Submittal

Submittal Data: TW18HQ2C2D
18,000 BTU/H (208/230V) Wall Mounted Heat Pump System
Job Name Location Date
Purchaser Engineer
Submitted To For
Unit Designation Schedule No.
GENERAL FEATURES
-Compact and Quiet Design
-High Efficiency DC Inverter Technology
-Vertical Swing Louver
-Wireless Remote with LCD Display
-XK-41 Wired Tether Controller ( Sold Separately)
-Low Ambient Cool to 0 deg F
-Blue Fin Condenser Coil
-5 year Limited Parts Warranty
-7 year Limited Compressor Warranty
Cooling
Fan Motor
Type Cross-Flow
Rated Capacity 18,000 BTU/H Output Power 60 W
Capacity Range 6,800-20,000 BTU/H FLA 0.24 A
Power Input (Max) 2,600 W
Airflow
SEER 20.0
Cooling Wet (Lo/Hi)
335/559 CFM
EER 12.5
Heating Dry (Lo/Hi)
335/559 CFM
Heating at 47° F
Rated Capacity 19,800 BTU/H Sound Pressure Level
Capacity Range 7,340-23,500 BTU/H
Cooling (Min/Max)
39/47 db(A)
Power Input (Max) 2,600 W
Heating (Min/Max)
39/47 db(A)
HSPF 11.0
COP 4.7 Dehumidification 3.80 pt/hr
Heating at 17° F
Rated Capacity 12,400 BTU/H
Compressor Type DC Inverter Driven Rotary
Operating Range
RLA 12.1 A
Cooling (Max)
115 (46 C)
(Min)
0 (-18 C) Refrigerant Type R410A
Heating (Max)
75 (24 C) Fan Motor Output Power 60 W
(Min)
-4 (-20 C) FLA 0.49 A
Gas Pipe Size (OD) 5/8-in Sound Pressure
Liquid Pipe Size (OD) 1/4-in Cooling/Heating 55/55 db(A)
Connection Method Flared
Factory Charge 56.4 oz Power Supply
Additional Charge 0.54 oz
Normal Operational Voltage
208/230 V, 1 Phase, 60 Hz
Pre-Charge Length 25-ft
Voltage Range
187 - 253 V
MAX Refrigerant Pipe Length 82-ft
MCA
16.0 A
MIN Refrigerant Pipe Length 10-ft
MOCP/Breaker Size
25 A
MAX Refrigerant Pipe Elevation 33-ft
Main Power Wire Size
10-2 AWG
Outdoor Unit Data
Indoor Unit Data
System Ratings
Refrigerant Piping Data
Electrical Data
Reference
Approval
Construction
All Rights Reserved
TOSOT Comfort 2017