixed 06 Heating suction temp shift 0002: +2°C (Floor type: 0) 0F Cooling only 0000: Shared for cooling/heating 10 Type According to model type 11 Indoor unit capacity According to capacity type 12 Line address 0099: Unfixed 13 Indoor unit address 0099: Unfixed 14 Group address 0099: Un
12. SETUP AT LOCAL SITE AND OTHERS 12-1. Indoor Unit 12-1-1. Test Run Setup on Remote Controller button on the remote controller for 4 seconds or more, “TEST” is displayed on LC display. 1. When pushing Then push button. • “TEST” is displayed on LC display during operation of Test Run. • During Test Run, temperature cannot be adjusted but air volume can be selected. • In heating and cooling operation, a command to fix the Test Run frequency is output.
12-1-2. Setup to Select Function Use this function while the indoor unit stops. 1 2 3 4 5 buttons concurrently for 4 seconds or more. Push SET , , and The unit No. displayed at the first time indicates the indoor unit address of the master unit in the group control. In this time, fan and flap of the selected indoor unit operate. Every pushing button, the indoor unit numbers in the group control are displayed successively. In this time, fan and flap of the selected indoor unit only operate.
Item No. (DN) table (Selection of function) Item DN Description At shipment 01 Filter sign lighting time 0000 : None 0002 : 2500H 0004 : 10000H 0001 : 150H 0003 : 5000H 0005 : Clogged sensor used According to type 02 Dirty state of filter 0000 : Standard 0001 : High degree of dirt (Half of standard time) 0000 : Standard 03 Central control address 0001 : No.1 unit 0099 : Unfixed to 0064 : No.
12-1-3. Cabling and Setting of Remote Controller Control 2-remote controller control (Controlled by two remote controllers) One or multiple indoor units are controlled by two remote controllers. (Max. 2 remote controllers are connectable.
12-1-4. Monitor Function of Remote Controller Switch n Call of sensor temperature display Each sensor temperature of the remote controller, indoor unit, and outdoor unit can become known by calling the service monitor mode from the remote controller. SET DATA UNIT No. R.C. No. 1 2 Push + buttons simultaneously for 4 seconds or more to call the service monitor mode. The service monitor goes on, the master indoor unit No.
n Calling of error history The error contents in the past can be called. SET DATA 1 2 3 UNIT No. R.C. Push + buttons simultaneously for 4 seconds or more to call the service check mode. Service Check goes on, the item code 01 is displayed, and then the content of the latest alarm is displayed. The number and error contents of the indoor unit in which an error occurred are displayed.
12-2. Network Adapter Model name: TCB-PCNT20E 12-2-1. Function A network adapter is an optional P.C. board to connect the indoor unit to AI net (Central control remote controller). 12-2-2. Microcomputer Block Diagram Central control remote controller Remote controller Indoor unit Optional communication P.C. board CN41 Indoor control P.C. board CN309 AC220240V Terminal block (A.
12-2-5. Communication Cable Specifications No.
12-3. How to Set an Address Number When connecting indoor units to the central control remote controller by using a network adapter, it is required to set up a network address No. • The network address No. should be agreed with the line No. of the central control remote controller. • When the unit was shipped from the factory, the network address has been set to 1. The following two methods to set the network address are provided. 1.
Table 2 Network address No. setup table (SW01) 〇 : ON side × : OFF side Address No. ① ② ③ ④ ⑤ ⑥ Address No.
12-4. Display and Operation of Main Remote Controller and Central Control Remote Controller 1. Turn on all the power supplies of the air conditioner, and then turn on power of the central control remote controller (Line 16 RBC-SXC1P, Line 64 TCB-SC641). If both power supplies are simultaneously turned on or if they are turned on reversely, the check code [97] may be temporarily displayed on the central remote controller.
13. ADDRESS SETUP 13-1. Address Setup
When an outdoor unit and an indoor unit are connected, or when an outdoor unit is connected to each indoor unit respectively in the group operation even if multiple refrigerant lines are provided, the automatic address setup completes with power-ON of the outdoor unit. The operation of the remote controller is not accepted while automatic address works. (Approx.13-2. Address Setup & Group Control Indoor unit No. : N - n = Outdoor unit line address N (Max. 30) - Indoor unit address n (Max. 64) Group address : 0 = Individual (Not group control) 1 = Master unit in group control 2 = Sub unit in group control Master unit (= 1) : The representative of multiple indoor units in group operation sends/receives signals to/from the remote controllers and sub indoor units.
13-3. Address Setup In case that addresses of the indoor units will be determined prior to piping work after cabling work (Manual setting from remote controller)
• Set an indoor unit per a remote controller. • Turn on power supply. 1 2 (← ← Line address) Using the temperature setup / buttons, set 12 to the item code. 3 4 5 6 7 8 9 (Example of 2-lines cabling) (Real line: Cabling, Broken line: Refrigerant pipe) Push SET + + buttons simultaneously for 4 seconds or more.n Confirmation of indoor unit No. position 1. To know the indoor unit addresses though position of the indoor unit body is recognized • In case of individual operation (Wired remote controller : indoor unit = 1 : 1) (Follow to the procedure during operation) 1 2 Push button if the unit stops. CODE No. UNIT No. Push button. Unit No. 1-1 is displayed on LCD. (It disappears after several seconds.) The displayed unit No. indicate line address and indoor unit address.
RAV-SM800AT-E LED display when SW800 : Bit 1, 2, 3, 4 OFF • • • • When multiple errors are detected, the latest error is displayed. While LED displays 〇 (go on), there is the main cause of error in control at CDB side and it stops abnormally. While LED displays ◎ (flash), there is the main cause of error in control at IPDU side and it stops abnormally. For an error in case thermo operation, the communication is interrupted on the serial circuit.
14. TROUBLESHOOTING 14-1. Summary of Troubleshooting 1. Before troubleshooting 1) Required tools/instruments • + and – screwdrivers, spanners, radio cutting pliers, nippers, push pins for reset switch • Tester, thermometer, pressure gauge, etc. 2) Confirmation points before check The following operations are normal. a) Compressor does not operate.
(a) Outline of Judgment A primary judgment to detect cause of error exists on the indoor unit or outdoor unit is performed in the following procedure. The indoor unit monitors operating status of the air conditioner, and if a protective circuit works, contents of the self-diagnosis are displayed with a block restricted to the following cases on the indoor unit display part.
2. Troubleshooting procedure When a trouble occurred, check the parts along with the following procedure. Trouble → Confirmation of check code by service mode → Check defective position and parts. NOTE : For cause of a trouble, power conditions or malfunction/erroneous diagnosis of microcomputer due to outer noise is considered except the items to be checked. If there is any noise source, change the cable of the signal line to shield cable.
(c) Self-diagnosis with remote controller With the indoor unit control, self-diagnosis of protective circuit action can be done by turning the remote controller operation into service mode, operating the remote controller, observing the remote controller indicators and checking whether TIMER lamp flashes (5 Hz). NOTE : • To perform this self-diagnosis, the remote controller with the service code of 43069666 is required. 1.
1. The self-diagnosis by the check codes is conducted under the block displays. 2. Remote controller key operation under the service mode is conducted by ON/OFF or TEMP. The remote controller display by each key operation is varied as shown below. Two digit number is displayed in a hexadecimal number. 3. The self-diagnosis by the check codes is conducted with procedures shown below.
14-2. Troubleshooting with CHECK Display of Remote Controller 14-2-1. In case of main remote controller/sub-remote controller A RBC-AM1E RBC-AS1E 1. Operation for CHECK display When pushing the CHECK switch, the indoor unit No. (Group address No.) which sends the check code is displayed at the right side of the set up TEMP. display section, and the check data of 2 errors/faults x 16 units is displayed in the set up temp. display section. If there is a filter display, the indoor unit No.
2. Reading of CHECK monitor display <7 segment display> Hexadecimal notation 1 0 2 3 4 5 6 7 8 9 10 11 12 13 14 Decimal notation 15 UNIT CHECK 12 FILTER FILTER sign Indoor unit No. CHECK code (Example) Case that Filter signal is sent from No.1 and No.16 units under group operation UNIT UNIT FILTER FILTER (Example) Room temp.sensor of No.1 is defective. In No.16, first the heat exchanger sensor has failed.
14-2-2. Remote controller with timer RBC-AM1E 1. Operation for CHECK display When pushing the CHECK switch, the indoor unit No. (Group address No.) which sends the check code is displayed in the set up temp. display section, and check code is displayed in the TIME display section. If FILTER display (air filter cleaning sign) is present, the indoor unit No. which sends the filter signal is displayed in the set up temp. display section, and then the check code is displayed.
2. Reading of CHECK monitor display <7 segment display> Hexadecimal notation 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Decimal notation (Example) Filter signal is sent from No.1 and No.15 units under grouping operation FILTER FILTER CHECK CHECK UNIT UNIT CHECK UNIT Unit No. Check code detected at first Check code detected at last (Example) Room temp.sensor of No.1 is defective. In No.15, first the indoor heat exchanger sensor has failed.
14-2-3. Central remote controller 1. Operation for CHECK display When pushing the CHECK switch, the indoor unit No. (Network address No.) including the check data is displayed in the UNIT No. display section, and the check code is displayed in the set up temp. display section.
14-3. Check Code Table Error mode detected by indoor unit (1) Operation of diagnostic function Block display Check code [MODE] [TIMER] lamp 5Hz flash Cause of operation Status of air conditioner The serial signal is not output Operation from outdoor unit to indoor unit. continues • Miscabling of inter-unit cables Judgment and measures Condition Displayed when 1. Outdoor unit does not completely error is detected operate.
Error mode detected by indoor unit (1) Operation of diagnostic function Block display Check code [MODE] lamp 5Hz flash Cause of operation Error in indoor fan system Status of air conditioner All stop Revolutions frequency error of fan Judgment and measures Condition Displayed when 1. Check indoor fan motor connector error is detected circuit (CN210). 2. Check indoor fan. 3. Check indoor P.C. board (Main P.C. board). Error in indoor unit or other positions Operation continues Displayed when 1.
Error mode detected by outdoor unit Operation of diagnostic function Check code Cause of operation Inverter over-current protective circuit operates. (For a short time) Status of air conditioner All stop Judgment and measures Condition Displayed when 1. Inverter immediately stops even if restarted. error is detected • Compressor rare short 2. Check IPDU. • Cabling error Error on current detection circuit All stop Displayed when 1. Compressor immediately stops even if restarted.
14-4. Troubleshooting for Each Check Code [1A error] Are connections of CN301 and CN300 of CDB correct? YES Does the fan rotate without trouble when handling the fan with hands under condition of removing CN301 and CN300 from CDB? CN301 NO YES The status that the resistance values between leads below are 50 to 80 for 40W motor (ICF-140-43) and 25 to 55 for 60W motor (ICF-140-63-1) is normal.
[04 error] NO Does outdoor unit operate? YES Are 1, 2, 3 inter-unit cables normal? NO Correct inter-unit cable. YES Are connections of connectors normal? NO Correct connection of connector. YES Is DC310 to 340V applied between terminals of electrolytic capacitor of IPDU main circuit? NO * For RAV-SM560AT-E, replace control P.C. board. YES * For RAV-SM560AT-E, check case thermo. Is DC310 to 340V power supplied to CDB? (CN03) Replace IPDU. NO Replace IPDU.
[08 error] Is operation of 4-way valve normal? NO Is 200V applied to 4-way valve coil terminal in heating operation? YES YES NO Is flow of refrigerant by 2-way valve, check valve, or electron expansion valve normal? NO Check 4-way valve. YES Check and replace 2-way valve, check valve, or electron expansion valve. NO Is circuit cable normal? YES Check and correct circuit. Are characteristics of TC sensor resistance value normal? NO * For RAV-SM560AT-E, check control P.C. board.
[0d error] Is connection of TC sensor connector (Indoor P.C. board CN05) normal? NO Correct connection of connector. YES Are characteristics of TC sensor resistance value normal? YES NO Replace TC sensor. * Refer to Characteristics-2. Check indoor P.C. board (MCC-1370A). Replace Defect [0F error] Is connection of TCJ sensor connector (Indoor P.C. board CN20) normal? NO Correct connection of connector. YES Are characteristics of TCJ sensor resistance value normal? YES NO Replace TCJ sensor.
[99 error] NO Is inter-unit cable of A, B and C normal? Correct inter-unit cable of remote controller. YES Is there no disconnection or contact error of connector? YES Correct connection of connector. Check circuit cables. NO YES Is individual (1 : 1) operation? NO NO Set the unit to No.1. Is unit set to No.1? YES Are not No.1 unit duplicated? NO YES NO Does indoor unit operate? YES Does LED (Green) on indoor main P.C. board flash? (D13) YES NO Avoid duplication of unit No.1 setting.
[11 error] Turn off the breaker once. Turn on the breaker after approx. 10 seconds. Does fan stop when operation stopped? NO YES Is DC1V or more voltage applied between 5 + and 3 – of the motor connector (CN210)? NO Replace indoor fan motor. YES Start the operation with cooling mode [L (Low)]. NO Does the fan rotate? YES Is DC280V or more voltage applied between 1 + and 3 – of the motor connector (CN210)? Replace indoor main P.C. board (MCC-1370A).
[11 error] Indoor fan starts rotating by inserting receptacle. P.C. board CN210 [Check output voltage (DC) of P.C. board fan motor.] 6 (Blue) Yellow Measure the voltages of the motor connector CN210 Pin 3 (GND (minus): Black) and Pin 5 (V line (plus): Yellow) under condition that indoor fan rotates. 5 (Yellow) 4 (White) Black 3 (Black) 2 – 1 (Red) DC1.0V or more DC1.0V or less DC Defective indoor main P.C. board (MCC-1370A) Defective indoor fan motor [12 error] NO Check power voltage.
[14 error] NO Improve the power supply line. Is power voltage normal? YES Are connections of cabling/connector normal? Check and correct circuit cables. Correct connection of connector. Check and correct reactor connection. NO YES * For RAV-SM560AT-E, check RY01 on the control P.C. board. Does RY01 relay of IPDU operate? YES Is not “14” errors output when an operation is performed by removing 3P connector of compressor? NO NO YES * Single-phase type is not provided to RAV-SM560AT-E. Replace IPDU.
[18 error] Are connections of TE/TS sensor connectors of CDB CN604/CN605 normal? NO YES Correct connection of connector. * (For RAV-SM560AT-E, CN600 TE sensor and CN603 TS sensor) NO Are characteristics of TE/TS sensor resistance values normal? Replace TE and TS sensors. * Refer to Characteristics-3. YES Check CDB. Replace Defect * For RAV-SM560AT-E, replace the control P.C. board [19 error] NO Is connection of TD sensor connector of CDB CN600 normal? YES Correct connection of connector.
[1d error] NO Improve power line. Is power voltage normal? YES Are connections of cable/connector normal? Check and correct circuit cabling such as cabling to compressor (phase missing) and connector. NO YES NO Is there no slackened refrigerant? Is compressor normal? YES NO Compressor lock Replace YES Does electron expansion valve normally operate? NO Check TE and TS sensors. Replace Check electron expansion valve. Replace YES Check IPDU and CDB.
[21 error] [ ] LCD flash Is high-voltage protective operation by TE sensor normal? NO YES NO Is connection of cabling connector normal? Correct connection of cabling connector. YES Check TE sensor. Defect Replace Does cooling outdoor fan normally operate? NO YES NO Is connection of connector normal? Correct connection of connector. YES NO Is fan motor normal? Replace fan motor.
14-5. Simple Check Method for Main Parts 14-5-1. Indoor unit 1 Part name Check procedure Temperature sensor (Ta) Measure the resistance value with tester by removing the connector. Heat exchanger sensor (Tc) (Normal temperature) Heat exchanger sensor (Tcj) Normal value 2 Louver motor MP35EA12 Indoor fan motor (ICF-340-30-1) Refer to Characteristics table. Measure the resistance value of each winding coil with tester.
Relational graph of temperature sensor resistance value and temperature 20 40 TA sensor TC, TCJ sensor 30 Caracteristics-2 Caracteristics-1 Resistance (k ) Resistance (k ) 10 20 10 0 10 20 30 40 0 –10 50 0 10 Temperature [ C] 20 30 40 50 60 70 Temperature [ C] 20 200 TE, TO, TS sensor Caracteristics-3 Resistance (k ) (10 C or higher) Resistance (k ) (10 C or lower) 10 100 0 0 -10 0 10 20 30 40 50 60 70 Temperature [ C] TD sensor 200 20 Caracteristics-4 Resi
Resistance (K ) (10 C or higher) 20 Resistance (K ) 200 TH sensor Caracteristics-5 150 15 100 10 50 5 –30 –20 –10 0 10 20 30 40 Temperature [ºC] – 134 – 50 60 70 80 90 100
15. DETACHMENTS 15-1. Indoor Unit RAV-SM560UT-E, SM800UT-E No. Part name Q Suction grille Remarks Procedure REQUIREMENT Never forget to put on the gloves at disassembling work, otherwise an injury will be caused. Knob of suction grille 1. Detachment 1) Stop operation of the air conditioner, and then turn off switch of the breaker. 2) Hang down the suction grille while sliding two knobs of the suction grille inward.
No. Part name S Adjust corner cap Procedure 1. Detachment 1) Perform work of item 1. of Q. 2) Remove screws at 4 corners of the suction port. (Ø4 x 10, 4 pcs.) 3) Push the knob outward and remove the adjust corner cap by sliding it. Remarks Screw 2. Attachment 1) Mount the adjust corner cap by sliding it inward. 2) Tighten screws at 4 corners of the suction port. (Ø4 x 10, 4 pcs.) Push outward T Ceiling panel 1. Detachment 1) Perform works of items 1 of Q, 1 of R and 1 of S.
No. Part name U Control P.C. board Procedure 1. Detachment 1) Perform works of items 1 of Q and 1 of R. 2) Remove connectors which are connected from the control P.C. board to other parts.
No. Part name V Fan motor Procedure Remarks 1. Detachment 1) Perform works of items 1 of Q and 1 of R. 2) Remove clamps of the lead wires connected to the following connectors of the control P.C. board.
No. Part name W Drain pan Remarks Procedure 1. Detachment 1) Perform works of items 1 of Q, 1 of R, 1 of S and 1 of T. 2) Remove clamps of the lead wires connected to the following connectors of the control P.C. board.
No. Part name X Drain pump assembly Procedure 1. Detachment 1) Perform works of items 1 of Q, 1 of R, 1 of S, 1 of T and 1 of W. 2) Picking the hose band, slide it from pump connecting part to remove the drain hose. 3) Remove screw fixing the drain pump assembly, slide hooking claws of the drain pump assembly and the main body (1 position), and then remove the assembly. (Ø4 x 8, 3 pcs.) Remarks Slide to hose side. Hose band 3. Attachment 1) Fix the drain pump assembly as before.
No. Procedure Part name Remarks Y Heat exchanger 1. Detachment 1) Recover refrigerant gas. 2) Remove refrigerant pipe at the indoor unit side. 3) Perform works of items 1 of Q, 1 of R, 1 of S, 1 of T and 1 of W. 4) Remove screws fixing the pipe cover. (Ø4 x 8, 2 pcs.) 5) Remove the heat exchanger by removing fixing band and fixing screws while holding the heat exchanger. (Ø4 x 8, 3 pcs.) 2.
15-2. Replacement of Distributor Assembly RAV-SM560UT-E 1. Cutting of Capillary Tube A capillary tube ( 023 : Inner diameter 2mm, Length 1000mm) is brazed to a distributor assembly. Cut and divide the tube to each length as shown below. Ref No. No. of capillary tubes Cutting 023 4 200 mm : 2 pcs. 400 mm : 2 pcs. [Cutting] Plane circumference of the capillary tube with triangle file, etc., and then break off it. NOTE) Break off the capillary tube so that inner diameter is not deformed 2.
RAV-SM800UT-E 1. Cutting of Capillary Tube A capillary tube ( 025 026 : Inner diameter 2mm, Length 1000mm) is brazed to a distributor assembly. Cut and divide the tube to each length as shown below. Ref No. No. of capillary tubes 025 7 100 mm : 1 pc. 300 mm : 1 pc. 400 mm : 1 pc. 600 mm : 2 pcs. 700 mm : 1 pc. 800 mm : 1 pc. 026 10 100 mm : 2 pcs. 150 mm : 1 pc. 500 mm : 4 pcs. 600 mm : 2 pcs. 900 mm : 1 pc. Cutting [Cutting] Plane circumference of the capillary tube with triangle file, etc.
15-3. Replacement of Main Parts RAV-SM560BT-E, SM800BT-E Be sure to turn off the power supply before disassembling work. No. Item 1 Electric parts box 2 3 4 5 Fan Drain pan Heat exchanger TC sensor (Sensor side) Procedure 1) Remove the electric parts box. (Supplement: Refer to How to remove the electric parts box.) In this time, remove connectors of TA sensor, TC sensor, and TCJ sensor, if necessary.) Electric parts fixing screw 1) Remove connector of the fan motor.
AID-P710BH, P800BH, P1120BH Be sure to turn off the power supply before disassembling work. No. Item 1 Electric parts box Procedure 1) Remove the electric parts box. (Supplement: Refer to How to remove the electric parts box.) In this time, remove connectors of TA sensor, TC sensor, and TCJ sensor, if necessary.) Electric parts fixing screw 2 Fan 1) Remove connector of the fan motor.
[SUPPLEMENT] How to remove the electric parts box Electric parts box The electric parts box is fixed to the indoor unit with claws at the rear side. Lift up it once and pull toward you. Then claws come off. Hook F7-4 3-4 Procedure 2 Remove these two screws to remove the electric parts box. Electric cable Remote controller cable Electric parts box cover A hole at the ceiling surface side is fixed to upper part of the electric parts box with claws. Lift up it once and pull toward you.
15-4. Replacements of Main Parts 15-4-1. Indoor Unit No. Part name Front panel Remarks Procedure 1) Stop operation of the air conditioner, and turn off the power supply. 2) Push “PUSH” part at the lower side of the front panel, and then take off claws of the front panel from the installation board. 3) Open the suction grille and take off the front panel fixing screws (4 pcs.). 4) After turning the side grille as shown in the right figure, perform the following works.
No. Part name Electric parts box assembly Side grille Procedure Remarks 6) Take off fixing screw (1 position) of the electric parts base, and then pull out the electric parts base toward you. 7) Pull out Tc sensor and Tcj sensor from sensor holder of the heat exchanger. After replacement of the parts, incorporate two sensors without mistake as shown in the right figure. (Tube is attached to Tcj sensor.
No. Fan motor Remarks Procedure Part name 1) Perform work of item . 2) Perform work of item . 3) Loosen set screw of the cross flow fan from the discharge port. 4) Remove the bushing (right). Bushing (right) Set screw Push this part upward Cross fan Fixing screws 5) Take off two fixing screws of the motor band (right). 6) Pull out the motor band (right) and the fan motor outward.
15-4.2. Replacement Procedure of Service Main P.C. Board Replacement Procedure of Indoor Control P.C. Board (AIK-PXXXH series, SIK-PXXXH series) For this indoor control P.C. board [AIK/SIK-P SERVICE] corresponding to the common P.C. boards, follow to this replacement procedure when replacing P.C. board. (When using SIK-PXXXH series, P.C. board name, parts layout, etc. of the presently mounted P.C. board differ from those of this service P.C. board. However there is no problem in the functions.
[Mounting] In case of AIK-PXXXH series 1. As same as P.C. board before replacement, attach a cable (Black) which is screwed to the electric parts box to CN240 without using a cable (Black) attached previously to CN240 of the service P.C. board. CN204 Cable (Remove a cable attached previously to CN240 of the service P.C. board.) Service P.C. board 2. Attach other cables as same as P.C. board before replacement.
CN213 display part CN04 temp. sensor CN05 heat exchanger CN240 Label CN231 CN230 P.C.
15-5. Outdoor Unit RAV-SM560AT-E No. Part name Common procedure Procedure Remarks CAUTION Valve cover Never forget to put on the gloves at working time, otherwise an injury will be caused by the parts, etc. 1. Detachment 1) Stop operation of the air conditioner, and turn off the main switch of the breaker for air conditioner. 2) Remove the valve cover. (ST1T Ø4 x 10L, 1 pc.) • After removing screw, remove the valve cover pulling it downward. 3) Remove wiring cover (ST1T Ø4 x 10L, 2 pcs.
No. Part name Front cabinet Remarks Procedure 1. Detachment 1) Perform work of item 1 of . 2) Remove screws (ST1T Ø4 x 10L, 2 pcs.) of the front cabinet and the inverter cover. 3) Take off screws of the front cabinet and the bottom plate. (ST1T Ø4 x 10L 3 pcs.) 4) Take off screws of the front cabinet and the motor support. (ST1T Ø4 x 10L, 2 pcs.) • The left side of the front side if made to insert to the rear cabinet, so remove it pulling upward. 3.
No. Part name Inverter assembly Procedure 1. Detachment 1) Perform work of item 1 of . 2) Take off screws of the upper part of the front cabinet. • If removing the inverter cover under this condition, P.C. board can be checked. • If there is no space in the upper part of the upper cabinet, perform work of . CAUTION Remarks Screws Front cabinet Inverter cover Be careful to check the inverter because high-voltage circuit is incorporated in it.
No. Part name Control P.C. board assembly Remarks Procedure 1) Disconnect lead wires and connectors connected from the control P.C. board assembly to other parts. 1. Lead wires • Connection with the power terminal block: 3 wires (Black, White, Orange) • Earth wire: 1 wire (Black) 2. Connectors • Connection with compressor: Remove 3P connector.
No. Part name Rear cabinet Fan motor Remarks Procedure 1) Perform works of items 1 of and , . 2) Take off fixed screws for the bottom plate. (ST1T Ø4 x 10L, 3 pcs.) 3) Take off fixed screws for the heat exchanger. (ST1T Ø4 x 10L, 2 pcs.) 4) Take off fixed screw for the valve mounting plate. (ST1T Ø4 x 10L, 1 pc.) 1) Perform works of items 1 of and . 2) Take off the flange nut fixing the fan motor and the propeller. • Turning it clockwise, the flange nut can be loosened.
No. Part name Compressor Procedure Remarks 1) Perform works of items 1 of and , , , . 2) Discharge refrigerant gas. 3) Remove the partition plate. (ST1T Ø4 x 10L, 2 pcs.) 4) Remove the noise-insulator. 5) Remove the terminal covers of the compressor, and disconnect lead wires of the compressor and the compressor thermo assembly from the terminal. 6) Remove pipes connected to the compressor with a burner.
No. Part name Procedure Remarks Pulse Modulating 1. Detachment Valve (PMV) coil 1) Perform works of items and . 2) Release the coil from the concavity by turning it, and remove coil from the PMV. PMV body Positioning extrusion 2. Attachment 1) Put the coil deep into the bottom position. 2) Fix the coil firmly by turning it to the concavity. Concavity PMV coil Fan guard 1. Detachment 1) Perform works of items 1 of , and .
RAV-SM800AT-E No. Part name Common procedure Procedure Remarks CAUTION Never forget to put on the gloves at working time, otherwise an injury will be caused by the parts, etc. 1. Detachment 1) Stop operation of the air conditioner, and also turn off switch of the breaker. 2) Remove the front panel. (ST1T Ø4 x 10L, 3 pcs.) • After taking off screws, remove the front panel by pulling it downward. 3) Disconnect the connecting cables and power cord from the terminals and cord clamp.
No. Procedure Part name Remarks Discharge port 1. Detachment cabinet 1) Perform work of item 1 of . 2) Take off screws (ST1T Ø4 x 10L, 3 pcs.) of discharge port cabinet for the partition plate. 3) Take off screws (ST1T Ø4 x 10L, 2 pcs.) of discharge port cabinet for the bottom plate. 4) Take off screw (ST1T Ø4 x 10L, 1 pc.) of discharge port cabinet for the heat exchanger. 5) Take off screws (ST1T Ø4 x 10L, 2 pcs.) of discharge port cabinet for the fin guard. Side cabinet Inverter Fin guard 2.
No. Part name Inverter assembly Procedure 1) Perform works of items of 1) to 5) of . 2) Take off screw (ST1T Ø4 x 10L, 1 pc.) of the upper left part of the inverter cover. • If removing the inverter cover under this condition, P.C. board can be checked. • If there is no space in the upper part of the upper cabinet, perform works of items 6) to 7) of (1) and remove the partition fixing plate. (ST1T Ø4 x 10L, 1 pc.
No. Part name Control P.C. board assembly Remarks Procedure 1) Remove the inverter box from P.C. board base. 2) Disconnect lead wires and connectors connected from the control P.C. board assembly to other parts. 1. Lead wires: With the power terminal block: 2 pcs. (Single phase) (Red, White) With the compressor: 3 pcs. (Red, White, Black) 2.
No. Part name Fan motor Remarks Procedure 1) Perform works of items 1) to 5), 7) of 2) Remove the flange nut fixing the fan motor and the propeller fan. • Loosen the flange nut by turning clockwise. (To tighten the flange nut, turn it counterclockwise.) 3) Remove the propeller fan. 4) Remove the lead wire from the hook fixing the fan motor lead wires on the motor base. (Three positions) 5) Disconnect the connector for fan motor from the inverter. 6) Take off the fixing screws (4 pcs.
No. Part name Compressor Procedure Remarks 1) Perform works of items , , , , and . 2) Evacuate refrigerant gas. 3) Disconnect the connector for fan motor from the inverter. 4) Take off screws fixing the motor base to the bottom plate. (ST1T Ø4 x 10L, 2 pcs.) 5) Remove the motor base together with the fan motor and the propeller fan. 6) Take off screws fixing the partition plate to the valve support plate. (ST1T Ø4 x 10L, 2 pcs.) 7) Remove the valve support plate. (M6 x 4 pcs.
No. Part name Reactor Procedure 1) Perform works of items 1 of and . 2) Take off screws fixing the reactor. (Ø4 x 10L , 2 pcs. per one reactor. An outdoor unit has two reactors on the partition plate.) Remarks Screws Partition plate Reactor Pulse Modulating Valve (PMV) coil 1. Detachment 1) Perform works of items 1 of and . 2) Remove the coil from PMV body while pulling it upward. PMV body Positioning extrusion 2.
No. Part name Fan guard Procedure Remarks 1. Detachment 1) Perform works of items 1 of and . 2) Remove the air flow cabinet, and put it down so that the fan guard side directs downward. Discharge port cabinet Bell mouth Perform work on a corrugated cardboard, cloth, etc. to prevent flaw to the product. Remove two screws 3) Take off screws fixing the bell mouth. (ST1Tf4 x 10L, 2 pcs.) 4) Remove the bell mouth.
16. EXPLODED VIEWS AND PARTS LIST 16-1. Indoor Unit 4-Way Air Discharge Cassette Type RAV-SM560UT-E/RAV-SM800UT-E 209 229 CODE No. SET DATA UNIT No. 225 208 SETTING TEST 202 226 201 207 210 203,204 No. UNIT SET 224 R.C. 215,216,217, 218,221,222 211,212,213, 214,219,220 CL 223 227,228 206 Location No. Part Description Location No.
402 A B 404 405 403 Location No. Part Description 401 402 403 404 43060750 43050382 43150297 43160445 405 4316V188 Terminal Block, 3P Sensor, TC (F6) Sensor, TC Terminal Block, 2P, 1A, AC30V P.C.
Concealed Duct Type RAV-SM560BT-E/RAV-SM800BT-E 230,231 202,203 210,211,214, 215,218,219 204 227 212,213,216, 217,220,221 CODE No. SET DATA UNIT No. SETTING TEST R.C. No. 224,225 222 Location No. Part 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 43120149 4314J100 4314J101 43147654 43147655 43121643 43121645 43191304 43191305 43047545 43047546 43194081 43194078 43194051 43194026 43194080 43194079 208,209 Description 206,207 201 UNIT SET CL Location No.
403 402 3 401 A B 1 2 406 404 405 Location No. Part 401 402 403 404 43060750 43050382 43150299 43160445 405 4316V189 406 43158180 Description Terminal Block, 3P Sensor, TC (F6) Sensor, TA Terminal Block, 2P, 1A, AC30V P.C.
RBC-U21PG(W) - E 304 311 312 306 305 307 301 303 313 302 310 308 309 Location No. Part 301 302 303 304 305 306 307 43409164 43480010 43407120 4302C029 43409173 43422001 43422002 Description Location No.
High-Wall Type RAV-SM560KRT-E/RAV-SM800KRT-E 220 219 221 232 213 229 222 227 201 218 216 211 228 230 208 209 231 226 203 217 205 224 223 225 212 210 207 204 236 233 202 206 Location No. Part Description Location No.
RAV-SM560KRT-E/RAV-SM800KRT-E 411 410 406 408 402 401 412 413 404 404 403 Location No. Part Description Location No. Part Description 401 402 403 404 406 408 410 43T60047 43T60320 43T60321 43T50304 43T69005 43T58302 43T69346 Terminal, 3P Terminal, 3P Terminal, 2P Temperature Sensor, TC, TCJ Sensor, Thermostat, TA Transformer, TT-02 P.C. Board, Ass’y, MCC1370A, MCC-1370B (SM560KRT-E) 410 43T69347 411 43T69325 412 43T69066 413 43162047 P.C.
16-2. Outdoor Unit 4 RAV-SM560AT-E 31 INVERTER 11 30 25 17 13,14 2 29 10 9 18 7 8 28 26 21, 22 23, 24 27 3 12 6 15 16 20 5 19 1 Location No.
702 TE Sensor TS Sensor TO Sensor TD Sensor 701 705 703 704 Location No. Part 701 43050334 702 43050382 703 704 43062228 43160469 706 4316V182 Description Sensor, TD (F4), TD Sensor Sensor, TC (F6), TC Sensor Base, P.C. Board, ABS Terminal Block, 6P, AC250V, 20A P.C.
Revised 3/June/2004 RAV-SM800AT-E 4 5 11 38 37 10 8 9 36 32 21,22 34 24 2 23 7 35 30 14 1 6 31 3 13 27 15 18 33 16,17 12 19 20 26 Location No. Part Description Location No.
INVERTER COVER 708,709 702 TO Sensor TE Sensor TS Sensor TD Sensor 706 701 INVERTER BOX 707 704 703,705 Location No. Part Description 701 702 704 43050334 43050382 43160469 705 707 43162042 4316V183 708 4316V184 Sensor, TD (F4), TD Sensor Sensor, TC (F6), TC Sensor Terminal Block, 6P, AC250V, 20A Base, P.C. Board, ABS P.C. Board Ass’y, CDB, MCC-1398 P.C.
RAV-SM560XT-E/RAV-SM800XT-E 220 222 217 227 224 218 214 208 207 223 208 212 203 206 202 216 219 235 204 221 225 226 213 210 211 229 215 209 233 228 231 205 201 235 234 232 230 Location No. Part Description Location No.
401 403 402 404 405 406 408 Location No. Part 401 401 401 401 402 43T69311 43T69312 43T69313 43T69314 43T50004 407 Description P.C. Board P.C. Board P.C. Board P.C.