Welding System User Manual

E6581301
B-12
2
Terminal
symbol
Input/
output
Function (Sink Source logic)
Electrical
specifications
Inverter internal circuits
P24/
PLC
Output
24Vdc power output (when SW1 is in any
position other than PLC)
24V internal output terminal
24Vdc-200mA -
Input
If SW1 is turned to the PLC position, this
terminal can be used as a common terminal
when an external power supply is used.
- -
CC *1
Common
to input/
output
Digital signal equipotential (0V) terminal for the
control circuit and equipotential (0V) terminal
for an optional control power supply backup.
- -
PP Output Analog input setting power output
10Vdc
(Permissible load
current:10mAdc)
RR/S4 Input
SW3: Multifunction programmable analog input
terminal when SW3 is in the RR position.
Standard default setting:0~10Vdc input and
0~60Hz frequency.
10Vdc
(Internal impedance:30 k)
VI/I I Input
Multifunction programmable analog input.
Standard default setting: 0~10Vdc input and
0~60Hz frequency.
This terminal can also be used as a 4-20mAdc
(0-20mAdc) input terminal, if the parameter
H set to .
10Vdc
(Internal impedance:30 k)
4~20mA
(Internal impedance:242)
RX Input
Multifunction programmable analog input.
Standard default setting:0~±10Vdc input and
0~±60Hz frequency.
10Vdc
(Internal impedance:22 k)
FM Output
Multifunction programmable analog output.
Standard default setting: output frequency
Use this terminal to connect a 1mAdc full-scale
ammeter. This terminal can also be used as a
0-10V (H=) or 0-20mA terminal
(H=), if the SW2 switch is set to
0-10V/0-20mA side.
1mA full
-
scale DC
ammeter (Allowable
load resistance 7.5k or
less) or 7.5Vdc-1mA
full-scale DC voltmeter
0-10V full-scale DC
voltmeter (Allowable
load resistance 500 or
more)/0-20mA (4-20mA)
Full-scale DC ammeter
voltmeter (Allowable
load resistance 500 or
less
)
AM Output
Multifunction programmable analog output.
Standard default setting: output current
Use this terminal to connect a 1mAdc full-scale
ammeter or 7.5Vdc (10Vdc)-1mA full-scale
voltmeter.
1mA full
-
scale DC
ammeter ammeter
(Allowable load
resistance 7.5k or
less) or 7.5Vdc-1mA
full-scale DC
voltmeter
OUT1
Output
Multifunction programmable open collector
output. The default setting is to output a signal
when output low speed threshold has been
reached. Depending on the SW4 setting,
pulses are output with frequencies of 1.00kHz
to 43.20kHz. Standard default setting:3.84kHz
Open collector output
24Vdc-50mA
*Sink logic/source
logic switchable
OUT2
Multifunction programmable open collector
output. By default, it is set to output a signal
indicating the completion of acceleration or
deceleration.
NO
Digital output signal equipotential (0V) terminal
for the control circuit. It is isolated from the CC
terminal.
CCA
*1
Common
to input/
output
Analog input/output signal equipotential (0V)
terminal for the control circuit.
- -
*1: Although the CC terminal and the CCA terminal are not insulated, they should be used separately, one for the logic circuit and
the other for the analog circuit
!
P15
!
15k
!
7k
!
!
P5
!
15k
!
15k
!
242
!
S4
!
P5
!
RR
!
SW3
!
12.7k
!
2.2k
!
15k
!
!
SW2
!
+
!
-
!
+
!
-
!
4.7k
!
120
!
70
!
0
-
1
mA
!
0-20mA
!
0-10V
0-20mA
!
0-10V
4.7k
+
-
!
20
P24
OUT1
OUT2
SW4 PULS
LO
20
NO
!
15V
!
Constant
voltage
circuit
!