Pocket Quick Reference Guide 2012 On the TOSHIBA RBC-AMT32E / RBC-AMS41E Remote Controllers
Quick Reference Guide To assist service engineers working on Toshiba air conditioning equipment, there is a large quantity of data available via the standard remote controller, either the RBC-AMT32E or the RBC-AMS41E, this data is NOT available via an Infra Red remote or the RBC-AS21E2 simplified remote controller. Accessing the data is a simple process of pressing a sequence of buttons on the remote controller.
Digital/Super digital “0-1-2-3” series data Code 00 01 02 03 04 Indoor Data Room Temp (Control Temp) (oC) Room Temp. (Remote Controller) (oC) TA Return Air Temp. (oC) TC Coil – Vapour Temp. (oC) TCJ Coil – Liquid Temp. (oC) Code 60 61 62 63 65 Outdoor Data TE Sub-cooled Liquid Temp. (oC) TO Ambient Temp. (oC) TD Discharge Temp. (oC) TS Suction Temp. (oC) THS – Inverter Heat Sink Temp. (oC) Code 60 61 62 63 65 6A 70 72 73 F1 Outdoor Data TE Sub-cooled Liquid Temp. (oC) TO Ambient Temp.
VRF Outdoor data for SMMSI equipment Code *0 *1 *2 *3 *4 *5 *6 *7 *8 *9 *A *B *C *D *E *F Outdoor Data Code Outdoor Data Pd – High Pressure Sensor (MPa) #0 Compressor 1 Revolutions (rps) Ps – Low Pressure Sensor (MPa) #1 Compressor 2 Revolutions (rps) Td1 – Compressor 1 Discharge Temp. (oC) #2 Compressor 3 Revolutions (rps) o Td2 – Compressor 2 Discharge Temp. ( C) #3 Outdoor Fan Mode o Td3 – Compressor 3 Discharge Temp. ( C) #4 Compressor IPDU 1 Heat Sink Temp. (oC) o TS – Suction Temp.
Common Configurable Control Options *Accessed via Toshiba hard wired remote controller RBC-AMT32E and RBC-AMS41E Relocation of room temperature sensing from return air to remote controller sensor Press and hold the TEST, SET & CL Buttons simultaneously for 4 seconds The Engineering Menu is accessed at item code 10 Use the Temperature Buttons to navigate to item code 32 Use the Timer Buttons to adjust the value from 0000 to 0001 Press SET to acknowledge the change Press Test to exit the Engineering Me
Simplified Instructions for the RBC-AMS41E Remote Controller Setting Present Time and Day of Week Press and hold SCHEDULE for 4 seconds, (setting appears on screen) Press DAY until the correct day of the week is indicated Press TIME up and down keys to set current time Press SET to confirm entries. Day and time now set. Setting ON and OFF Times (scheduled operations) 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11.
Time, Temperature and Mode Selection when Programming the RBC-AMS41E Setting Present Time and Day of Week Press and hold SCHEDULE for 4 seconds, (setting appears on screen) Press DAY until the correct day of the week is indicated Press TIME up and down keys to set current time Press SET to confirm entries. Day and time now set. Setting Scheduled Operations with Mode and Temperature functionality 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24.
Contact details: Cool Designs Ltd Technical Support 0844 800 0250 Toshiba Air Conditioning 24/7 technical support 0870 843 0333 Text back service 07624 803 017 (Type fault code in lower case no spaces)