Thermostat User Manual
BMTK-SVN01D-EN 15
®
Chapter 2
Termination module 
mounting 
After unpacking and inspecting the shipment, mount the termination 
module. The mounting process for the termination module consists of 
selecting a location and mounting the module. This chapter provides 
information and procedures that enable you to mount the termination 
module.
Select a location for the controller
When selecting a location for the Tracker controller:
• Select a location that is in a clean, non-corrosive, indoor environment. 
The controller is only intended for indoor installation. 
• Consider both security and control wire lengths when making the 
selection. 
• Select a location that limits controller access to operating and service 
personnel. 
• Select a location that conforms to the operating environment 
described in Table 1 on page 9. The recommended operating environ-
ment will extend the life of the electronic components. Verify that the 
location does not subject the controller to extreme operating condi-
tions (including excessive vibration). 
CAUTION
Avoid Equipment Damage!
Install the Tracker controller out of direct sunlight. Failure to do so may 
cause overheating, which could result in equipment damage.
IMPORTANT
Do not install the Tracker controller near high-power radio signals, elec-
trical switching gear, power buses, large motors, or other sources of 
electrical noise. The electrical interference may lead to control malfunc-
tions.
Verify location conformance to controller specifications
Verify that the selected location conforms to the applicable controller 
specifications listed in Table 1 on page 9.