Datasheet
Isolation Test Voltage
- Input to Output, 60 s
3'000 VAC
- Input to Case or PE, 60 s
1'500 VAC
- Output to Case or PE, 60 s
500 VAC
Creepage
- Input to Output
7 mm min.
- Input to Case or PE
4 mm min.
- Output to Case or PE
1 mm min.
Clearance
- Input to Output
5 mm min.
- Input to Case or PE
2.5 mm min.
- Output to Case or PE
0.5 mm min.
Isolation Resistance
- Input to Output, 500 VDC
100 MΩ min.
Isolation Capacitance
- Input to Output, 100 kHz, 1 V
1'120 pF typ.
Leakage Current
- Earth Leakage Current
500 µA max.
- Touch Current
100 µA max.
Reliability
- Calculated MTBF
(see application note)
Environment
- Vibration
IEC 60068-2-6
1 g, 3 axis, sine sweep, 10-55 Hz, 1 oct/min
- Mechanical Shock
IEC 60068-2-27
10 g, 3 axis, half sine, 11 ms
20 g, 3 axis, 3 shocks
Housing Type
Open Frame
Mounting Type
Chassis Mount
Connection Type
Pin Connector
Weight
170 g
Power Back Immunity
3.3 VDC model:
5 VDC max. (6 VDC for 1 s)
5 VDC model:
6.3 VDC max. (7 VDC for 1 s)
12 VDC model:
16 VDC max. (18 VDC for 1 s)
15 VDC model:
20 VDC max. (23 VDC for 1 s)
24 VDC model:
35 VDC max. (40 VDC for 1 s)
48 VDC model:
63 VDC max. (68 VDC for 1 s)
Environmental Compliance
- REACH Declaration
www.tracopower.com/info/reach-declaration.pdf
REACH SVHC list compliant
REACH Annex XVII compliant
- RoHS Declaration
www.tracopower.com/info/rohs-declaration.pdf
Exemptions: 7a, 7c-I
(RoHS exemptions refer to the component
concentration only, not to the overall
concentration in the product (O5A rule).)
- SCIP Reference Number
14dcee4b-8b62-447f-a548-9bdfc3eceaa4
Supporting Documents
Overview Link (for additional Documents)
www.tracopower.com/overview/top100
TOP 100 Series, 100 Watt
All specifications valid at nominal voltage, resistive full load and +25°C after warm-up time, unless otherwise stated.
www.tracopower.com September 20, 2023
Page 4 / 5