Dehumidifier User Manual

ClimaDry Whole House Dehumidication - ClimateMaster Geothermal Heat Pumps - Rev.: 18 April, 2008B
2
Notes:
1. ClimaDry reheat option must be ordered with original equipment (cannot be eld added). Unit must have DXM
control. Not available for units with internal water valve, or ow regulator options. Check unit product catalog for
limitations and specic requirements.
2. ClimaDry cannot be used on open loop systems, only closed loop systems.
3. ClimaDry systems must use appropriate antifreeze solutions.
4. ClimaDry is not recommended for applications with poor water quality (see water quality guidelines in unit IOM).
The copper heat exchanger with cast iron pump (standard ClimaDry option) are designed for closed loop sys-
tems.
5. Max working water pressure for the ClimaDry option is 145psig.
6. Available with TT, TS models. Check unit product catalog data nomenclature for models with ClimaDry reheat
option.
7. Thermostat must be either:
1. Thermostat with dehumidication mode (similar to ATA32U02)
2. Thermostat and separate humidistat or dehumidistat controller (see Table 3 for DXM DIP settings).
8. ClimaDry units must have minimum entering air temperature of 70°F DB / 61°F WB
A0 7 2 DG 0 1 D L K
4 5 6 7
8
9 10 12 13 14
026, 038, 049, 064, 072
Unit Size
Return Air Flow Configuration
Voltage
C = CXM
Controls
D = DXM
+
A = Current Revision
Revision Level
Heat Exchanger Options
Cabinet
Supply Air Flow &
Motor Configuration
TT
1 2
TT = Tranquility Two-Stage Scroll
Series
V
3
V = Vertical Up
Configuration
L = Left Return
R = Right Return
0 = None
Water Circuit Options
S
15
S = Standard
Standard
H = Horizontal
D = Vertical Down
0 = Residential
1 = HWG w/Internal Pump
Supply Configuration Motor
K TTV
N TTD
P TTH
W TTH
Top
Down
Back
Straight
ECM
ECM
ECM
ECM
Standard
Coated Air Coil
Copper Cupro-Nickel
A J
Rev.: 18 April, 2008B
ClimaDry
*
D N/A
G = 208-230/60/1
11
Notes
+
= Only Available With ClimaDry Option
*
= Not Available On DownFlow Units
CAUTION!
Water Source Heat Pump systems (including Water Loop Heat Pump systems) must have antifreeze protec-
tion to 20°F [-6.7°C] for ClimaDry applications. The ClimaDry option MUST NOT be used on open water loop
systems, or any system without antifreeze protection.