E6581279⑦ TOSVERT VF-AS1/PS1 PROFIBUS-DP Option Instruction Manual PDP002Z Notice 1. Make sure that this instruction manual is delivered to the end user of the PROFIBUS option for the VF-AS1/PS1. 2. Read this manual before installing or operating the PROFIBUS option for the VF-AS1/PS1. And keep it in a safe place for reference. * The data given in this manual are subject to change without notice. © Toshiba Schneider Inverter Corporation 2005 All rights reserved.
E6581279⑦ Safety precautions On the inverter and in its instruction manual, important information is contained for preventing injuries to users and damages to assets and for proper use of the device. Read the instruction manual attached to VF-AS1/PS1 along with this instruction manual for completely understanding the safety precautions and adhere to the contents of these manuals.
E6581279⑦ ■ General Operation Warning ▼ Never disassemble, modify or repair. Disassembly prohibited Doing so could result in electric shock, fire and injury. For repairs, call your sales agency. ▼Do not attach this option to any inverter other than the VF-AS1/PS1. Prohibited Doing so could result in electric shock or fire. ▼ When the inverter is energized, never detach the this option from the VF-AS1/PS1. Doing so could result in electric shock.
E6581279⑦ ■ Wiring Warning ▼ Shut off power when installing and wiring this option. Mandatory Wait at least 15 minutes and check to make sure that the charge lamp (VF-AS1/PS1) is no longer lit. ▼ Electrical construction work must be done by a qualified expert. Installation or connection of input power by someone who does not have that expert knowledge may result in fire or electric shock.
E6581279⑦ Introduction Thank you for purchasing a “VF-AS1/PS1 PROFIBUS Option (PDP002Z),” for TOSVERT VF-AS1/PS1 inverter. Installing this option in the VF-AS1/PS1 and using it together, data communication can be made with a host computer or other device via PROFIBUS DP (DP-V0). Please read the entire manual carefully before attempting to control your inverter via PROFIBUS connection.
E6581279⑦ Contents 1. OVERVIEW ..............................................................................................................................................6 2. EXTERIOR FEATURES...........................................................................................................................7 2.1. PROFIBUS connector .....................................................................................................................8 2.2. Status indicator ..........................
E6581279⑦ 1. Overview The PDP002Z option allows the VF-AS1/PS1 inverter to be connected as a slave (DP-V0) into a PROFIBUS network. Up to 126 stations* can be connected to the network (* including a master. If no repeater is provided, up to 32 stations can be connected to each segment). VF-AS1/PS1 VF-AS1/PS1 PDP002Z PDP002Z Master (PLC, etc.) Repeater PROFIBUS Maximum connectable units: 126 (In a case like the one above, PLC is included in the count.
E6581279⑦ 2. Exterior features The external view of this option and the name of each part are shown below. Status indicator (Refer to Section 2.2) Panel mounting tabs (Refer to Section 3) Address switch (Refer to Section 4.2) PROFIBUS connector (Refer to Section 2.1) Warning ▼ Do not change the switch setting when the power is on. Prohibited It could lead to electric shocks, or the option might breaks down or get damaged.
E6581279⑦ 2.1. PROFIBUS connector Used to connect PROFIBUS network cables. The connector is a D-Sub connector with 9 pin female and the connector pin allocation described below follows the PROFIBUS standard.
E6581279⑦ 3. Installing the PDP002Z Install the PROFIBUS option to VF-AS1/PS1 as follows: *1 When this option is used together with the IO card option, attach this option to the front panel side. (1) Turn off input power of VF-AS1/PS1 and wait for at least 15 minutes and then check that the CHARGE lamp on VF-AS1/PS1 is no longer lit.
E6581279⑦ (B) For VFAS1/VFPS1 200V 55kW or more, 400V 90kW or more a) Insert a flat-blade screwdriver in each of the two holes at the upper part of the front panel, release the panel mounting tab by pushing the screwdriver down, and remove the front panel cover. b) Push the hooks pointed by the arrows and remove the standard option case. c) Install the option in the inverter by fitting the tabs on the lower side of the option into the slots at the lower part of the inverter front panel.
E6581279⑦ LED name label f) ST DX MNS MNS MNS 4. Connecting to the network 4.1. Installation method (1) Using the DIP switchon the PROFIBUS option, seta station address. (Refer to Section 4.2.) (2) Connect a PROFIBUS connector to the PDP002Z. (Refer to Section 2.1.) * If the PDP002Z is located at an end of the bus, connect a terminal resistor to it. (When using a connector with termination resistor, set it ON.
E6581279⑦ 4.2. Setting a station address The DIP switch on the circuit board of the option is used to set a station address. Each DIP switch is ON when it is flipped to the lower position. By default, it is factory-configured to 2. The station address must be unique and not match any other device on the network.
E6581279⑦ SW ID 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 1 2 3 4 5 6 7 8 OFF ON OFF OFF OFF OFF OFF OFF OFF ON OFF OFF OFF OFF OFF ON OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF ON ON OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF OFF OFF ON OFF ON OFF ON OFF OFF OFF ON ON OFF OFF ON OFF OFF OFF ON ON ON OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF ON OFF ON OFF OFF ON OFF O
E6581279⑦ 5. Communications-related parameters On the network, the VF-AS1/PS1 (including the PDP002Z) serves as a slave device. Using the parameters listed below, set the slave device on the network and its mode of operation. The GSD files used to configure the PDP002Z can be downloaded from the following web site. VF-AS1 http://www.inverter.co.jp/product/inv/vfas1/pdp/ VF-PS1 http://www.inverter.co.
E6581279⑦ 5.1. f851: Communication Loss Action Setting (Network breaks) This parameter sets up the VF-AS1/PS1 response to a loss of communications with the PROFIBUS network. (On some occasions, the master side will need to be configured.) 0: Stop and break of connection The inverter decelerates the motor to a stop and gives the alarm. Commands entered through the network are canceled, and the commands set with parameters cmod and fmod become effective.
E6581279⑦ 5.3. f830: PPO TYPE Setting The PPO type of PDP002Z is set up by this parameter. The PROFIBUS-DP protocol uses so-called PPOs (Parameter/Process Data Objects) in cyclic communication. The figures below show the PPO types and configurations that the PDP002Z supports.
E6581279⑦ 6. PROFIBUS Local/Remote Operation The example below shows how to configure the VF-AS1/PS1 for local / remote operation. F terminal ............ RUN command R terminal............ PROFIBUS/Local (Terminal in this example) switching RR/S4 terminal....
E6581279⑦ 7. Specifications Item Specifications Model number PDP002Z Technical data PROFIBUS DP-V0 PPO TYPE: 1 to 4 by No.3.072 Profile for Variable Speed Drives Connector: D-Sub 9 pin female Station address setting: DIP switch Baud rate: 9.