User's Manual
30
4.14 LOCK 210, LOCK 250 AND LOCK 500 -
DIGITAL IN/OUT PORT WITH 24V DC OUT
The Digital I/O port is equipped with a removable plug-in connector
included in the sales package. Remove the connector if needed
and in case of a solid wire simply insert the stripped signal wire
to the correct port opening. In case a flexible wire is used, press
the release button with a flat blade screwdriver to open the
locking springs and insert the wire. Follow the signal symbols
in the front panel and connect all needed signals. Make sure the
connector is completely plugged in and secure the connector into
the Lock frame by tightening the locking screws with a flat blade
screwdriver. The wires with a cross-section of up to 1.5 mm
2
(AWG 16) can be used with the connector. The stripping length of
the conductor is 10 mm. The wire is released from the connector
by pushing the corresponding release button with a flat blade
screwdriver.
4.15 LOCK 210, LOCK 250 AND LOCK 500 -
SOFTWARE CONFIGURABLE I/O
The Digital I/O state information and configuration can be
accessed from Settings -> Digital I/O menu. For signal physical
properties, please refer to section I/O specifications at the end of
this manual.
Input port roles can be selected from:
Not selected – no action based on port state
Allow Internet connection – when port voltage is set high, Lock
allows Internet connections. When port voltage is set low, there
is no Internet access and the Lock visibility is “offline” for all Keys
matched with it.
Prevent Internet connection – when port is set high, Lock
prevents Internet connection and the Lock visibility is “offline” for
all Keys matched with it. When port voltage is low, Internet access
is allowed.
Allow VPN connections – when port voltage is set high, Lock allows
incoming VPN connections from matched Keys. When port voltage
is low, VPN connections are not allowed and the Lock visibility is
“offline” for all Keys matched with it.
Prevent VPN connections – when port is set high, VPN connections
are not allowed and the Lock visibility is “offline” for all Keys
matched with it. When port voltage is low, Lock allows incoming
VPN connections from matched Keys.