Installation Instructions
TowerIQ, Inc | 1609 Park 370 Place, Hazelwood, MO 63042| 844‐626‐7638 | cs‐guardian@tower‐iq.com
14
2.12 Alarm
LEDs
INSIDE BDA ALARM INTERFACE OUTSIDE TYPE 4 ALARM INTERFACE
Status Description
1 AC Power Normal
Green ON AC Power is working properly
OFF
2
AC Power Loss /DC Power
Switchover
Red ON AC Power is not working, and BDA has switched to DC Power.
OFF
3
Donor Antenna Malfunction
Red ON Connection to the donor antenna has been interrupted or is not
present. Possible bad connector or cable termination.
OFF
4
RF Malfunction /Oscillation
Detected
Red ON RF emitting device can’t function because oscillation is happening,often
caused by indoor and outdoor antennas being too close.
OFF
5
System Component
Malfunction /BDA Failure
Red ON Some system components failing. Overpowering has occurred.
Off
6 Silencing (button)
If the trouble is triggered, press this button to silence the audible alarm. It needs to be
pressed once every 22 hours when it’s in silencing position or the booster will sound.
Note: Dedicated building annunciation should be provided to indicate DC loss or low DC secondary power source. Secondary power source
annunciator needs to be installed adjacent to the BDA system and the BDA shall be located in close proximity to the FACP. Please refer to the
wiring instruction provided by the secondary power source.