[Parameter setting]
Title Function Adjustment range Default setting
WXE
Regenerative power ride-through
control selection
:Disabled
:Power ride-through
: Deceleration stop during power failure:
:
Synchronized deceleration/acceleration
(synchronized acceleration/deceleration signal)
:Synchronized deceleration/acceleration
(synchronized acceleration/deceleration
signal+power failure)
H
Non
-
stop
control time/Deceleration
time during power failure
~ sec. 
H Synchronized deceleration time ~ sec. 
H Synchronized acceleration time ~ sec. 
H

Under
voltage
detection
level

~

%
,

:
Automatic mode

H
Regenerative power ride-through control level
~ % 
Note 1: The power ride-through control time when WXE= depends on the setting of H, and the
deceleration time when WXE= depends on the setting of H.
Also, the deceleration time and the acceleration time when WXE= or depend on the setting of
H and that of H, respectively.
Note 2: Even if these functions are used, a motor may coast according to load conditions.
In this case, use the auto-restart function along with this parameter function.
Note 3: These functions do not operate at the time of torque control.
Note 4: Jog run function doesn't operate at synchronized acceleration/deceleration.
Note 5: Although the setting of H can be written when WXE is set to (non-stop control), it cannot be
written when WXE is set to (momentary power failure slowdown stop).
Note 6: For the parameter Hѽ 100% corresponds to 200V (200V class) or 400V (400V class).
An example of setting when WXE=
[When power is interrupted]
Motor speed"
About 100ms$10s
Input voltage
Coasting stop
%&'" Note: If power is interrupted during deceleration stop
, power
ride-through control will not be performed."
Internal DC
voltage level
H
H
Regenerative power
ride-through control selection
[If momentary power failure occurs]
Motor speed
"
Input voltage
"
*1
'"
Note: If power is interrupted during deceleration stop
, power
ride-through control will not be performed.
"
Internal DC"
voltage level
"
H
H
Non-stop control
Normal acceleration
#The time for which the operation of the motor
can be continued depends on the machine
inertia and load conditions. Before using this
function, therefore, perform verification tests.
#Use with the retry function allows the motor to
be restarted automatically without being
brought to an abnormal stop.
*1
*1