E6581160 Safety precautions I Contents Read first Industrial Inverter Connection For 3-phase induction motors Operations Instruction Manual TOSVERTTM VF-S11 < Simplified manual > Basic VF-S11 operations Monitoring the operation status Measures to satisfy the standards Table of parameters and data Specifications Before making a service call Measures to satisfy the standards 1-phase 240V class 3-phase 240V class 3-phase 500V class 3-phase 600V class 0.2 0.4 0.4 0.75 2.
E6581160 I. I Safety precautions The items described in these instructions and on the inverter itself are very important so that you can use the inverter safely, prevent injury to yourself and other people around you as well as to prevent damage to property in the area. Thoroughly familiarize yourself with the symbols and indications shown below and then continue to read the manual. Make sure that you observe all warnings given.
E6581160 I Q General Operation Danger • Never disassemble, modify or repair. This can result in electric shock, fire and injury. For repairs, call your sales distributor. Disassembly prohibited Prohibited Mandatory • Never remove the front cover when power is on or open door if enclosed in a cabinet. The unit contains many high voltage parts and contact with them will result in electric shock. • Don't stick your fingers into openings such as cable wiring hole and cooling fan covers.
E6581160 I Q Transportation & installation Danger Prohibited Mandatory • Do not install or operate the inverter if it is damaged or any component is missing. This can result in electric shock or fire. Please consult your local sales agency for repairs. Call your local sales agency for repairs. • Do not place any inflammable objects nearby. If a flame is emitted due to malfunction, it may result in a fire.
E6581160 I Danger Mandatory Be Grounded • Electrical installation work must be done by a qualified expert. Connection of input power by someone who does not have that expert knowledge may result in fire or electric shock. • Connect output terminals (motor side) correctly. If the phase sequence is incorrect, the motor will operate in reverse and that may result in injury. • Wiring must be done after installation.
E6581160 Warning Prohibited • Observe all permissible operating ranges of motors and mechanical equipment. (Refer to the motor's instruction manual.) Not observing these ranges may result in injury. When sequence for restart after a momentary failure is selected (inverter) Warning Mandatory • Stand clear of motors and mechanical equipment. If the motor stops due to a momentary power failure, the equipment will start suddenly after power recovers. This could result in unexpected injury.
E6581160 Contents I Safety precautions .........................................................................................................................................................1 1. Read first........................................................................................................................................................................7 1.1 Check product purchase ...................................................................................................
E6581160 1. Read first Thank you for your purchase of the Toshiba “TOSVERT VF-S11” industrial inverter. This manual is a simplified version. If you need a detailed explanation, refer to the full version of English manual (E6581158). 1 This is the Ver. 108 / Ver. 109 CPU version inverter. Please be informed that CPU version will be frequently upgraded. 1.1 Check product purchase Before using the product you have purchased, check to make sure that it is exactly what you ordered.
E6581160 CD-ROM E6581167 Contains the instruction manual in digital form. Some models do not come with this CD-ROM. 1 Warning Do not play this CD-ROM on any audio CD player to avoid hearing loss due to very loud noises or damage to the CD player. Prohibited [System requirements] OS: Microsoft Windows 98/NT/2000/XP Browser: Internet Explorer 4.
E6581160 1.2 Contents of the product Explanation of the name plate label. Always shut power off first then check the ratings label of inverter held in a cabinet. Type Form V F S 11 S Model name TOSVERT VF-S11series 2 0 0 7 P L E - W N - A 2 2 Applicable motor capacity Input (AC) voltage 2 : 200V to 240V 4 : 380V to 500V 6 : 525V to 600V 002 : 0.2kW 004 : 0.4kW 005 : 0.55kW 007 : 0.75kW 015 : 1.5kW 022 : 2.2kW 037 : 3.7kW 055 : 5.5kW 075 : 7.
E6581160 2. Connection 2.1 Standard connections 2.1.1 2 Standard connection diagram 1 This diagram shows a standard wiring of the main circuit.
E6581160 2.1.
E6581160 2.2 Description of terminals 2.2.1 Power circuit terminals In case of the lug connector, cover the lug connector with insulated tube, or use the insulated lug connector. 2 Screw size tightening torque M3.5 screw 0.9Nm 7.1lb y in M4 screw 1.3Nm 10.7lb y in M5 screw 2.5Nm 22.3lb y in M6 screw 4.5Nm 40.1lb y in Q Power circuit Terminal symbol R/L1,S/L2,T/L3 U/T1,V/T2,W/T3 Connect to braking resistors. Change parameters H , H , H , H if necessary.
E6581160 Voltage class Capacity of applicable motor (kW) Inverter model Power circuit (mm2) (Note 1.) 0.4 0.75 1.5 2.2 4.0 5.5 7.5 11 15 0.75 1.5 2.2 4.0 5.5 7.5 11 15 VFS11-4004PL VFS11-4007PL VFS11-4015PL VFS11-4022PL VFS11-4037PL VFS11-4055PL VFS11-4075PL VFS11-4110PL VFS11-4150PL VFS11-6007P VFS11-6015P VFS11-6022P VFS11-6037P VFS11-6055P VFS11-6075P VFS11-6110P VFS11-6150P 2.0 (2.0) 2.0 (2.0) 2.0 (2.0) 2.0 (2.0) 2.0 (2.0) 2.0 (2.0) 3.5 (2.0) 5.5 (2.0) 8.0 (5.5) 2.0 2.0 2.0 2.0 2.0 2.0 3.5 5.
E6581160 Q Control circuit terminals 2 Input/output F Input R Input RES Input S1 Input S2 Input S3 Input PLC Input (common) CC Common to Input/output Electrical specifications Function Shorting across F-CC causes forward rotation; open causes slowdown and stop. (When ST is always ON) Shorting across R-CC causes reverse rotation; open causes slowdown and stop. (When ST is always ON) This inverter protective function is disabled if RES are CC is connected.
E6581160 Terminal symbol Input/output Electrical specifications Function Inverter internal circuits Multifunction programmable analog input. Standard default setting: 0~10Vdc input and 0~60Hz (0~50Hz) frequency VIB FM Input Output By changing parameter setting, this terminal can also be used as a multifunction programmable contact input terminal. When using the sink logic, be sure to insert a resistor between P24 and VIB. (4.7 kΩ―1/2 W) Multifunction programmable analog output.
E6581160 Terminal symbol RY RC 2 Input/output Output Electrical specifications Function Multifunction programmable relay contact output. Standard default settings detect and output low-speed signal output frequencies. Multifunction output terminals to which two different functions can be assigned. Inverter internal circuits +24V 250Vac-1A (cosφ=1) : at resistance load 30Vdc-0.5A 250Vac-0.5A (cosφ=0.
E6581160 Q SINK (Negative) logic/SOURCE (Positive) logic (When an external power supply is used) The PLC terminal is used to connect to an external power supply or to insulate a terminal from other input or output terminals. As for input terminals, turn the SW1 slide switch to the PLC position.
E6581160 Q Logic switching/Voltage-current output switching (slide switch) (1) Logic switching Use SW1 to switch between logics. Switch between logics before wiring to the inverter and without supplying power. If switching between sink, source and PLC is done when power is turned on after switching or when the inverter is supplied with power, the inverter might become damaged. Confirm it before supplying power.
E6581160 3. Operations 3.1 Simplified Operation of the VF-S11 The procedures for setting operation frequency and the methods of operation can be selected from the following.
E6581160 3.1.1 How to start and stop [Example of a EOQF setting procedure] Key operated LED display Operation Displays the operation frequency (operation stopped). (When standard monitor display selection H = [Operation frequency]) MODE CWJ 3 EOQF Displays the first basic parameter [History (CWJ)]. Press either the or key to select “EOQF”. Press ENTER key to display the parameter setting. (Default setting: ). Change the parameter to (terminal board) by pressing the ⇔EOQF key.
E6581160 3.1.2 How to set the frequency [Example of a HOQF setting procedure] Key operated LED display Operation Displays the operation frequency (operation stopped). (When standard monitor display selection H = [Operation frequency]) MODE CWJ HOQF Press either the key or key to select “HOQF”. Press ENTER key to display the parameter setting. (Default setting: ).
E6581160 (3) Setting the frequency using the operation panel (HOQF= or ) Frequency setting 1) Setting the frequency using external potentiometer ★Potentiometer Setting frequency using the potentiometer (1-10kΩ, 1/4W) PP VIB 3 : Setting frequency using potentiometer 60Hz Frequency CC 0 MIN MAX * The input terminal VIA can be used in the same way.
E6581160 3.2 How to operate the VF-S11 Overview of how to operate the inverter with simple examples. Setting the operation frequency using built-in potentiometer and running and stopping using the operation panel. Ex.
E6581160 Setting the operation frequency using the operation panel and running and stopping using the operation panel. Ex.2 (1) Wiring PO MCCB 3 PA/+ PB PC/- R/L1 S/L2 T/L3 Motor U/T1 * Noise filter Power circuit V/T2 IM W/T3 Braking circuit (2) Parameter setting Title (3) Function Programmed value EOQF Command mode selection 1 HOQF Frequency setting mode selection 1 3 Operation Run/stop: Press the and keys on the panel.
E6581160 Setting the operation frequency using built-in potentiometer and running and stopping using external signals. Ex.3 (1) Wiring PO MCCB R/L1 S/L2 T/L3 * Noise filter PA/+ PB PC/- Power circuit Braking circuit F R CC (2) IM Run forward signal Run backward signal Common Parameter setting Title Function Programmed value Command mode selection 0 Frequency setting mode selection HOQF Operation Run/stop: ON/OFF input to F-CC, R-CC.
E6581160 Operation frequency setting, running and stopping using external signals. Ex.4 (1) Wiring PO MCCB 3 PA/+ PB PC/- Motor R/L1 S/L2 T/L3 U/T1 * Noise filter V/T2 Power circuit IM W/T3 Braking circuit F Run forward signal R Run backward signal Common CC Current signal: 4∼20mA VIA CC VIA VIB PP Voltage signal: 0∼10V External potentiometer (Otherwise, input voltage signal (0~10V) between the terminals VIA-CC.
E6581160 4. Basic VF-S11 operations The VF-S11 has the following four monitor modes. Standard monitor mode : The standard inverter mode. This mode is enabled when inverter power goes on. This mode is for monitoring the output frequency and setting the frequency designated value. In it is also displayed information about status alarms during running and trips. • Setting frequency designated values ⇒ see 3.1.
E6581160 Flow of status monitor mode Status monitor mode Flow of monitor as following Setting monitor mode Standard monitor mode 60.0 MODE Display mode Hz MON f60.0 fr-f n<> 10 kinds of data Data of 4 times. n 28 kinds of data t0.10 MODE Of the 10 kinds of data predetermined, any data can be read out 4 times. Data collected at the time of occurrence of a trip is retained. 4 RUN auh PRG MODE 2 t8.56 o}> ENT oc1 4 ENT op3 3 ENT oh 2 ENT oc3 1 a16.
E6581160 4.2 How to set parameters The standard default parameters are programmed before the unit is shipped from the factory. Parameters can be divided into 4 major categories. Select the parameter to be changed or to be searched and retrieved. Basic parameters Extended parameters User parameters (automatic edit function) History parameter * : The basic parameters that must be programmed before the first use. (See 4.2.1) : The parameters for detailed and special setting. (See 4.2.
E6581160 4.2.1 How to set the basic parameters All of the basic parameters can be set by the same step procedures. [Steps in key entry for basic parameters] MODE Switches to the setting monitor mode. Selects parameter to be changed. 4 Reads the programmed parameter setting. * Parameters were factory-set by default before shipment. * Select the parameter to be changed from "Table of parameters".
E6581160 4.2.2 How to set extended parameters The VF-S11 has extended parameters to allow you to make full use of its functions. All extended parameters are expressed with H and three digits. ENT Basic parameters H ~H H 4 MODE Press the V key or the W key to change the set value. Pressing the ENTER key allows the reading of parameter setting. Press the MODE key once and use the VW key to select H from the basic parameters.
E6581160 Q Example of parameter setting Steps in setting are as follows (Example of changing the dynamic braking selection H from 0 to 1.) Key operated LED display . MODE 4 CWJ Operation Displays the operation frequency (operation stopped). (When standard monitor display selection H = [Operation frequency]) The first basic parameter “CWJ” (history function) is displayed. H Press either the H .
E6581160 Key operated LED display W or W H (W T) ↓ CEE MODE Searches for parameters that are different in value from the standard default setting and displays those parameters. Press the ENTER key or the key to change the parameter displayed. (Pressing the key moves the search in the reverse direction). Press the ENTER key to display the set value. Press the key and key to change set value. ⇔CEE Press the ENTER key to save the changed value.
E6581160 Q How to use the history function Key operated LED display MODE 4 CWJ The first basic parameter “CWJ” (history function) is displayed. CEE The parameter that was set or changed last is displayed. Press the ENTER key to display the set value. Press the ⇔CEE **** MODE MODE MODE Operation Displays the operation frequency (operation stopped).
E6581160 4.2.6 Returning all parameters to standard default setting Setting the standard default setting parameter V[R= , all parameters can be returned to the those factory default settings. Note: For more details on the standard default setting parameter V[R, see 5.6. Notes on operation • We recommend that before this operation you write down on paper the values of those parameters, because when setting V[R= , all parameters with changed values will be returned to standard factory default setting.
E6581160 5. Monitoring the operation status Refer to 4.1 about flow of monitor. 5.1 Status monitor mode 5.1.1 Status monitor under normal conditions In this mode, you can monitor the operation status of the inverter. To display the operation status during normal operation: Press the MODE key twice. Setting procedure (eg. operation at 60Hz) Key LED Item displayed operated display 5 Communic ation No. .
E6581160 (Continued) Item displayed Key operated LED display Communic ation No. Description The ON/OFF status of each of the control signal input terminals (F, R, RES, S1, S2, S3, VIB and VIA) is displayed in bits. }}}ii}ii ON: OFF: _ Note 4 Input terminal }}}ii}ii FE06 VIA F VIB R S3 RES S2 S1 The ON/OFF status of each of the control signal output terminals (RY, OUT and FL) is displayed in bits.
E6581160 (Continued) Item displayed Note 7 Key operated Past trip 4 LED display Communic ation No. PGTT ⇔ FE13 Description Past trip 4 (displayed alternately) The ON/OFF status of each of the cooling fan, circuit board capacitor, main circuit capacitor of parts replacement alarm or cumulative operation time are displayed in bits.
E6581160 5.1.2 Display of detailed information on a past trip Details on a past trip (of trips 1 to 4) can be displayed, as shown in the table below, by pressing the key when the trip record is selected in the status monitor mode. Unlike the "Display of detailed trip information at the occurrence of a trip" in 5.2.2, details on a past trip can be displayed, even after the inverter is turned off or reset.
E6581160 5.2 Display of trip information 5.2.1 Trip code display If the inverter trips, an error code is displayed to suggest the cause. Since trip records are retained, information on each trip can be displayed anytime in the status monitor mode. For the kinds of causes that can be indicated in the event of a trip, see section 9.1. 5.2.2 Display of trip information at the occurrence of a trip At the occurrence of a trip, the same information as that displayed in the mode described in 5.1.
E6581160 (Continued) Item displayed Key operated LED display Communic ation No. Description The ON/OFF statuses of the control input terminals (F, R, RES, S1, S2, S3, VIB and VIA) are displayed in bits. Note 4 Input terminal }}}ii}ii FE06 ON: OFF: _ }}}ii}ii VIA F VIB R S3 RES S2 S1 The ON/OFF status of each of the control signal output terminals (RY, OUT and FL) at the occurrence of a trip is displayed in bits.
E6581160 (Continued) Item displayed Key operated LED display Communic ation No. Description The ON/OFF status of each of the cooling fan, circuit board capacitor, main circuit capacitor of parts replacement alarm or cumulative operation time are displayed in bits.
E6581160 Note 9: The cumulative operation time increments only when the machine is in operation. Note 10: At the occurrence of a trip, maximum values are not always recorded and displayed for reasons of detecting time. Note 11: If there is no trip record, nerr is displayed. ✩ Of the items displayed on the monitor, the reference values of items expressed in percent are listed below. • Load current: The current monitored is displayed.
E6581160 6. Measures to satisfy the standards 6.1 How to cope with the CE directive In Europe, the EMC directive and the low-voltage directive, which took effect in 1996 and 1997, respectively, make it obligatory to put the CE mark on every applicable product to prove that it complies with the directives.
E6581160 Table 1 EMC standards Category Emission Immunity Product standards Subcategory Radiation noise Transmission noise Static discharge Radioactive radio-frequency magnetic contactor field First transient burst Lightning surge Radio-frequency induction/transmission interference Voltage dip/Interruption of power Test standard and level EN55011 Class A Group 1 EN55011 Class A Group 1 IEC61000-4-2 IEC61000-4-3 IEC 61800-3 IEC61000-4-4 IEC61000-4-5 IEC61000-4-6 IEC61000-4-11 Emission standards other
E6581160 Three-phase 500V class Inverter VFS11-4004PL VFS11-4007PL VFS11-4015PL VFS11-4022PL VFS11-4037PL VFS11-4055PL VFS11-4075PL VFS11-4110PL VFS11-4150PL Combination of inverter and filter Transmission noise Transmission noise Transmission noise EN55011 Class A Group 1 EN55011 Class B Group 1 EN55011 Class A Group 1 Applicable filters Applicable filters Applicable filters (Length of motor connecting cable: (Length of motor connecting cable: (Length of motor connecting cable: Max. 5 m) Max. 20 m) Max.
E6581160 [Example of wiring] VF-S11 EMC plate (Note 1) FL relay wiring Grounding terminal screw To relay Power supply wiring Control wiring (Shielded cables) Motor wiring (Shielded cables) Braking resistor wiring (Shielded cables) Note 1: Strip and earth the shielded cable, following the example shown in Fig. Shielded cable 6.1.3 Strip the cable and fix it to the metal plate by means of a metal saddle for electrical work or equivalent.
E6581160 EN 50178 applies to electrical equipment intended specially for use in power installations, and sets out the conditions to be observed for electric shock prevention when designing, testing, manufacturing and installing electronic equipment for use in power installations. 6.1.4 Measures to satisfy the low-voltage directive When incorporating the inverter into a machine or system, it is necessary to take the following measures so that the inverter satisfies the low-voltage directive.
E6581160 Q AIC, Fuse and Wire sizes Voltage class Capacity of applicable motor (kW) Single-phase 240V class Inverter model AIC (A) (Interrupting capacity) Fuse class and current (A) Wire sizes of power circuit 0.2 VFS11S-2002PL AIC 1000A CC/J 6A max. AWG 14 0.4 VFS11S-2004PL AIC 1000A CC/J 10A max. AWG 14 0.75 VFS11S-2007PL AIC 1000A CC/J 15A max. AWG 14 1.5 VFS11S-2015PL AIC 1000A CC/J 20A max. AWG 12 2.2 VFS11S-2022PL AIC 1000A CC/J 30A max. AWG 10 0.
E6581160 7. Table of parameters and data For details on the function of each parameter, refer to the full version of English manual (E6581158). 7.1 Title HE 7.2 User parameters Function Operation frequency of operation panel Unit Hz Minimum setting unit Panel/Comm unication 0.1/0.01 Adjustment range User setting Default setting 0.0 NN-WN Reference E6581158 3.2 Basic parameters • Four navigation functions 7 Title Communication No.
E6581160 Minimum setting unit Adjustment range Panel/Commun ication 0: Output frequency 1: Output current 2: Set frequency 3: DC voltage 4: Output voltage command value 5: Input power 6: Output power 7: Torque 8: Torque current 9: Motor cumulative load factor 10: Inverter cumulative load factor 11: PBR (braking reactor) cumulative load factor 12: Frequency setting value (after PID) 13: VIA Input value 14: VIB Input value 15: Fixed output 1 (Output current: 100%) 16: Fixed output 2 (Output current: 50%) 17:
E6581160 7 Title Communication No.
E6581160 7.3 Extended parameters • Input/output parameters 1 Title Communication No.
E6581160 7 Title Communication No.
E6581160 Minimum setting unit Panel/Commun ication 1/1 0-100 Title Communication No.
E6581160 7 Minimum setting unit Adjustment range Panel/Commun ication 0.1/0.01 0.0-30.0 Title Communication No. H 0273 Jumping width 2 Hz H H H 0274 Jump frequency 3 Hz 0.1/0.01 0.0-HJ 0.0 0275 0287 Hz Hz 0.1/0.01 0.1/0.01 0.0-30.0 NN-WN 0.0 0.0 H 0288 Hz 0.1/0.01 NN-WN 0.0 H 0289 Hz 0.1/0.01 NN-WN 0.0 H 0290 Hz 0.1/0.01 NN-WN 0.0 H 0291 Hz 0.1/0.01 NN-WN 0.0 H 0292 Hz 0.1/0.01 NN-WN 0.0 H 0293 Hz 0.1/0.01 NN-WN 0.
E6581160 Title Communication No.
E6581160 • Torque boost parameters 1 Title H Communication No. 0400 Function Auto-tuning Unit - Minimum setting unit Adjustment range Panel/Commun ication 0: Auto-tuning disabled Default setting User setting 0 Reference E6581158 5.11 6.17.
E6581160 • Acceleration/deceleration time parameters Title Communication No.
E6581160 7 Title Communication No.
E6581160 • Output parameters Title Communication No.
E6581160 Title 7 Communication No.
E6581160 Title Communication No. Function Unit % H 0811 H 0812 H 0813 H 0814 H 0829 H 0870 Communication command point 1 setting Communication command point 1 frequency Communication command point 2 setting Communication command point 2 frequency Selection of communication protocol Block write data 1 H 0871 H Minimum setting unit Panel/Commun ication 1/1 0-100 Adjustment range Default setting User setting 0 Hz 0.1/0.01 0.0-500.0 0.
E6581160 Q Default settings by inverter rating XD/H (%) Dynamic braking resistance H (Ω) (Note) Dynamic braking resistor capacity H (kW) Automatic torgue boost value H (%) VFS11S-2002PL VFS11S-2004PL 6.0 6.0 200.0 200.0 0.12 0.12 VFS11S-2007PL 6.0 200.0 VFS11S-2015PL 6.0 75.0 VFS11S-2022PL 5.0 VFS11-2002PM VFS11-2004PM Motor adjustment coefficient H Over-voltage stall protection level H (%) 70 65 90 90 134 134 3.4 60 80 134 6.2 55 70 134 4.1 8.
E6581160 Q Table of input terminal functions 1 Function No.
E6581160 Q Table of input terminal functions 2 7 Function No.
E6581160 Q Table of input terminal functions 3 Function No.
E6581160 Q Table of output terminal functions 2 Function No.
E6581160 Q Table of output terminal functions 3 Function No.
E6581160 8. Specifications 8.1 Models and their standard specifications Q Standard specifications Item Power supply Rating Input voltage Applicable motor (kW) Type Form Capacity (kVA) Note 1) Rated output/current (A) Note 2) Output voltage Note 3) Overload current rating 0.2 2002PM 0.6 1.5 (1.5) 0.4 0.55 2004PM 2005PM 1.3 1.4 3.3 3.7 (3.3) (3.3) Specification 3-phase 240V 0.75 1.5 2.2 4.0 5.5 7.5 VFS11 2007PM 2015PM 2022PM 2037PM 2055PM 2075PM 1.8 3.0 4.2 6.7 10 13 4.8 8.0 11.0 17.5 27.5 33 (4.
E6581160 Note 1. Capacity is calculated at 220V for the 240V models, at 440V for the 500V models and at 575V for the 600V models. Note 2. Indicates rated output current setting when the PWM carrier frequency (parameter F300) is 4kHz or less. When exceeding 4kHz, the rated output current setting is indicated in the parentheses. It needs to be further reduced for PWM carrier frequencies above 12 kHz. The rated output current is reduced even further for 500V models with a supply voltage of 480V or more.
E6581160 Protective function Item Protective function Electronic thermal characteristic Reset function Alarms Causes of failures Display function Monitoring function Past trip monitoring function Output for frequency meter 4-digit 7-segments LED Indicator Environments 8 Use environments Ambient temperature Storage temperature Relative humidity Specification Stall prevention, current limitation, over-current, output short circuit, over-voltage, over-voltage limitation, undervoltage, gr
E6581160 8.2 Outside dimensions and mass Q Outside dimensions and mass Voltage class 1-phase 240V 3-phase 240V 3-phase 500V 3-phase 600V Applicable motor (kW) 0.2 0.4 0.75 1.5 2.2 0.2 0.4 0.55 0.75 1.5 2.2 4.0 5.5 7.5 11 15 0.4 0.75 1.5 2.2 4.0 5.5 7.5 11 15 0.75 1.5 2.2 4.0 5.5 7.
E6581160 Q Outline drawing f5 R2.5 105 8 50 4-M4 D D M5 M5 EMC plate 68 Fig.B 170 W: Width H: Height D: Depth W1: Mounting dimension (horizontal) H1: Mounting dimension (vertical) H2: Height of EMC plate mounting area D2: Depth of frequency setting knob 14 157(Installation dimension) 65 Note 1. To make it easier to grasp the dimensions of each inverter, dimensions common to all inverters in these figures are shown with numeric values but not with symbols.
E6581160 8 .5 R2 220 12 210(Installation dimension) 5 f1 3 160(Installation dimension) 2-R2.5 8 180 170 75 87 VF-S11 M5 4-M4 178 EMC plate Fig.D 9 310 19.5 295(Installation dimension) 7 4 f1 8 R3 225 (Installation dimension) 245 8 2-R3 190 75 94.5 VF-S11 M4 4-M4 198 EMC plate Fig.
E6581160 9. Before making a service call - Trip information and remedies 9.1 Trip causes/warnings and remedies When a problem arises, diagnose it in accordance with the following table. If it is found that replacement of parts is required or the problem cannot be solved by any remedy described in the table, contact your Toshiba dealer.
E6581160 (Continued) Error code QR Failure code 000A Problem Overvoltage during acceleration QR 000B Overvoltage during deceleration QR 000C Overvoltage during constant-speed operation Possible causes • The imput voltage fluctuates abnormally. (1) The power supply has a capacity of 200kVA or more. (2) A power factor improvement capacitor is opened or closed. (3) A system using a thyrister is connected to the same power distribution line.
E6581160 (Continued) Error code 9 QJ G Failure code 002E 0011 Problem External thermal trip Emergency stop GGR 0012 EEPROM fault 1 • An external thermal trip is input. • During automatic operation or remote operation, a stop command is entered from the operation panel or a remote input device. • A data writing error occurs.
E6581160 [Alarm information] Each message in the table is displayed to give a warning but does not cause the inverter to trip. Error code Problem Possible causes Remedies QHH OQHH ST terminal OFF Undervoltage in main circuit • The ST-CC circuit is opened. • The supply voltage between R, S and T is under voltage. TVT[ Retry in process • The inverter is n the process of retry. • A momentary stop occurred.
TOSHIBA TOSHIBA INTERNATIONAL CORPORATION TOSHIBA INTERNATIONAL CORPORATION PTY., LTD 13131 West Little York RD., Houston, TX 77041, U.S.A TEL: +1-713-466-0277 FAX: +1-713-896-5226 2 Morton Street Parramatta, NSW2150, Australia TEL: +61-(0)2-9768-6600 FAX: +61-(0)2-9890-7542 INDUSTRIAL AND POWER SYSTEMS & SERVICES COMPANY TOSHIBA ASIA PACIFIC PTE., LTD OVERSEAS SALES & MARKETING DEPT. ELECTRICAL APPARATUS & MEASUREMENT DIV. 152 Beach Rd.