User Guide Tracer CH530™ Chiller Control System CGWN/CCUN 205-211 CGAN 209-214 CG-SVU02B-E4
General information Foreword Warnings and cautions Reception These instructions are given as a guide to good practice in the installation, start-up, operation, and maintenance by the user, of Trane CH530 chiller control system on CGWN/CCUN and CGAN 209-214 chillers. They do not contain full service procedures necessary for the continued successful operation of this equipment.
General information Warranty Training Warranty is based on the general terms and conditions of the manufacturer. The warranty is void if the equipment is repaired or modified without the written approval of the manufacturer, if the operating limits are exceeded or if the control system or the electrical wiring is modified. Damage due to misuse, lack of maintenance or failure to comply with the manufacturer's instructions or recommendations is not covered by the warranty obligation.
Contents General Information 2 Overview 5 DynaView Interface 6 Display Screens TechView Interface 4 6 19 Software Download 20 Diagnostics 22 CG-SVU02B-E4
Overview The Trane CH530 control system that runs the chiller consists of several elements: • The main processor collects data, status, and diagnostic information and communicates commands to the LLID (for Low Level Intelligent Device) bus. The main processor has an integral display (DynaView). • LLID bus. The main processor communicates to each input and output device (e.g.
DynaView Interface The display on DynaView is a 1/4 VGA display with a resistive touch screen and an LED backlight. The display area is approximately 4 inches wide by 3 inches high (102mm x 60mm). CAUTION! Equipment Damage! Putting excessive pressure on the touch screen could cause damage. It takes less than 7 kg of force to break the screen. In this touch screen application, key functions are determined completely by software and change depending upon the subject matter currently being displayed.
DynaView Interface The bottom of the screen (7) is present in all screens and contains the following functions. The contrast (8,9) may require re-adjustment at ambient temperatures significantly different from those present at last adjustment. The other functions are critical to machine operation. The AUTO and STOP keys are used to enable or disable the chiller. The key selected is in black (reverse video). The chiller will stop when the STOP key is touched and after completing the Run Unload mode.
DynaView Interface Main Screens The Main screen shall be the default screen. After an idle time of 30 minutes the CH530 shall display the Main screen with the first data fields. The remaining items (listed in the following table) will be viewed by selecting the up/down arrow icons.
DynaView Interface Figure 4 - Main screen menu, Chiller Operating Modes - Sub Level Back Chiller Mode: Running Maximum Capacity Capacity Control Softloading Ice Building Auto Stop Figure 5 - Main screen menu, Chiller Operating Modes - Sub Level Back Circuit 1 Mode: Running - Limit Low Evaporator Pressure Start Auto CG-SVU02B-E4 Stop 9
DynaView Interface Table 1 - Main screen menu, Chiller Operating Modes - Top Level Chiller Level Mode Top Level Mode Description MP Resetting The main processor is going through reset. MP Resetting Sub Modes Description No Chiller Sub-Modes Chiller Level Mode 10 Top Level Mode Description Stopped The chiller is not running either circuit, and cannot run without intervention.
DynaView Interface Chiller Level Mode Top Level Mode Description Run Inhibit The chiller is currently being inhibited from starting (and running), but may be allowed to start if the inhibiting or diagnostic condition is cleared. Run Inhibit Sub Modes Description Ice Building Is Complete The chiller is inhibited from running as the Ice Building process has been normally terminated on the evaporator entering temperature.
DynaView Interface Chiller Level Mode Top Level Mode Description Waiting to Start The chiller is going through the necessary steps to allow the lead circuit to start. Waiting to Start Sub Modes Description Waiting For Condenser Water Flow The chiller will wait a user adjustable time in this mode for condenser water flow to be established per the flow switch hardwired input. Chiller Level Mode Top Level Mode Description Running At least one circuit on the chiller is currently running.
DynaView Interface Chiller Level Mode Top Level Mode Description Shutting Down The chiller is still running but shutdown is imminent. The chiller is going through a compressor run-unload. Shutting Down Sub Modes Description Evaporator Water Pump Off Delay: MIN:SEC The Evaporator pump is executing the pump off delay timer. Condenser Water Pump Off Delay: MIN:SEC The Condenser pump is executing the pump off delay timer. Chiller Level Mode CG-SVU02B-E4 Top Level Mode Description Misc.
DynaView Interface Table 2 - Circuit Level Operating Modes: Circuit Level Mode Top Level Mode Description Stopped The circuit is not running, and cannot run without intervention. Stopped Sub Modes Description Diagnostic Shutdown - Manual Reset The circuit has been shutdown on a latching diagnostic. Front Panel Circuit Lockout The circuit is manually locked out by the circuit lockout setting - the nonvolatile lockout setting is accessible through either the DynaView or TechView.
DynaView Interface Circuit Level Mode Top Level Mode Description Running - Limit The compressor on the given circuit is currently running in a limit mode. Running - Limit Sub Modes Description Hot Start Limit Additional stages on a given circuit are being held off based on leaving evaporator temperature. Condenser Pressure Limit The circuit is being inhibited from loading due to high condenser pressure.
DynaView Interface Reports Screen Figure 6 - Reports screen The Reports tab will allow a user to select from a list of possible reports headings. Each report will generate a list of status items as defined in the following tables. Main Reports Settings Evaporator Condenser Compressor Chiller Log Auto Stop Alarms Table 3 - Reports screen Description Units Resolution Evap Entering Water Temp Temperature + or -XXX.X Evap Leaving Water Temp Temperature + or -XXX.
DynaView Interface ASHRAE Chiller Log Current Time/Date Date / Time Chiller Mode Text XX:XX mmm dd, yyyy Active Chilled Water Setpoint Temperature XXX.X Evap Entering Water Temp Temperature XXX.X Evap Leaving Water Temp Temperature XXX.X Evap Water Flow Switch Status Text Cond Entering Water Temp Temperature XXX.X Cond Leaving Water Temp Temperature XXX.X Cond Water Flow Switch Status Text Outdoor Air Temp Temperature XXX.
DynaView Interface Settings Screen The Settings screen provides a user the ability to adjust settings justified to support daily tasks. The layout provides a list of sub-menus, organized by typical subsystem. This organization allows each subscreen to be shorter in length which should improve the users navigation.
DynaView Interface Feature Settings Chilled Water Reset Text (Constant, Outdoor, Return, Disable), Disable Return Reset Ratio Percent XXX Return Start Reset Temperature XXX.X Return Maximum Reset Temperature XXX.X Outdoor Reset Ratio Percent XXX Outdoor Start Reset Temperature XXX.X Outdoor Maximum Reset Temperature XXX.
DynaView Interface Diagnostics Screen The diagnostic screen is accessible by depressing the Alarms enunciator A scrollable list of the last (up to 20) active diagnostics will be presented. Performing a Reset All Active Diagnostics will reset all active diagnostics regardless of type, machine or refrigerant circuit. Compressor diagnostics, which hold off only one compressor, will be treated as circuit diagnostics, consistent with the circuit to which they belong.
TechView Interface TechView is the PC (laptop) based tool used for servicing Tracer CH530. Technicians that make any chiller control modification or service any diagnostic with Tracer CH530 must use a laptop running the software application "TechView." TechView is a Trane application developed to minimize chiller downtime and aid the technicians' understanding of chiller operation and service requirements.
TechView Interface Software Download Instructions for First Time TechView Users This information can also be found at http://www.trane.com/commercial/s oftware/tracerch530/. 1. Create a folder called "CH530" on your C:\ drive. You will select and use this folder in subsequent steps so that downloaded files are easy to locate. 2.
TechView Interface 6. Select the product family. A table with the download link will appear for that product family. 7. Download the main processor software onto your PC in the CH530 folder (please note that this does not install the main processor, it only downloads the installation utility). • To do this, click on the latest version of the main processor. • Select "Save this program to disk" while downloading the files (do not select "Run this program from its current location"). 8.
Diagnostics The following diagnostic table contains all the diagnostics possible. Not all data is available unless tech view is connected. Code: Three digit hexadecimal code used on all past products to uniquely identify diagnostics. Diagnostic Name: Name of Diagnostic and its source. Note that this is the exact text used in the User Interface and/or Service Tool displays. Severity: Defines the severity of the above effect.
Diagnostics Table 5 - Main Processor Diagnostics Diagnostic Name Effects Severity Persistence Active Modes [Inactive Modes] MP: Reset Has Occurred Chiller Warning NonLatch All Low Pressure Cutout Circuit Immediate Latch Starting and Running [Stop, See criteria] The suction refrigerant pressure (gauge) fell below the given threshold for the refrigerant installed: • 0.7 bar for R22 and R407c • 0.3 bar for R134a • 1.
Diagnostics Evaporator Entering Water Temp Sensor Chiller Normal Latch All Bad Sensor or LLID Remote Evaporator Leaving Water Temp Sensor Chiller Normal Latch All Bad Sensor or LLID Remote Condenser Entering Water Temp Sensor Chiller Warning Latch All Bad Sensor or LLID Remote Condenser Leaving Water Temp Sensor Chiller Warning Latch All Bad Sensor or LLID Remote Discharge Pressure Transducer Circuit Normal Latch All Bad Sensor or LLID Remote Suction Pressure Transducer C
Diagnostics High Evaporator Water Temperature Chiller Immediate NonLatch All The evaporator leaving water temperature is above 46°C. This diagnostic shall clear once the evaporator leaving water temperature falls below 43.3°C. This diagnostic protects the rupture disk. The evaporator water pump shall not run when this diagnostic is active. Local High Pressure Cutout Circuit Immediate Latch All The high pressure cutout switch was open for more than one second.
Diagnostics Evaporator Water Flow Lost Pump 1 (or Pump 2) Chiller Warning and Special Action NonLatch Evaporator Water Flow Overdue Pump 1 (or Pump 2) Chiller Warning and Special Action NonLatch Fault Detected: Evaporator Water Pump 1 (or Pump 2) Chiller Warning and Special Action NonLatch All Condenser Water Flow Lost Pump 1 (or Pump 2) Chiller Warning and Special Action NonLatch Condenser Water Flow Overdue Pump 1 (or Pump 2) Chiller Warning and Special Action Fault Detected: Condenser
Diagnostics Table 6 - Communication Diagnostics Notes: 1. The following communication loss diagnostics will not occur unless that input or output is required to be present by the particular configuration and installed options for the chiller. 2. Communication diagnostics (with the exception of "Excessive Loss of Comm" are named by the Functional Name of the input or output that is no longer being heard from by the Main Processor.
Diagnostics Comm Loss: Suction Pressure Transducer Circuit Immediate Latch All Continual loss of communication between the MP and the Functional ID has occurred for a 35-40 second period. Remote Comm Loss: Ext Chilled/Hot Wtr Setpoint Chiller Warning and Special Action Latch All Continual loss of communication between the MP and the Functional ID has occurred for a 35-40 second period.
Diagnostics Comm Loss: Condenser Fan Control Relays Circuit Immediate Latch All Continual loss of communication between the MP and the Functional ID has occurred for a 35-40 second period. Remote Comm Loss: Fan Fault Chiller Warning Latch All Continual loss of communication between the MP and the Functional ID has occurred for a 35-40 second period.
Diagnostics Comm Loss: Suction Temperature Circuit Normal Latch All Continual loss of communication between the MP and the Functional ID has occurred for a 35-40 second period. Remote Comm Loss: Compressor Staging Relay Circuit Normal Latch All Continual loss of communication between the MP and the Functional ID has occurred for a 35-40 second period.
Diagnostics A Valid Configuration is Present A valid configuration is present in the MP's nonvolatile memory. The configuration is a set of variables and settings that define the physical makeup of this particular chiller. These include: number/airflow and type of fans, number/and size of compressors, special features, characteristics, and control options. Temporary display of this screen is part of the normal power up sequence.
Diagnostics Programmable Relays (Alarms and Status) CH530 provides a flexible alarm or chiller status indication to a remote location through a hard wired interface to a dry contact closure. Four relays are available for this function, and they are provided (generally with a Quad Relay Output LLID) as part of the Alarm Relay Output Option. The events/states that can be assigned to the programmable relays are listed in the following table and through a TechView configuration.
Notes CG-SVU02B-E4 35
Literature Order Number CG-SVU02B-E4 Date 0805 New CG-SVU02A_0405 Literature Stocking Location Europe www.trane.com Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform the installation and servicing of equipment referred to in this publication. For more information, contact your local sales office or e-mail us at comfort@trane.