Installation Manual

12
Smart PoE+ Switch
Lightning Protection
Cable Pave Way
Min Parallel
Length (mm)
2 to 5kVA
powerline
Parallel cabling 300
One is in the grounded metal raceway or metal pipe 150
The both are in the grounded metal raceway or metal
pipe
80
>5kVA
powerline
Parallel cabling 600
One is in the grounded metal raceway or metal pipe 300
The both are in the grounded metal raceway or metal
pipe
150
Device Min Distance (m)
Switch case 1.00
Transformer room 2.00
Elevator tower 2.00
Air-conditioner room 2.00
3.2 Connect to Ground
Connecting the device to ground is to quickly release the lightning over-voltage and
over-current of the device, which is also a necessary measure to protect the body
from electric shock.
In different environments, the device may be grounded differently. The following
will instruct you to connect the device to the ground in two ways, connecting to
the grounding bar or connecting to the ground via the power cord. Please connect
the device to ground in the optimum way according to your specific operation
environment.
Note: For the device without grounding terminal, please refer to the first way
Connecting to the Ground via the Power Supply only.
Connecting to the Ground via the Power Supply
If the device is installed in the normal environment, the device can be grounded via
the PE (Protecting Earth) cable of the AC power supply as shown in the following
figure.