Pre-installation wiring notes
BMTK-SVN01D-EN 69
®
Pre-installation wiring notes
The wiring for the Tracker system will have been completed prior to 
Tracker installation. All Tracker wiring conforms to the following 
guidelines: 
• The Tracker controller receives 24 Vac from a dedicated power circuit. 
If not, the Tracker controller may malfunction. 
• Each UCM receives 24 Vac from a dedicated power source. If not, the 
UCM may malfunction. 
• Input wires and ac power wires are run in separate conduits or wire 
bundles. If not, the Tracker controller may malfunction due to 
induced electrical noise. 
• Comm5 cable and ac power wires are run in separate conduits or wire 
bundles. If not, the Tracker controller may malfunction due to 
induced electrical noise. 
• UCM communication cables do not run near lighting ballasts or other 
transformers. If they do, the UCM may malfunction due to induced 
electrical noise. 