Datasheet

http://www.tracopower.com Page 4 of 11
TSP–REM360 Redundancy Module
Industrial Power Supplies
TSP-WR Series 180–600 Watt
With this module and two power supplies of the TSP-WR series (of same type) a
highly reliable, true redundant power system can be configured without any addi-
tional components. This module enforces equivalent sharing of the output current
by each power supply. The system is fully redundant and provides output power
even if one power supply has completely failed e.g. by short circuit on the output. In
the event of either power supply failing or being disconnected, the second unit will
automatically supply the full current to the load. The redundancy of the system is
monitored and if lost, indicated by an alarm output. The inputs are hot swappable
and can be loaded up to 15A each.
Order Code
(includes terminal plugs)
Input Max Power
per Input
Output Voltage
adjust.
Output Power
max.
TSP–REM360
2 x 24 VDC
2 x 360 W
24 VDC
360 W
TSP–REM600
2 x Control input
2 x 600 W
(24 - 27 VDC)
600 W
Models
Function Diagram Connector Positions
REM Controller
TSP
TSP
Volt adjust
Output
Load
Alarm
DC IN 1
+
_
J1.2
J1.1
J3.1
J3.2
DC IN 2
+
_
J1.4
J1.3
J4.1
J4.2
J5.1 J5.2
J2.2
J2.1
J2.4
J2.3
+
_
Remote
Link 2
Redundancy
ok
Remote
Link 1
Remote On/Off
J5.3 J5.4
Power
Supplies
Front viewBottom vie
wT
op view
Output
- -
+ +
DC IN 1
-
+
-
+
DC IN 2
Remote Link 1
Remote Link 2
Alarm
Remote On/Off
Specifications
Operating temperature 25°C to +7C max.
derating above +40°C :1.5 %/K
Electromagnetic compatibility in correspondence to connected units (no internal swit
ching device)
Redundancy OK signal (Alarm) trigger threshold at 1822VDC,
contact open if both inputs failed
Dimensions see page 8
Remote link cable (0.5m) 2 cables included (order code TSP-JC)
www.tracopower.com/products/tsp-rc-cable.pdf
Remote On/Off by ext. contact: contact open = On, contact closed = Off
Installation instructions www.tracopower.com/products/tsp-rem_inst.pdf