Thermostat User Manual
BMTK-SVN01D-EN 65
®
Appendix A
Installation checklists
Required supplies
Table 15 lists the supplies required for all Tracker installations.
Optional supplies
Table 16 lists the supplies that may or may not be necessary, depending 
on the Tracker installation.
Table 15. Required supplies checklist
;
Wiring installation  Item
24 Vac
18 AWG (1.02 mm
2
) wire recommended
24 Vac, 40 VA minimum transformer
 Comm Communication wire (see Table 7 on page 30 
and Table 8 on page 31 for specifications)
Table 16. Optional supplies checklist
;
Inputs/output 
wiring installation
Item
 Alarm relay wiring
18 AWG (1.02 mm
2
) wire and metal conduit
 Priority shutdown 
wiring and 
Meter input
18—22 AWG (1.02 mm
2
—0.643 mm
2
) wire and 
metal conduit
 Thermistor wire
18—22 AWG (1.02 mm
2
—0.643 mm
2
) twisted 
pair, shielded wire
 Alarm relay power 
supply
Power supply for alarm relay output (not to 
exceed 24 Vac)
 Alarm relay output 
load
Load for alarm relay output (not to exceed 
1 amp at 24 Vac)
 Thermistor Outdoor air temperature sensor